Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.8 LAccepted-Finance | ₹10.8 L | L1 | Accepted-Finance Lowest Bidder |
| 2 | L2₹11.2 L+₹40,772 (3.78%)Rejected-Finance 315 KUMARAN NAGAR MAIN ROAD NATHAM KUNRATHUR KANCHIPURAM TAMIL NADU 600069 | KANCHIPURAM | TAMIL NADU | 600069 | ₹11.2 L+₹40,772 (3.78%) | L2 | Rejected-Finance L2 |
| 3 | L3₹15.8 L+₹5.0 L (46.4%)Rejected-Finance NEW NO 5A OLD NO 80 53RD STREET ASHOK NAGAR CHENNAI TAMIL NADU 600083 | CHENNAI | TAMIL NADU | 600083 | ₹15.8 L+₹5.0 L (46.4%) | L3 | Rejected-Finance L3 |
Tender Value
₹13.7 L
EMD Value
₹27,389
Closing Date
27 May 2026, 3:00 pmClosed
DVP(FM)
HLL Infra Tech Services Ltd.HLL Bhavan, Poojappura, Trivandrum
Setting up of Cleanroom Facility for Heart Transplant ICU in Super Speciality Block (SSB), JIPMER, Puducherry
2026_HITE_276745_1
HITES/FM/JIPMER/AC/2025-26/08
Open Tender
Miscellaneous Works
Works
90 days
Puducherry
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
HLL Infra Tech Services Ltd
₹27,389
Yes
8 Jul 2026
7 May 2026
28 May 2026
7 May 2026
27 May 2026
7 May 2026
7 May 2026 - 16 May 2026
Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). - Inverter Type - Cooling only
2 TR 5 star rated as per BEE
Supply, installation, testing and commissioning of copper refrigerant piping with 13 mm thick nitrile rubber insulation interconnecting the Condensing unit to evaporating unit for split units as per site condition
Copper refrigerant piping for 2 TR Cassette unit of suitable size 5/8" & 3/8".
Voltage Stabilizer 5 KVA rating suitable for 2TR Cassette AC Units with Overcurrent & Under voltage protection. (The input voltage is 230V ± 10% AC 50 c/s)
Supply and installation of 20A-25A 3 pin metal clad plug and socket with 20A-25A MCB with suitable powder coated sheet steel enclosure with fixing accessories etc
Supply and installation of PVC drain pipe with 6mm nitrile rubber insulation ISI marked, connecting the drain lines from the indoor units to floor sump to be concealed or to be laid as per site required with as may be decided by Engineer-in-charge.
Dismantling and Modification of Existing ducts of various size, collars, elbows, gaskets, hangers, supports etc. as required
Supplying, installation, testing and commissioning of Exhaust Inline fan of 600 CFM capacity. The work includes making holes in walls by making smooth cement finish etc., as required
Supplying, installation, testing and commissioning of External thermal insulation on supply air ducts using min 9mm thick nitrile rubber class"O"closed cell type with anti microbial protection as per specifications
Ceiling Suspended Fan Filter Unit:Supply & Fixing of ceiling suspended type fan filter unit made up of GI sheet with powder coated finish construction. The fan filter unit consists of inbuilt blower with motor, 0.3 micron HEPA filter and GI perforated grilles with the provisions for suspending from the ceiling. The blower is design to provide 90 to 120 FPM of air velocity. a) For Ante Room: Dim : L 4'0" x W 2'0" x H 2'0", Capacity : 700 CFM - 900 CFM / Unit. - 1 No. b.) for Transplant ICU: ( 250 Sq.ft) Dim : L 4'0" x W 2'0" x H 2'0", Capacity : 700 CFM - 900 CFM / Unit - 5 Nos
Inbuilt - Return Air Riser Panel : Supply & Fixing of return air riser panels made up of 1.2 mm thick GI sheet. The return air riser duct is inserted into the "PUF" wall panels and laid along with wall panels. It has the provision to connect the flexible hose and dampers. Dim : W 540 mm x H 2800 mm - 14 Nos
Flexible Hose: Supplying & Fixing of insulated flexible hose between return air riser and fan filter unit. Dia : 10 inches
GI Butterfly dampers: Supply & Fixing of GI butterfly dampers in the return air riser panel collar and fan filter unit collar in order to adjust the volume of Air. Dia : 10 inches
Pre Filter & SS304 diffuser for Return air riser: Supply & Fixing of 10 micron pre filter and SS304 perforated diffuser in the return air riser panel. Dimension : W 1'6" x H 2'0"
Walkable steel panel false ceiling: Supplying & fixing of 50mm thick double skin .PUFF panel false ceiling. The inner and outer skin of the panel is PPGI or PCGI sheet of 0.5 mm thick. The density of the PUFF is 38+-2 kg/m3. The rate is includes of L angles, Screws and sealant etc. Color : RAL 9002 and Type : Tongue & Groove.
Supplying and Fixing of Electrical Control panels to Turn ON/OFF the Fan filter units which includes Electrical cabling from control panels to FFU's.
PUF Infilled steel wall panel partition: Supply & fixing of 50mm thick double skin "PUFF" panel partition. The inner and outer skin of the panel is PPGI or PCGI sheet of 0.5 mm thick. The density of the PUFF is 38+-2 kg/m3. The rate is includes of C angles, Screws and sealant etc., Color : RAL 9002 and Type : Tongue & Groove , Height - 2.5 Mtr
Steel powder coated "PUF" infilled door : Supply & fixing of steel powder coated "Honeycomb" infilled door made up of GI sheet with powder coated finish. The sheet thickness for the frame is 1.2 mm and the sheet thickness for the shutter is 0.8 mm. The rate shall inclusive of door closer, D handle, Lock and SS304 BUTT hinges and double glazing view glass of size W 300 x H 600 mm with the provision for drop seal. Dim : W 1500 x H 2100 mm - Double Leaf Door - Equal Shutter
Validation & Documentation charges : Charges towards the validation and documentation of the below paramaters like particle count, ACPH, Air Velocity, Air Flow pattern & Recovery Test , HEPA Integrity etc.,
Air Curtain with Limit Switch: Supplying & Fixing of air curtains with automatic On/Off (Limit switch) while opening and closing the doors of each cleanrooms. Dimension: 1220 x 225 x 225 mm. Model : High Velocity series
Miscellaneous Charges: Charges towards the packing, loading, freight of materials and unloading at the site as required.
Supplying, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps, collars etc as required complete in all respect in confirmation with IS : 655 and approved drawings and specifications of following sheet thickness complete as required.
Supplying, Fixing, installation, testing and commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core in confirmation to SMACNA/IS and as per specifications complete etc. as required
No Rupees Only
No Rupees Only
No Rupees Only
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.07 MB
Vol 1 NIT.pdf
Tender Documents • 0.49 MB
Vol 2 GCC.pdf
Tender Documents • 1.37 MB
Vol 3 SCC.pdf
Tender Documents • 4.64 MB
Vol 4 TS.pdf
Tender Documents • 0.45 MB
BOQ_2.xls
Tender Documents • 0.15 MB
NIT.pdf
Tender Documents • 0.05 MB
BOQ.xls
Other Document • 0.15 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .