REPLACEMENT OF 2.5M, VA 33 11 KV POWER TRANSFORMER 33 KV SF6 BREAKER FOR DMRL 33 KV MRS AGAINST BER ITEMS AT KANCHANBAGH HYDERABAD
2021_MES_455663_1
CA NO.CERD/SEC/TOKEN/23 OF 2020 -2021
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Hyderabad
as per NIT
7 documents required · 7 mandatory
₹1,000
Yes
GE I R N D Kanchanbagh Hyderabad
₹1.3 L
Yes
8 Sept 2021
29 Jun 2021
21 Aug 2021
29 Jun 2021
14 Aug 2021
30 Jul 2021
Amount
Supply installation, testing, commissioning in replacement of Power Transformer step down, outdoor type, copper bound of capacity 2500 KVA, 33 KV/11 KV, 3phase, 50 cycles AC with ON LOAD TAP CHANGING arrangements with remote control panel operation on 33 KV sides to vary secondary voltage from +5% to (-) 15% in steps of 1.25% (16Steps / 17switch positions), impedance 6% at normal / common tap including suitable marshalling box and HV terminals 3 Nos outdoor bare bushings with sockets and LV terminals connectors to connect the transformer with HT XLPE power cable of size 400 sqmm x 3 core with copper conductor and LV additional Neutral with one number solid porcelain type outdoor bushings with sockets on the transformer lid for earthing purpose complete in all respects with standard accessories and fittings conforming to IS-2026 - 2011, primary side delta and secondary side star including control panel of transformer. The salient features of the transformer and comprising of the following fixtures and fittings: - Make: VOLTAMP / SCHNEIDER / ABB / SIEMENS. GENERAL SPECIFICATIONS 1) KVA : 2500 KVA 2) Voltage Ratio : 33000/11000V 3) Type of Tap changer : On Load Changer with tapping range + 5% to -15% in steps of 1.25% 4) Winding Material : Copper
TECHNICAL SPECIFICATIONS Reference Standard : Transformer - IS :2026 - 2011 , Oil - IS : 335 : 2018 Rated KVA HV : 2500KVA LV : 2500 KVA Phases : 3 Service : Outdoor Mounting : Plinth Wound : Double wound Temp. Rise in Oil [Degree C.] : 50 By Resistance [Degree C.] : 55 Ambient temperature (Degree C): 50 Winding Material : Copper Type of Cooling : ONAN Vector Group : Dyn11 Frequency [Hz.] : 50 Phase : 3 Insulation Level [kV/Kvp] H.V. : 70 / 170, L.V. : 28 / 75 Primary Connection [HV] : Delta Primary Volts : 33000V Primary Wires : 3 Primary rated current : 43.74 A Secondary Connection [LV] : Star Secondary Volts : 11000V
Secondary Wires : 4 Secondary rated current : 131.22 A Taps on Primary / Secondary Winding for : + 5% to -15% in steps of 1.25% Primary / Secondary Voltage Variation On Load Tap Changer No. of switch positions : +5%to -15% in steps of 1.25(16Steps/17 Positions) Terminal Arrangement H.V. : Bare Bushing, L.V : Cable Box Losses * No Load Losses [Watts] : IS TOL * Load Losses [Watts] : IS TOL * Impedance (Z) [Percentage] HV - LV : 6% * No Load Current (% of Rated Current) : Less than 1% * EFFICIENCY Efficiency at 75 Deg. C. : UPF 0.8 P.F. 100% full Load % : 98.96 98.70 75% full load % : 99.15 98.94 50% full load % : 99.30 99.13 Max. efficiency % : 99.34 Load at which max. efficiency occurs kVA : 902.89 Economical to operate between 902.89 KVA to 2500KVA * SUBJECT TO IS : 2026 TOLERANCE Bushing - IS : 2099 & IS: 3347 Porcelain Bushings HV : 3 Porcelain Bushings LV : 4 Painting (Finish) : Two coats of polyurethane Light Grey, Shade No 631- IS: 5
TESTS - Routine Tests as per IS: 2026 - 2011 1) Voltage Ratio test 2) Polarity 3) Phase angle error measurement 4) Vector group test 5) B D V of oil 6) I R Values 7) Winding resistance 8) Open circuit test 9) Short circuit & Impedance test 10) Separate source voltage test 11) Induced over voltage test 12) Magnetic balance test STANDARD FITTINGS AND ACCESSORIES Sl No. Description 1) Rating & Terminal Marking Plate 2) Earthing Terminals 3) Lifting Lugs 4) Drain Valve with blanking plate 5) Filter Valve with blanking plate 6) Conservator 7) Conservator Oil filling hole with cap 8) Oil Level indicator with min. marking 9) Dehydrating Breather 10) Conservator Drain Plug
11) Air Release Device 12) Thermometer Pocket 13) Pressure relief valve with trip contact 14) Roller Bi directional 15) Radiators (Detachable Type) 16) Bare Bushing HV 17) Cable Box LV 18) Separate Neutral Terminal 19) On Load Tap Changer 20) O.T.I with Alarm & Trip Contacts 21) Buchholz relay with Alarm & Trip Contacts 22) Radiator Valves 23) Marshalling Box 24) Drain Valve with blanking plate (OLTC) 25) Filter Valve with blanking plate (OLTC) 26) Current Transformer 27) OLTC surge relay 28) RTCC 29) AVR 30) W.T.I with Alarm & Trip Contacts 31) W.T.I. Pocket 32) M.O.G. with LOLA Contacts 33) Buchholz relay shut off valve 34) Jacking pads
Note: (a) Disconnection of HT cable connection from incoming and outgoing of exisiting Transformer complete including dismantling old Transformer and shifting to E/M store and meggering the cable and connecting existing cable with new cold shrinkable end joints including loop removal from trench deemed to be included in the quoted rates. One No of cable end joint indoor type for HT XLPE cable of 400 Sqmm is deemed to be included in the quoted rates and also connecting to the existing 11 KV SF6/VCB breakers. (b) For shifting of Old Transformer from MRS DMRL to AGE E/M No 1 Transportation like vehicle, crane / labour / Forke lift deemed to be included in the quoted rates. (c) The following works deemed to be included in the quoted rates: - (i) Tools & plants, safety devices like helmet, belt, Rain coat, HT/LT insulation gloves, earth rod, Megger etc shall be provided by contractor. (ii) Complete duct / trenches cleaning of trenches. (iii) After taking shutdown contractor should complete the commisioning of the Job within 24 hrs. (vi) Provn of civil works addition / alteration to exisiting foundation / plinth / Trenches for mounting of Transformer or making the new plinth complete as per site requirment. (v) Testing, calibration of relays / primary / secondary injection, testing the relays / submission of test report and control wiring / power wiring complete. (vi) Inspection testing of Transformer at factory premises prior to despatch shall be carried out by the representative or officer nominated by the Accepting Officer. The cost is deemed to be included in the rate quoted.
Supply and installation of HT 33 KV 630 Amps, 3 phase, 50 cycles with aluminium bus bar totally enclosed metal clad VCB motorized Switch gear conforming IEC 62271 100/200 (Latest version) having having Rupturing capacity upto 350 MVA, current transormer 200-400/1-1A Potential transformer 33 KV/110 voltage core -1 along with outdoor incoming and outgoing porcelain bushes and degree of IP65 protection overload and earth fault protection, ammeter, voltmeter and of rating upto 630 Amp along with indoor control relay panel. (MAKE: SIEMENS / ABB) OUTDOOR VCB Panels(Outdoor) & Control Relays panel (Indoor) CRP panel: 01 Each 33kV, 630A, 26kA/1Sec Cubicle with Main copper Busbar Symatic - 01No 33KV Indoor Type Control Relay panels. Symatic - 01No Vacuum Circuit Breaker 33kV,630A , 26KA/3 sec Draw out type Make: Siemens / ABB Current Transformer-STC 20KA/1 Sec 200-400/1-1A, CL-0.2 /10VA, 5P20/10VA, Make: Pragati / Gemini / ECS / NP - 03 No Potential transformer fixed type 33kV/rt3/110v/rt3, core-1:Cl.0.2/30VA, 3P/30VA Make: Pragati / Gemini / ECS / NP Meter Digital Voltmeter, 96x96 Make: Meco/AE Digital Ammeter, 96x96 Make: Meco/AE Digital multifunction Meter. EM-7290 Make :Conserve / Secure / L&T
Switches / Indications Digital Voltmeter, 96x96 Make: Meco/AE T-N-C Switch Make : Switron - 02 Nos L-R Switch Make : Switron - 02 Nos Control MCB/Fuse 1Set Make : MDS-02 Nos Indicating Lamp 1 Set Make : Tecknic / DAV-02 Push Button for TCH Make : Tecknic / DAV 12 W Annunciator + Hooter Make : Alan - 01No in control relay panel Space heater & Thermostat with toggle switch Reputed-02 Nos Panel illuminaton Lamp With Door Limit Switch Reputed-02 Nos 30KV, 10KA, surge Arrester Raychem - 1 Set in VCB panel AC & DC fail indication Technic-02 Nos Incoming and outgoing from TOP Bushing Reputed - 6 Nos in VCB panel Relay 3 OC/1 EF - Relay with Communication port 7SR-10 Make : Siemens / ABB-01 No Auxilary relay for transformers protection VAA31, Make : Siemens / ABB - 03 Nos Microprocessor controlled Transformer differential relay 7SR242 with all connected items Make : Siemens / ABB-01No Master Trip Relay type VAJHM23 Make : Alstom-01No
Note: (a) Disconnection of HT cable / jumpers connection from incoming and outgoing of exisiting SF6 BREAKER with complete including dismantling old SF6 BREAKER and shifting to EM store and connecting the incoming and outgoing bushes with new HT jumpers ACSR panther conductor with suitable lugs / pad clamp as per requirement at the site and deemed to be included in the quoted rates. (b) For shifting of HT/LT SF6 BREAKER Transpotation like vehicle, crane / labour / Forke lift deemed to be included in the quoted rates. (c) The following works deemed to be included in the quoted rates:- (i) Tools & plants, safety devices like helmet, belt, rain coat, HT/LT insulation gloves, earth rod, Megger etc shall be provided by contractor (ii) Complete duct / trenches cleaning / repairs of trenches. (iii) After taking shutdown contractor should complete the commisioning of the Job within 24 hrs. (iv) Provn of civil works addition / alteration to exisiting foundation / plinth / Trenches for mounting of VCB / Control relay panel (v) Testing, calibration of relays / primary / secondary injection, testing the relays / submission of test report and control wiring / power wiring complete. (vi) Provision of control cabling for motorized remote operation with armoured copper cabling not less than 12 cores of size not less than 1.5 Sqmm copper conductor cables as required at site.
Chemical Earthing complete with copper earth plate electrode 900x600x5mm buried directly in ground vertically to a depth of not less than 2.25mtr below ground level than 1.5mtr below ground level connected to copper strip 32x6mm by means of bolts washers etc made out of copper earth strip will be protected by galvanized iron pipe medium grade 50mm bore up to main distribution board / main switch including necessary excavation and earth work PCC 1:3:6 type CI (using 20mm graded stone aggregate) RCC cover 1:2:4 type B1 including necessary reinforcement with recommended chemical compound to achieve less than 01 ohm etc complete all as show electric plate No. 3 of MES SSR Part-I, directed by Engineer-in-Charge.
Earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc as required copper strip 32x6mm copper strip complete all specified and directed.
Rajesh Engineering Consultants
JAZZCON ENGINEERS PVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .