Tender Value
₹19.2 L
EMD Value
₹38,400
Closing Date
14 Sept 2021, 6:00 pmClosed
CWE Shimla Hills Jutogh
CWE Shimla Hills Jutogh, Jutogh Cantt, Shimla-171008
SPECIAL REPAIR/ REPLACEMENT OF HT 11/0.433 KV, 500 KVA STEP DOWN TRANSFORMER 01 NO AGAINST DECLARED BER OF RADIANA PUMP HOUSE AT SUBATHU UNDER GE KASAULI
2021_MES_466413_1
CA NO CWE/KAS-21 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Subathu
Please refer Tender Documents
6 documents required · 6 mandatory
₹500
GE KASAULI
₹38,400
Yes
24 Sept 2021
9 Aug 2021
18 Sept 2021
9 Aug 2021
14 Sept 2021
31 Aug 2021
Amount
Excavation in trenches in hard/dense soil not exceeding 1.5 metre deep and not exceeding 1.5 metre wide and getting out including dressing/ trimming sides and leveling/grading and ramming of bottom of excavation complete all as specified.
Returning, filling in, including spreading leveling, watering and well ramming excavated soil in layers not exceeding 25 cm thick, filling back in trenches after cables have been laid and tested, poles, stays, struts have been erected and tested complete all as specified.
Removing of surplus soil to a distance n.exc 50 mtr and depositing at a level n.exc 1.5 mtr above starting point where directed complete all as specified.
Sand cushioning to UG cable 8 cm thick before laying the cable and 15cm above the cable, stretching and testing of cable complete all as specified.
Supplying and laying un-reinforced precast concrete cable cover, class LV, Type 2, flat, size 300mm x 180mm x 40mm complete all as specified and directed.
Supply, install, testing and commissioning of Outdoor Non-sealed type Mineral oil immersed Distribution Transformer ISI marked (IS-1180:2014) Step up/Step down, Copper wound , having Primary side voltage at 11 kV, 3 Phase and secondary side voltage at 433 Volts, 3-Phase, 50 Hz frequency of Capacity 500 KVA with following specifications:-
(i) No load Voltage ratio : 11000/433-250 Volts
(ii) No of Phase - Three
(iii) Type of Cooling - ONAN
(iv) Frequency - 50 c/s
(v) Vector Group - DYn11
(vi) Indoor or Outdoor type : Outdoor type
(vii) Application of Transformer : Distribution
(viii) Basic insulation level : 75 KVp
(ix) No of Tap position on HV Side ( offload & manual operated) : 7
(x) Tapping range : +5% to -10% in steps of 2.5%
(xi) Two earthing terminals for body earthing and two additonal for neutral brought out on a bushing
(xii) Oil level gauge indicating oil level at minimum, 30°C and maxImum operating temperature
(xiii) Rating and terminal marking plates
(xiv) Lifting lugs
(xv) Dehydrating Breather with dehydrating agent.
(xvi) Cable end box - HV - open terminal types bush fot HT connection & LV side (box type with brass cable gland)
(xvii) Percentage Impedance - 4.5%
(xviii) Oil temperature indicator and winding temperature indicator
(xix) Arcing horns/ Lightning areestor for HT side - 03 Nos
(xx) Thermometer pocket with cap
(xxi) Conservator with drain plug and a filling hole (1¼" normal size thread) with cover
(xxii) Drain-cum-samping valve (¾" nominal size thread, IS 554) preferably steel with plug for three phase transformer.
(xxiii) Pressure relief device or explosion vent
(xxiv) One filter valve on the upper side of tank
(xxv) Unidirectional flat rollers.
(xxvi) Inspection hole
(xxvii) Buchholz relay
(xxviii) First filling of transformer oil of specifications as per IS-335
(xxix) Maximum losses of transformer shall be as per energy efficiency level-3 as per IS-1180 (Part-I) : 2014
(xxx) Altitude of installation - 1750m above MSL
Note: 1. The transformer shall be ISI marked with energy efficiency level -2 category and having BEE certification. Routine and type test cerificatete (as per IS-2026) shall be produced by the tenderer. Certification from BIS and BEE shall be produced against the manufacturer.
2. Any subsequent amendment to IS or Govt notification on the subject shall be assumed as implemented in the schedule mentioned above on the date of supply.
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sq mm 3½ core including taking down the old unserviceable one complete all as specified and directed.
Cable jointing kit for 1.1 KV grade cable for outdoor temination, heat shrink type, joint complete with jointing material and accessories suitable for 3.5 core XLPE, armoured, Al conductor cable of size 300 Sqmm complete all as specified and directed.
Earthing complete with galvanised steel earth plate of size 60cmx60cmx6mm thick, burried directly in ground, earth pit not less than 2.25m deep below normal ground level with top edge of the plate not less than 1.5m below normal ground level, connected to equipment by using GI strips of size 32x6mm as earthing lead by means of bolts, nuts, checknut & washers of galvanised iron all shown in electrical plate No. 3 of MES schedule and connected to earthing test point all as specified and directed including earth pit of size 30cmx30cmx45cm made of PCC 1:3:6 and PCC 1:2:4 cover, funnel, Gl tubing etc. & testing on completion including taking out the old unserviceable earthing all as specified and directed. Note : The units rate includes the cost of excavation & earth work in any type of soil, charcoal & salt in alternate layers, 20mm GI Pipe (light grade) for watering, 40mm Gl protection pipe (light grade), funnel wire mesh, PCC 1:2:4 type B1 chamber in cernent concrete, 50 mm thick precast RCC M-25 (Design mix) cover duly reinforced with XPM (weight not less than 3 kg/sqm) and Cl frame etc and including provision of test point , connecting to test point and testing on completion etc complete all as specified NOTE: The unit rate include earthing lead and protection pipe upto 6.5 metre from top of earth plate
Galvanised iron strip 32 x 6mm buried in ground fixed in repair complete all as specified and directed.
Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size complete all as specified and directed.
R D Bansal
bharat refrigeration and electric co.
MONA GENERATOR SEVICES PVT. LTD.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .