| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.7 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹20.5 L+₹80,210 (4.08%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹25.8 L+₹6.2 L (31.4%)Rejected-Finance | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹27.9 L+₹8.2 L (41.7%)Rejected-Finance | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹35.6 L+₹15.9 L (80.9%)Rejected-Finance | L5 | Rejected-Finance Other than L1 |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
11 Sept 2023, 6:00 pmClosed
GE Satwari
GE Satwari Jammu
REPAIR/MAINT OF LT PANELS AND ALLIED WORKS AT Y STATION RIDGE AREA ROULKI AREA DEFENCE COLONY NCC OFFRS MESS AREA UNDER AGE E/M OF GE SATWARI
2023_MES_612937_1
GEJM-44/2023-24
Open Tender
Civil Works
Item Rate
180 days
GE Satwari
D Class Cat b i
9 documents required · 9 mandatory
₹500
GE Satwari
₹60,000
Yes
16 Nov 2023
12 Aug 2023
13 Sept 2023
12 Aug 2023
11 Sept 2023
28 Aug 2023
Amount
Dismantling PCC taking down unserviceable LT panel complete all as dirrected and making good surface
M & L for shifting of LT panel/ APFC panel incl necessary PCC foundation wk and necessary electric connection complete all as specified and directed.
Repair/ maintenance of APFC panel by disconnecting and replacing all unserviceable capacitors, Contactors, wiring, relays etc complete all as specified and directed by Engr in charge. Note:- this Job includes labour for replacement of unserviceable items only, items required to be repaced are to be measeured and paid separately. .
Supply and fixing in replacement of Contactor MO C3. Make L&T/Seimens/Schneider
Supply and fixing in replacement of Contactor MO C5. Make L&T/Seimens/Schneider
Supply and fixing in replacement of Contactor MO C10. Make L&T/Seimens/Schneider
Supply and fixing in replacement of Contactor MO C15. Make L&T/Seimens/Schneider
Supply and fixing in replacement of Contactor MO C20. Make L&T/Seimens/Schneider
Supply and fixing in replacement of APP Technology 1 Kvar Standard duty Capacitor in existing panels all as specified and directed. Make : L&T/Seimens/Schneider
Supply and fixing in replacement of APP Technology 2 Kvar Standard duty Capacitor in existing panels all as specified and directed. Make : L&T/Seimens/Schneider
Supply and fixing in replacement of APP Technology 5 Kvar Standard duty Capacitor in existing panels all as specified and directed. Make : L&T/Seimens/Schneider
Supply and fixing in replacement of APP Technology 10 Kvar Standard duty Capacitor in existing panels all as specified and directed. Make : L&T/Seimens/Schneider
Dismentiling, taking down unserviceable feeder pillar and Supply, installation, testing & commissioning in renewal of totally enclosed feeder pillar outdoor type fabricated out of 3.15 mm thick CRCA sheet dust and vermin proof powder coated double door type (independent cabin including locking arrangement for each MCCBs, bus bar chamber enclosed complete suitable for operating on 415 Volt 50 Hz AC supply internally wired with copper conductor having legs 90 cms made out of 50x50x6 mm angle iron grouted on brick masonary platform upto 45 cms. Brick masonary platform should be 60 cms above the Ground Level. Comprising the following:- .Note:- (i) The panel shall be front operated with cable entry from the bottom with cable glands. Earth bus shall be part of the main feeder pillar. (ii) Fabrication of feeder pillar box to be approved by CPRI width of the panel not less than 75 cms. (iii) Cost for construction of platform for panel of brick masonary work in CM 1:6 with foundation PCC 1:4:8 type D-2 including plaster work, PCC copping 1:2:4 (40 mm thick stone aggerate), deemed to be included in the item rate. No Extra payment will be made. (iv) MCCB's should be connected with extensions terminals at both side (incoming and outgoing).
M&L for Bus bar chamber of size 750 x 600 x 500 mm outdoor pedestal type, factory made, powder coated made out of 3.15 mm thick CRCA sheet dust and vermin proof complete suitable for operating on 415 Volt 50 Hz AC supply having legs 90 cms made out of 50x50x6 mm angle iron grouted on brick masonry platform upto 45 cms. Brick masonry platform should be 60 cms above the Ground Level. Comprising the following:- Note:- (i) 01 set of 500 Amps TPN aluminum bus bar of length suitable for fixing minimum 6 cables and of resection as per design with colour codding. Bus bars shall be designed to with stand a fault level of 36 KA at 415 volts. (ii) The panel shall be front operated with cable entry from the bottom with cable glands. Earth bus shall be part of the main feeder pillar. (iii) Fabrication of feeder pillar box to be approved by CPRI width of the panel not less than 30 cms. (iv) Cost for construction of platform for panel of brick masonry work in CM 1:6 with foundation PCC 1:4:8 type D-2 including plaster work, PCC copping 1:2:4 (40 mm thick stone aggregate), deemed to be included in the item rate. No Extra payment will be made. (v) After fixing the bus bar panel, all electric connections will be made without any extra cost all as specified and directed.
Taking out the broken hinges/unserviceable hinges & door handles from feeder pillar/LT Panel and replace with cold rolled MS hinges of appropriate size through spot welding & Mild steel sliding door bolt including making necessary adjustment for free and smooth movement of panel and 2 coat of powder coated spray painting inside & outside the panel complete all as specified and directed.
Taking out the burnt bus bar of any capacity and length, by disconnecting copper cable inter connections including insulators from feeder pillar/LT Panel & reftting the same after cleaning with emery paper including replacing bus bar insulators, S/S nut bolts ,washers appropriate size of copper cable inter connections complete all as specified and directed.
Taking out the damaged/deshaped CRCA sheets from LT Panel/feeder pillar box and replacing with new CRCA sheets having thickness 3mm including making necessary adjustment and alignment to make the existing feeder pillar/LT Panel to its required shape and size including with 2 coats of powder coated spray painting inside and outside the complete panel all as specified and directed.
Taking out the existing unserviceable voltmeter, ammeter, phase indication lamps, CTs of any description and size and S&F digital voltmeter, ammeter, phase indication lamps, CTs as per existing capacity and sizes all as specified and directed. Make :- L& T equivalent in AE / Enercon /Rishab.
Supply and fixing in replacement of unsv MCCB 630 Amp 4 pole 50 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL)
Supply and fixing in replacement of unsv MCCB 400 Amp 4 pole 36 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL)
Supply and fixing in replacement of unsv MCCB 320 Amp 4 pole 36 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL)
Supply and fixing in replacement of unsv MCCB 250 Amp 4 pole 36 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL)
Supply and fixing in replacement of unsv MCCB 200 Amp 4 pole 36 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL)
Supply and fixing in replacement of unsv MCCB 160 Amp 4 pole 36 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL).
Supply and fixing in replacement of unsv MCCB 125 Amp 4 pole 16 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL)
Supply and fixing in replacement of unsv MCCB 100 Amp 4 pole 16 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL)
Supply and fixing in replacement of unsv MCCB 63 Amp 4 pole 16 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL)
Supply and fixing in replacement of unsv MCCB 63 Amp 3 pole 16 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL)
Supply and fixing in replacement of unsv MCCB 125 Amp 3 pole 16 KA, thermal and magnetic releases with Ics=100%Icu. conforming to IS/IEC 60947-2 and IEC 60947-2 with short circuit and over load protection. Outgoing and incoming spreaders should be provided for connecting cable without any extra cost. Makes: Legrand(DPX^3) or equivalent to Schneider(NSX)/Siemens(3VL)
Supply and fixing in replacement of unsv MCB TPN 63 Amps 10 KA C Curve in existing panels including making all connections with proper thimbling and connectors. Legrand (DX^3) Cat No.408702 and equivalent Make of Seimens (Betagard 5SL4)
Supply and fixing in replacement of unsv MCB SPN 40 Amps 10 KA C curve including making all connections with proper thimbling and connectors. Legrand (DX^3) and equivalent Make of Seimens (Betagard 5SL4)
Supply and fixing in replacement of unsv MCB DP 32 Amps 10 KA C curve including making all connections with proper thimbling and connectors. Legrand (DX^3) Cat No.408617 and equivalent Make of Seimens (Betagard 5SL4)
Supply and fixing in replacement of unsv MCB SP 6 to 30 Amps 10 KA C curve including making all connections with proper thimbling and connectors. Legrand (DX^3) and equivalent Make of Seimens (Betagard 5SL4)
Supply and fixing of spreaders 4 pole 100 To 250 Amps fixing in MCCB of any make and models all as directed by Engr In Charge.
Disconnecting LT supply from panel/ pole and reconnecting LT supply and testing complete. Locating the fault through cable fault locating machine to pin point the exact location of the fault lenth cable (100rm to 500rm) complete all as specified and directed by engr - in - charge.
Supply & fixing in replacement of onload change over switch 415V AC, 4 pole front openable type in sheet steel enclosure including fixing arrangements in existing panel/on wall, including provision of thimble, nut bolts etc of required capacity and of following cap:- (Make C&S/L&T/Havells/Indo-asian) (a). Change over switch 63 Amp
(b). Change over switch 100 Amp
(c). Change over switch 160 Amp
(d). Change over switch 200 Amp
(e). Change over switch 250Amp
(f). Change over switch 400Amp
Supply & fixing in replacement of unsv automatic change over switch 240V AC, three phase front openable type in sheet steel enclosure including fixing arrangements in existing panel/on wall, including provision of thimble, nut bolts etc of required capacity and of following cap:- (Make : Havells/C&S/L&T) (a). Change over switch 63 Amp
(b). Change over switch 160 Amp
M & L for earthing complete with galvanised steel earth plate electrode 600 X 600 X 6 mm thick buried directly in ground (earth pit not less than 2.25M deep below ground level) with top edge of the plate not less that 1.5M below normal grouond level connected to GI earth wire 4 mm dia by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No 03 of SSR Part-I connected to earthing test point / DB including excavation / earth work in any type of strata, removal of surplus earth, GI pipe for watering pipe with and funnel, PCC 1:3:6 Type C-1 chamber with 40 mm thick RCC 1:2:4 type B-1 in cover slab with TMT bars @ 150 mm c/c both way with GI protection pipe complete all as specified and directed by Engineer-in-Charge.
M & L for earthing with galvanised steel earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25M deep below ground level with top edge of the plate not less than 1.5M below normal ground level connected to galvanised strip 32x6mm by means of nuts, bolts, checknuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I connected to earthing test point including excavation/ earth work in any strata removal of surplus earth, GI pipe for watering and funnel, PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 in cover slab with 40mm dia light grade GI protection pipe and 20mm dia light grade GI pipe for watering all as specified and directed by Eng-in-charge.
M & L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc as required 25X4 mm dia galvanised iron strip.
M & L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc as required 4 mm dia galvanised iron or steel wire.
M&L for earth testing, identifying the earthings in system and recording the results on indicator board and producing three copies of test sheet duly signed by Contractor/ JE/ AGE E/M all as directed by Eng-in-charge. Note :- (i) Cost of labour and tools required for testing is deemed to be included in quoted rates.
Supply & fixing in replacement of automatic street light switch using Nature Switch for automatic switching of street lights based on LUX level of natural light the sensor (nature switch) along with suitable power contactors and MCBs (Input-output) should be enclosed in pole/wall mountable enclosure made of rust proof, Electric shock proof, termite proof and FR grade SMC junction box (sintex make) conforming to IP 54.the contactor,MCBs and copper circuit wiring (min.10sqmm) should enough to take: Single-phase load of 5KW;contactor Rating 40Amps; MCB(sp) Rating 40Amps.MAKE:-Nature switch :Kakatiya energy systems pvt.ltd. hyderabad/bajaj/healer. Contactor:- BCH/L&T/Schneider or equivalent (as per IEC-60947-4-1/IS-13947-4-1), MCBs(Input-output):Hager/schneider/L&T/BCH or equivalent (as per IEC-60898/IS-8828),Circuit wiring : Finolex/polycab/RR Kable or equivalent. Model no SWADEEP-02EC5KW1P.
Supply & fixing in replacement of Off Load change over switch 415V AC, 4 pole, 50 Hz front openable type in sheet steel enclosure including fixing arrangements in existing panel/on wall, including provision of thimble, nut bolts etc of required capacity and of following cap:- (Make C&S/L&T/Havells/Indo-asian) (a). Change over switch 63 Amp
(b). Change over switch 100 Amp
(c). Change over switch 200 Amp
(d). Change over switch 250Amp
Supply and fixing in replacement of Danger notice plate of 1.6mm thick MS sheet vitreous enamelled white with letters, figures and conventional skull and bones in signal Red colour and inclusive fixed with MS flat clamps 25x3mm 2 Nos, nuts, bolts for LT 440 volt of size 20x15cm
Supply and fixing in replacement of aluminium lugs of size 630 Sqmm all as specified and directed.
Supply and fixing in replacement of aluminium lugs of size 400 Sqmm all as specified and directed.
Supply and fixing in replacement of aluminium lugs of size 300 sqmm all as specified and directed.
Supply and fixing in replacement of aluminium lugs of size 185 Sqmm all as specified and directed.
Supply and fixing in replacement of aluminium lugs of size 120 Sqmm all as specified and directed.
Supply and fixing in replacement of aluminium lugs of size 95 Sqmm all as specified and directed.
Supply and fixing in replacement of aluminium lugs of size 70 sqmm all as specified and directed.
M & L for preparation of old steel surfaces of steel/LT panel boards/feeder pillar boxes of any description & any position including removing disintegrated/detoriating part of paint and applying filler coat to obtain smooth surfaces and applying a coat of synthetic enamel paint using spray machine to obtain smooth finish to the entire satisfaction of Engineer-in-Charge complete.
M & L for cable jointing kit Indoor/outdoor type, heat shrinkable type including all jointing material & accessories suitable for 1100 Volt grade aluminium conductor cables of size 10 to 16 Sqmm 4/3.5 core cables all as directed and specified.
-ditto- but suitable for 25 Sqmm and upto 35 Sqmm x 4/3.5 core
-ditto- but suitable for 50 Sqmm x 3.5 core
-ditto- but suitable for 95 Sqmm x 3.5 core
-ditto- but suitable for 120 Sqmm and upto 185 Sqmm 3.5 core
-ditto- but suitable for 240 sq mm x 3.5 core
Supply and fixing in replacement of unsv MCB DP enclosure. Legrand Cat Part No 507791 and equvalent Seimens (Betagard 8GB32)
Supply and fixing in replacement of unsv MCB SP enclosure. Legrand Cat Part No 507790 and equvalent Seimens (Betagard 8GB32)
Supply and fixing in replacement of unsv three phase power contractor MNX 110 , 415 Volts all as specified and directed .
Harsh Electricals
vivek and co
M/S S K Electricals Regd
BMMJ TRADERS AND ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .