Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹3.6 L
EMD Value
₹7,288
Closing Date
13 Jul 2022, 3:00 pmClosed
DIRECTOR TMC
Office of Engineering services, Second Floor,Khanolkar Shodhika , ACTREC Kharghar Node, Navi Mumbai - 410210
Replacement of Package AC unit of IBU area, Ward Block ACTREC
2022_TMC_696490_1
Replacement of Pkg AC at ACTREC
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
120 days
ACTREC Kharghar
As per tender terms and condition
2 documents required · 2 mandatory
₹0
₹7,288
Yes
ACTREC Kharghar
17 Aug 2022
23 Jun 2022
13 Jul 2022
23 Jun 2022
13 Jul 2022
23 Jun 2022
23 Jun 2022 - 26 Jun 2022
27 Jun 2022
Amount
Supply, Installation, Testing & Commissioning of 11 TR capacity Air Cooled Package Air Conditioner unit (Duct connection type) as per the folowing technical specification: Nominal Cooling Capacity (TR): 11 TR Rated cooling Capacity: 132000 BTU/HR Refrigerant: R-410 A or R-407 or any other (Ecofriendly) External finish: pure polyster powder coated GI steel housing. The unit to include built in contros like HP/LP/OL/UL/TEMP,SPP, PHASE SEQUENCE RELAY Display of same. INDOOR UNIT (IDU): Type of Blower: Centrifugal forward curved, double inlet double width. Air Filter: Non-Woven polyster Media enclosed with HDPE mesh. Contrller: Factory fitted Microprocessor based with LCD display. Evaporator Coil:Hydropholic blue fins anticorosion coating. Compresssor Type: Hermetically sealed scroll (High energy efficient). No of compressor Unit: 02 ( double ckt) OUTDOOR UNIT ( ODU) : NO.of ODU : 02 NO with suitable MS stand Condenser Type: AIR COOLED FTHX,Hydropholic blue fins anticorosion coating. Condenser Fan Type : Proppeler. THE UNIT SHALL BE DESIGNED TO OPERATE EFFECTIVELY AT HIGHER AMBIENT TEMPERATURE,
Refrigerant Piping: Supply , Installation, Testing & commissioning of Hard drawn copper tube complete with all accessories and support between indoor & outdoor units RMT indicated is for set of piping (Liquid+ Gas) between indoor and outdoor machine, (individual piping will not be measured]. Piping should be laid in GI tray with proper clamping. 1 1/8"' ,5/8" Copper piping or equivivalent to the system.
Supply, laying & termination of copper cable from Departmental power supply to IDU & between IDU and ODU unit. Complete with lug fitting, ferruling, gland fitting etc. All Cable should be laid in GI tray.
GI DUCT: Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications and as per SMACNA standard of following sheet thickness complete as required. Thickness 0.63 mm sheet ( 24 SWG)
SITC PVC drain pipe having pressure holding of 6kg/cm2. Drain piping complete with all accessories with 12mm Nitrile Rubber Insulation.. Dia 25mm
Supply, installation, testing and commissioning of GI volume control duct damper/Non Return damper 18 guage GI. frame & 20 guage GI blades complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
Supplying, Fixing,testing and commissioning of fusible link type fire dampers in supply air duct/main branch and return air path as and where required of required sizes . The damper shall also be closed in the event of fire complete as required and as per specifications.
Supply & fixing of Fire retardant synthetic canvass connection with a provision to measure the canvass temperature at the mouth of package units & plenum with all fixing arrangement, nut bolts, hardware’s etc. as instructed and as directed by EIC for above package units.
Removing of existing water cooled package unit x 1 Nos of 11TR water cooled package AC including Condenser pipe removing & blank off with blind flange, cabling, copper piping, duct removing etc. including other items required to clear the space for new unit installation as directed by EIC-ES. Note:Removed items to be shifted in campus location as directed by EIC.
Replacement of switch gear in existing feeder as per suitable capacity and as directed and as instructed by EIC-ES
global air tecnix
FAIR ENGINEERING PVT LTD
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .