Supply, Installation, Testing and Commissioning (SITC) of Air Conditioners at WOT office, 7th Floor Service Block Building, North Yard, MDL
2020_MDL_84046_1
1900000092
Open Tender
Civil Works
45 days
North Yard, MDL
As per Tender Clause No 7
6 documents required · 6 mandatory
₹0
₹71,000
Yes
1 Jan 2021
27 Nov 2020
11 Dec 2020
27 Nov 2020
11 Dec 2020
2 Dec 2020
Supply & delivery of ceiling suspened Four way Inverter Cassette Air conditioner (Minimum 3 star) inclusive of Indoor Unit with in built drain pump, Out door unit, including refrigerant gas (eco friendly), cordless remote controllers with batteries, power supply cable along with connecting pin & accessories etc. all complete as directed by MDL Engineer Preferred Make : Toshiba/Daikin/Mitsubishi/Hitachi --Minimum 4 TR Capacity
Supply & delivery of ceiling suspened Four way Inverter Cassette Air conditioner (Minimum 3 star) inclusive of Indoor Unit with in built drain pump, Out door unit, including refrigerant gas (eco friendly), cordless remote controllers with batteries, power supply cable along with connecting pin & accessories etc. all complete as directed by MDL Engineer Preferred Make : Toshiba/Daikin/Mitsubishi/Hitachi --Minimum 3 TR Capacity
Supply & delivery of wall mounted Inverter Split Air conditioner (Minimum 3 star) inclusive of Indoor Unit, Out door unit, including refrigerant gas (eco friendly), cordless remote controllers with batteries, power supply cable along with connecting pin & accessories etc. all complete as directed MDL Engineer Preferred Make: Toshiba/Daikin/Mitsubishi/Hitachi --Minimum 1 TR Capacity
Supply & delivery of wall mounted Inverter Split Air conditioner (Minimum 3 star) inclusive of Indoor Unit, Out door unit, including refrigerant gas (eco friendly), cordless remote controllers with batteries, power supply cable along with connecting pin & accessories etc. all complete as directed MDL Engineer Preferred Make: Toshiba/Daikin/Mitsubishi/Hitachi --Minimum 2 TR Capacity
Supply & Installation of copper refrigerant piping of suitable diameter compatible with the refrigerant gas (eco friendly) & air conditioner model with insulation/nitrile rubber sleeves (19 mm thk), end connections with appropriate clamping / supporting arrangement,making holes in walls with core cutting, providing sleeves & proper finishing for connectivity from indoor to outdoor unit etc all complete as directed by MDL Engineer Insulation Preferred make - SUPERLON/K-FLEX/ARMACELL Note: Copper tubing work would be measured in running meters in one direction along the length from indoor unit to outdoor unit considering suction & discharge tubing as one combined set. Suction & discharge piping are not considered seperately one from another for arriving at the BOQ quantity. For payment purpose 3 mtrs.of copper refrigerant piping per A.C unit will be deducted, since these are standard free supply with each A.C unit from Vendor/Manufacturer of A.C.
Supply & Installation of suitable L-Shaped brackets duly painted (1set) with bush & fasteners for mounting outdoor unit as directed by MDL Engineer --For 4 TR Capacity
Supply & Installation of suitable L-Shaped brackets duly painted (1set) with bush & fasteners for mounting outdoor unit as directed by MDL Engineer --For 3 TR Capacity
Supply & Installation of suitable L-Shaped brackets duly painted (1set) with bush & fasteners for mounting outdoor unit as directed by MDL Engineer --For 1 TR Capacity
Supply & Installation of suitable L-Shaped brackets duly painted (1set) with bush & fasteners for mounting outdoor unit as directed by MDL Engineer --For 2 TR Capacity
Supply & installation of ISI mark UPVC plumbing grade condensate drain pipe with nitrile rubber insulation of 6 mm thk. & fittings with supports & clamps etc all complete for taking out condensate drain water from AC Units up to the Ground Level / washroom as directed by MDL Engineer, including looping. Preferred Make of UPVC PIPE - PRINCE / ASTRAL / SUPREME Preferred make of insulation - SUPERLON/K-FLEX/ARMACELL --40 mm dia
Supply & installation of ISI mark UPVC plumbing grade condensate drain pipe with nitrile rubber insulation of 6 mm thk. & fittings with supports & clamps etc all complete for taking out condensate drain water from AC Units up to the Ground Level / washroom as directed by MDL Engineer, including looping. Preferred Make of UPVC PIPE - PRINCE / ASTRAL / SUPREME Preferred make of insulation - SUPERLON/K-FLEX/ARMACELL --32 mm dia
Supply & installation of ISI mark UPVC plumbing grade condensate drain pipe with nitrile rubber insulation of 6 mm thk. & fittings with supports & clamps etc all complete for taking out condensate drain water from AC Units up to the Ground Level / washroom as directed by MDL Engineer, including looping. Preferred Make of UPVC PIPE - PRINCE / ASTRAL / SUPREME Preferred make of insulation - SUPERLON/K-FLEX/ARMACELL --25 mm dia
Supply & installation of 2.5 Sq mm 3 core Electrical cable for Inverter split AC (from indoor units to outdoor units) all complete as directed by MDL Engineer.
Installation of ceiling suspended Cassette Inverter Air conditioner & wall mounted Inverter Split Air conditioner inclusive of Indoor Unit, Out door unit, cordless remote controllers, power supply cable along with connecting pin, accessories etc. & Testing & Commissioning of ceiling suspended Cassette Inverter Air conditioner & wall mounted Inverter Split Air conditioner inclusive of Indoor Unit, Out door unit, cordless remote controllers,accessories, copper refrigerant piping with insulation/nitrile rubber sleeves (19 mm thk) complete with necessary electrical installation with wiring, drain piping, purging with suitable gas for flushing before leak test, leak testing of copper piping & first charge of pre-filled refrigerant gas (eco friendly) considering lengths of copper piping & A.C units capacity etc all complete as directed by MDL Engineer. --Four way inverter Cassette Air Conditioner minimum 4 TR / 3 TR Capacity
Installation of ceiling suspended Cassette Inverter Air conditioner & wall mounted Inverter Split Air conditioner inclusive of Indoor Unit, Out door unit, cordless remote controllers, power supply cable along with connecting pin, accessories etc. & Testing & Commissioning of ceiling suspended Cassette Inverter Air conditioner & wall mounted Inverter Split Air conditioner inclusive of Indoor Unit, Out door unit, cordless remote controllers,accessories, copper refrigerant piping with insulation/nitrile rubber sleeves (19 mm thk) complete with necessary electrical installation with wiring, drain piping, purging with suitable gas for flushing before leak test, leak testing of copper piping & first charge of pre-filled refrigerant gas (eco friendly) considering lengths of copper piping & A.C units capacity etc all complete as directed by MDL Engineer. --Wall mounted Inverter Split Air conditioner minimum 1 TR /2 TR Capacity
Supply, fabrication, fixing in postions with suitable GI angle supports GI perforated cable trays bolled tyres with all necessary bends, connectors etc. and fabricated using minium 14 gauges CRCA sheet. Further the rates shall also include supporting of these trays complete as required and as per final directions and final approval of MDL Engineer --Size: 300mm Wide & 75mm Deep.
Supply, fabrication, fixing in postions with suitable GI angle supports GI perforated cable trays bolled tyres with all necessary bends, connectors etc. and fabricated using minium 14 gauges CRCA sheet. Further the rates shall also include supporting of these trays complete as required and as per final directions and final approval of MDL Engineer --Size: 300mm Wide & 75mm Deep with Cover (Inverted cable tray)
Server Room Timer for Hi-wall AC units: Supply, installation, testing & commisioning of timer base Sequential controller for Hi-wall units. It should give command to units to operate on alternate basis. ( Preferred Make: Seimens / L&T / Schnieder)
Structural steel work bolted or welded in buit up sections, truss and framed work for safety Railing, platform etc. as per drawing including necessary Anchor fastners for fixing of Brackets. Including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer and two coats of approved enamel paint all etc. all complete and as per directives of MDL Engineer