Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.9 LAccepted-AOC | L1 | Accepted-AOC L-1 | |
| 2 | L2₹38.0 L+₹2.5 L (6.95%)Rejected-AOC | L2 | Rejected-AOC L-2 | |
| 3 | Rejected-Technical | - | Rejected-Technical Rejected due No remarks found in WLR QE Dec 2021 of HQ CE Jabalpur Zone |
Tender Value
₹45.4 L
EMD Value
₹90,900
Closing Date
12 Mar 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Sh A P Singh, IDSE CWE Chm
HQ CWE Chandimandir
CA NO CWE/CHM(U)-80/2021-22 REPAIR/ MAINT OF CERTAIN ESSENTIAL E/M SERVICES RELATED WITH HT/LT SUPPLY NETWORK UNDER GE (U) CHANDIMANDIR
2022_MES_509166_1
CWE/CHM(U)-80/2021-22
Open Tender
Miscellaneous Works
Item Rate
180 days
HQ CWE Chandimandir
Class D Cat b (ii)
8 documents required · 8 mandatory
₹500
Yes
GE (U) Chandimandir
₹90,900
Yes
24 May 2022
18 Feb 2022
19 Mar 2022
18 Feb 2022
12 Mar 2022
26 Feb 2022
19 Feb 2022 - 25 Feb 2022
60 days
Amount
Disconnecting and taking out old unserviceable panel of any type and size complete all as specified and directed.
Disconnecting and taking out defective HT cable of any size complete including joints/protection pipes etc from trenches/ducts/poles etccomplete all as specified and directed.
Taking out old damaged PCC pole of any size incl breaking PCC foundation and clearing the site complete all as specified and directed.
Excavation in trenches in hard/dense soil not exceeding 1.50 metre wide and not exceeding 1.50 metre in depth, for laying of cable, poles, stay etc. and getting out complete all as specified and directed.
All as per item No 04 here-in-before but depth exe 1.5 mtr and not exe 3.0 mtr complete all as specified and directed.
Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick each complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed.
Supplying and laying un-reinforced factory made precast concrete cable cover, class HV, type 1 flat , size 300mm x 180mm x 40mm complete all as specified and directed.
M & L dry sand filling under and around UG cable to provide cushioning complete all as specified and directed. Note. Only punned thickness shall be measured.
M & L GI pipe 100 mm bore light grade fixed for cable protection on poles/walls/under road/culvert etc complete all as specified and directed.
M & L PCC 1:4:8 type D-2 using 40 mm graded crushed stone aggregate as in pole foundations etc complete all as specified and directed.
M & L PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly including necessary form work complete all as specified and directed.
M & L PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate in pole / strut coping incl necessary form work complete all as specified and directed.
S & F in trenches, ducts or fixing along the poles or passing through pipes or laid under floors etc and testing XLPE insulated , screened PVC bedded, galvanised steel strip armoured, heavy duty HT power cables ISI marked with aluminium conductor, size 95 sqmm 3 core, 11 KV earthed, complete all as specified and directed.
All as per item No 14 here-in-before but 185 Sqmm 3 core complete all as specified and directed.
All as per item No 14 here-in-before but 240 Sqmm 3 core complete all as specified and directed.
S & F HT heat shrinkable type outdoor end termination cable jointing kit with accessories suitable for 11 KV (Earthed) grade XLPE cable of size 95 Sqmm, 3 core complete all as specified and directed.
All as per item No 17 here-in-before but cable of size 120 to 185 Sqmm, 3 core.complete all as specified and directed.
All as per item No 17 here-in-before but cable of size 240 Sqmm, 3 core complete all as specified and directed.
S & F HT heat shrinkable type indoor end termination cable jointing kit with accessories suitable for 11000 volt (Earthed) grade XLPE cable of size 95 Sqmm, 3 core complete all as specified and directed.
All as per item No 20 here-in-before but cable of size 120 to 185 Sqmm, 3 core.
All as per item No 20 here-in-before but cable of size 240 Sqmm, 3 core.
S & F HT straight through heat shrinkable type cable jointing kit with accessories for 11 KV grade, XLPE cable of size 95 sqmm 3 core complete all as specified.
All as per item No 23 here-in-before but cable of size 120 to 185 Sqmm, 3 core.
All as per item No 23 here-in-before but cable of size 240 Sqmm, 3 core.
M & L in replacement cross arms, bracings, supports, clamps and back plates fabricated from structural steel section including nuts, bolts , washers, welding, bending ( cold or hot ) drilling holes for bolts bent to any shape or size as indicated or directed inclusive of one primer coat of red oxide primer and two coats of aluminium paint complete all as specified and directed.
M&L in replacement outdoor gang operated air break switches 12 insultors vertical isolation type, triple pole, manually operated, mounted on insulators and steel frame complete with all accessories & drop out fuse unit, with operating mechanism worked from ground level for current rating 400 Amps, 11000 volts complete with GI operating pipe of heavy duty grade of suitable length complete all as specified and directed.
All as per item No 27 here in before but of capacity current rating 200 amps complete all as specified and directed.
S & F steel tubular swaged poles complete with mild steel base plate, closed at top as specified, type 410 SP-55 (11 metre long) including painting with two coats of black bitumonous paint externally up to the planted depth and internally through out and remaining external portion with two coats of aluminium paint , over a coat of red oxide primer complete all as specified and directed. Note: Excavation & earthwork, foundation concrete will be meaured & paid for separately under respective item(s).
M & L for GI pipe 80 mm bore light grade fixed for cable protection on poles/walls/under road/culvert etc complete all as directed.
Supply only jumpers in red/yellow/blue colour for HT lines/connections made from aluminium conductor single core PVC insulated cable of suitable size complete including winding wires, aluminium tapes etc complete all as specified and directed.
Finding of fault to 11 KV UG cable with suitable fault locator equipment & pin point the fault in the faulty cable including necessary excavation and earth work for exposing the faulty portion of the UG cable complete all as specified and directed.
Supply only moving contact blade (male contact) suitable for 200 amps 11000 volts outdoor GOAB switch complete all as specified and as directed.
Supply only spring loaded fixed contacts (female contact jaw) suitable for 200 amps 11000 volts outdoor GOAB switch complete all as specified and as directed.
Supply only tinned copper flexible wires woven connecting jumper suitable for 200 amps 11000 volts outdoor GOAB switch complete all as specified and as directed.
Supply only MS jumper carrier for 200 amps 11000 volts outdoor GOAB switch complete all as specified and as directed.
Supply only moving contact blade (male contact) suitable for 400 amps 11000 volts outdoor GOAB switch complete all as specified and as directed.
Supply only spring loaded fixed contacts (female contact jaw) suitable for 400 amps 11000 volts outdoor GOAB switch complete all as specified and as directed.
Supply only tinned copper flexible wires woven connecting jumper suitable for 400 amps 11000 volts outdoor GOAB switch complete all as specified and as directed.
Supply only MS jumper carrier for 400 amps 11000 volts outdoor GOAB switch complete all as specified and directed.
Supply only wall mounting indoor type 200 amps capacity 8 way TPN busbar chamber 415 volts in sheet steel enclosure complete including making all incoming and outgoing cable connections complete all as specified and directed.
Supply only main switch with rewireable fuses in sheet steel enclosure capacity 200 amps TPN 415 volts with and including porcelain fuses complete including making all incoming and outgoing cable connections all as directed.
Supply only changeover switch off load type in sheet steel enclosure capacity 200 amps FP 415 volts including making all incoming and outgoing cable connections complete all as specified and directed.
Attending day to day complaints round the clock pertaining to repairing of electric supply related services by maintaining of external electric supply system such as LT/HT lines, panels/feeder pillar boxes, distribution feeders, LV/HV switch gears, HT four pole structures, transformers etc of any make/type/size & capacity in Chandimandir Mil Stn including the areas across Kalka road complete all as specified and directed by Enginner-in-Charge. Note (a) The items required for the repair / rectification of complaints shall be measured and paid separately under respective item of Sch 'A'. (b) Contractor shall deploy minimum manpower of one electrician (Skilled) & two helpers (semi - skilled) for attending the complaints. Any more manpower/T&P etc required to attend any complaint as per the site requirements shall be provided by the contractor without any extra cost to the deptt & cost of the same shall deemed to be included in quoted rates. (c) Conveyance, necessary T&P safety gears, ladders etc for maintaing the services shall be provided by the contractor and cost of the same shall deemed to be included the quoted rates. (d) Electrical complaints as intimated by JE/Engineer-in-Charge shall be attended immediately.
Supply only LT insulation tape (FR PVC electrical insulation tape) 0.125 mm thick , 1.80 cm width and 25 mtr lengthcomplete all as specified and directed. Make - Steelgrip/Anchor or as approved by GE.
Supply only HT insulation tape FR, 0.75 mm thick , 1.90 cm width and 9.0 mtr length packed in boxcomplete all as specified and directed. Make- Kappa/3M Scotch/Gemini or as approved by GE.
Supply only copper tinned fuse wire complete all as specified and directed.
Supply only GI nuts/bolts/washers complete all as specified and directed.
Supply only on load type changeover switch without enclosure 630 amps capacity four pole 415 volts complete all as specified and directed.
Supply only on load type changeover switch without enclosure 800 amps capacity four pole 415 volts complete all as specified and directed.
Supply only heavy duty aluminium lugs eye type of size 16 to 35 sqmm complete all as specified and directed.
Supply only heavy duty aluminium lugs eye type of size 50 to 95 sqmm complete all as specified and directed.
Supply only heavy duty aluminium lugs eye type of size 120 to 185 sqmm complete all as specified and directed.
Supply only heavy duty aluminium lugs eye type of size 240 to 400 sqmm complete all as specified and directed.
Supply only heavy duty aluminium in line connector of size 16 to 35 sqmm complete all as specified and directed.
Supply only heavy duty aluminium in line connector of size 50 to 95 sqmm complete all as specified and directed.
Supply only heavy duty aluminium in line connector of size 120 to 185 sqmm complete all as specified and directed.
Supply only heavy duty aluminium in line connector of size 240 to 400 sqmm complete all as specified and directed.
Supply only CRC 2-26 power spray 500 ml bottle complete all as specified and directed.
Material and labour for E-watch online EMS with annual subscription charges paid having features of 1, 3, 5, 15, 30, 60 minutes data reading / pooling frequency, real time personalized dashboards, historical graphs and trends views, alarms, downloadable reports via e-mail or spreadsheet reports, carbon monitoring, mobile app/alerts, on demand reports, open access / scheduled demand analysis, 03 Nos simultaneous users complete all as specified and directed. Make : Secure or equivelant as approved by the GE.
Supply, installation and testing of Secure or equivelant make as approved by the GE M-Cubed 100 BCS (Base Computer Software) in physical form compatible with Secure Premium 300 electric meters/Availability Based Tariff meters/special energy meters. BCS shall be capable of exporting data in format : ASCII, CDR and CSU and shall be capable of displaying meter information such as energy & max demand register readings, event logs and load survey views such as tabular & line/log chart, 15 min/daily/weekly and AMR reports complete all as specified and directed.
Supply and fixing in repairs only electrical panel doors fabricated from MS sheet as per existing size and shape and fixed with hinges by properly welding and checking for proper closing and opening complete all as specified and directed. Note:- Reparing and refixing of one door panel fitted with 2/3 hinges shall be considered as one job. Any small piece of MS sheet of thickness 2/3 mm required for repairing the portion of the door to be fixed with hinges and replacing any damaged MS hinge shall be deemed to be included in the unit rate quoted.
M&L for earthing complete with galvanised steel earth plate electrode 60x60cmx6 mm thick burried directly in ground ( earth pit not less than 2.25 Mtr deep below ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to galvanised earth lead strip 32x6mm dia by means of bolts, nuts, check nuts and washers of GI or steel all as shown in electrical plate No. 5 of SSR Part-I 2009 connected to earthing test point panel all as specified or indicated and testing on completion including necessary excavation & earth work in any type of soil, funnel, PCC chamber (1 : 3 : 6) type C1, CI pit cover and frame , charcol, salt including earth lead protected by 40 mm dia medium grade GI pipe and 20mm dia medium grade GI Pipe for watering complete all as specified and directed. Note :- Earth lead strip 32 x 6 mm and GI 40 mm dia protecion pipe upto 7.5 mtr length will be deemed to include in the unit rate quoted.
Blank
Supply and installation in replacement incl connecting and testing of AC/DC back up system for HT 11 KV panel boards comprising of 1500 VA or nearest higher size capacity, single phase 220/240 volts, 50 Hz microprocessor control invertor system with overload/overcharge/deep discharge protection system, LED display, fitted with relays and other controls, DC charging system, two nos 12 volt 180 AH lead acid batteries connected with heavy duty copper leads and brass terminals. System having input AC 240 volt single phase or DC 24 Volt and output 220/240 volts AC single phase complete including suitable trolley/cabin for housing the entire system, input AC supply leads & output AC supply leads copper conductor of appropriate size and making all connections with the control wiring terminals of HT 11 KV VCB panels complete all as specified and directed. Make : Battries - Exide/Amron/Tata/ as per invertor system manufacturer, Invertor system- Luminous/Microtek/APC/V-Gaurd
M/S BALWINDER SINGH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .