| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.4 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹17.8 L+₹1.4 L (8.26%)Rejected-Finance 656 VINOBA BASTI SRI GANGANAGAR 335001 RAJ | SRI GANGANAGAR | SRI GANGANAGAR | RAJASTHAN | 335001 | L2 | Rejected-Finance L2 FOR REJECTED | |
| 3 | L3₹17.8 L+₹1.4 L (8.69%)Rejected-Finance | L3 | Rejected-Finance L3 FOR REJECTED | |
| 4 | L4₹18.8 L+₹2.4 L (14.5%)Rejected-Finance 1 A BASEMENT 30 31 RAJA HOUSE NEHRU PALACE NEW DELHI 110 019 | SOUTH EAST | DELHI | 110019 | L4 | Rejected-Finance L4 FOR REJECTED | |
| 5 | L5₹20.2 L+₹3.8 L (23.4%)Rejected-Finance HOUSE NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR PB 144022 | JALANDHAR | JALANDHAR | PUNJAB | 144022 | L5 | Rejected-Finance L5 FOR REJECTED |
Tender Value
Refer Docs
EMD Value
₹34,380
Closing Date
19 Oct 2021, 6:00 pmClosed
HQ COMMANDER WORKS ENGINEER SRI GANGANAGAR
HQ CWE POST BOX 48 SRI GANGANAGAR-335001 (Rajasthan)
CA NO CWE SGNR 30 OF 2021-22 PROVISION OF STANDBY TRANSFORMER OF 500 KVA TROLLEY MOUNTED INCLUDING HT/LT CABLES AT MIL STATION ABOHAR
2021_MES_466869_3
CA NO. CWE SGNR - 30 OF 2021-22
Open Tender
Civil Works
Item Rate
180 days
GE ABOHAR
CLASS-E
CATEGORY-B(ii)
10 documents required · 10 mandatory
₹500
₹34,380
Yes
11 Nov 2021
28 Sept 2021
21 Oct 2021
28 Sept 2021
19 Oct 2021
5 Oct 2021
Amount
Supply, installation, testing and commossioning out door type step down transformer 11000/443 volts (at no load) AC 3 phase, 50 Hz of capacity 500 KVA core type, double copper wound, oil immersed naturally cooled, oil natural, air natural (ONAN) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol DYN-11 ( Vector group) with neutral brought out on secondary side (LV side) and having tapping at + 2.5 % to 7.5% HV side to be changed by means of hand operated off load tape changer gear, suitable for mounting on trolly for using stand by transformer complete with standard fittings and accessories. The maximum temperature rise should not exceed 45 degree celsius in oil and 55 degree celsius in HV / LV winding when measured by resistance method after continuous full load run on an ambient temp of 40 degree celsius. the transformer shall be as per IS-1180 Part- I: 2014 marked and shall comprise of the following complete all as specified and directed by Engineer-in-Charge. (a) 3 Nos procelian arc bushing on HT side suitable for 11 KV complete with bushing, copper rods, nuts and washers etc. (b) One cable box on LT side ( secondary) side consisting of four nos procelian bushing with copper rods, complete with nuts washers with two nos cable glands suitbale for reception ) taking out of XLPE insulated Heavy duty armoured cable including gland, joint and jointing materials complete. (c) Certificate for die electric strength of oil shall be submitted by the contractor after filling oil.
Contd........ (d) Duty type continuous duty copper wound (e) Core type cold rolled grain oriented (CRGO) steel and HV and LV side withstand voltage 28/3 KV (f) Provision of name plate over the transformer complete details of manufacturer technical specification and drawing in all respects (g) Provision of oil level indicators,filter valve with plug , drain cum sampling value ,conservator with oil filling hole , thermometer pocket, dial type oil temp indicator with max indicating pointer, air release plug, silica gel breather, unidirectional wheel , vent with raised pipe , fst filling of transformer oil confirming ti IS : 335 (h) Cooling radiators direct mount on transformer tank.
Supply and fabrication of rigidly welded construction ribbed, MS 4 wheel tractor trolly industrial type suitable for accomodating out door type transformer of 500 KVA capacity upto 10TON cap of following dimensions not less than :- (I) Height- 2.0 mtr (ii) Length - 13 feet (iii)Width- 6.5 feet axle- 75 mm rim 16 Inches, chassis 6" x 3" channels of C type cross channel over chassis should be of min 100 mm x 50 mm size having at least six cross members and two longitudinal member. frame: 4" 2" channels floor ship plate using 6 mm thick, side body CR sheets angles 50 mm x 6 mm and fabricated out of MS channel angle iron of suitable and MS sheet of 6 mm thick including painting with two coats of synthetic enamelled paint over a coat of red oxide and the trolly comprises of the following :- (a) Toeing arrangements with suitable size of toeing hook and attachment incl rotating gear arrangments. (b) Tyre assy: 4 numbers wheel of suitable size tractor tyres (double plated ring type with 8 holes) and accordingly tyre shourld be branded of JK/MRF/Appolo/Good year should be double plated made one wheel rim should have two plates complete with wheel drum and leaf spring mounted on square/round axil bar to take load upto 10 ton. (c) XPM metal fencing mount on angle iron frame of size 40 mm x 5 mm incl opening door complete with locking arrangements (d) MS cable wheel drum 02 Nos with operating handle for HT cable and LT cable of 100 RM length for removing/winding suitable (e) wheel hub heavy duty of 08 holes with branded wheel bearings (f) towing hook spring loaded towing hook of mim 36 mm MS rod. (g) Jack: provision of two suitable jack as per capacity mentioned above and incl all connected accessories all as specified and directed by Engr-in-charge.
Supplying, laying, jointing and testing XLPE insulated, screened,PVC beded,galvanised steel strip or wire armoured,clectric power cables (heavy duty )with aluminium conductor HT cable 11000 volts grade with cross sectional area 95 sqmm 3 core complete all as specified & directed by Engineer-in- charge.
Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (Heavy Duty) with stranded aluminium conductor, 1100 volts grade of size 3.5 core 240 Sqmm complete all as specified and directed by Engineer-in-Charge.
Supply and fix cable jointing kit for HT 11 KV grade cable for out door termination heat shrink type complete with joining material and accessories suitable for 3 core XLPE armoured AI conductor cable of size 95 Sqmm complete all as specified and directed by Engineer-in-Charge.
Supply and fix cable jointing kit for 1100 Volt grade cable for out door termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured Al conductor cable of size for 240 sq mm complete all as specified and directed by Engineer-in-Charge. --------------------------------------------------------------------------------------------------------------
jassal engineering
N.R.Builders
MONA GENERATOR SEVICES PVT. LTD.
UNITED ENGINEERING CORPORATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .