GE AF SRINAGAR
GE AF SRINAGAR AF STN SRINAGAR 190007
REPAIR/ROUTINE MAINTENANCE OF DG SETS INSTALLED AT VARIOUS LOCATIONS UNDER GE (AF) SRINAGAR.
2023_MES_599163_2
GE(AF)SGR-43 OF 2023-24
Open Tender
Civil Works
Item Rate
365 days
GE AF SRINAGAR
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE (AF) SRINAGAR
₹60,000
Yes
8 Nov 2023
10 Aug 2023
1 Sept 2023
10 Aug 2023
31 Aug 2023
17 Aug 2023
Amount
Note for all items of this BOQ: - Contractor special is invited that at site DG set of Make:- Kirloskar / Cummins / Greaves / Ruston are installed. Make of spear part of DG set shall be as recommended by OEM, except for the items make specified under respective item(s) of this BOQ.
Phase I
Deployment of manpower / tools etc for carrying out Preventive Maintenance / routine maintenance as 'B' check norms for DG Set of capacity 7.5 KVA to 40 KVA ( Make:- Kirloskar / Cummins / Greaves / Ruston) through authorised / approved agency by OEM, comprising Inspection and checking as per B-check parameter i.e. lubrication service, lube oil filter, cooling system, fuel system, fuel filter, servicing of air filter and bypass filter, servicing and testing carried out of batteries, engine including replacement of oil filters, fuel filters, air filter, 'O' rings and drain out the old engine oil and filling up with the new engine oil including testing of diesel generator complete all as specified and directed by the Engr- in- charge
Deployment of manpower / tools etc for carrying out Preventive Maintenance / routine maintenance as 'B' check norms for DG Set of capacity 55 KVA to 100 KVA ( Make:- Kirloskar / Cummins / Greaves / Ruston) through authorised / approved agency by OEM, comprising Inspection and checking as per B-check parameter i.e. lubrication service, lube oil filter, cooling system, fuel system, fuel filter, servicing of air filter and bypass filter, servicing and testing carried out of batteries, engine including replacement of oil filters, fuel filters, air filter, 'O' rings and drain out the old engine oil and filling up with the new engine oil including testing of diesel generator complete all as specified and directed by the Engr- in- charge
Deployment of manpower / tools etc for carrying out Preventive Maintenance / routine maintenance as 'B' check norms for DG Set of capacity 125 KVA to 250 KVA (Make:- Kirloskar / Cummins / Greaves / Ruston) through authorised / approved agency by OEM, comprising Inspection and checking as per B-check parameter i.e. lubrication service, lube oil filter, cooling system, fuel system, fuel filter, servicing of air filter and bypass filter, servicing and testing carried out of batteries, engine including replacement of oil filters, fuel filters, air filter, 'O' rings and drain out the old engine oil and filling up with the new engine oil including testing of diesel generator complete all as specified and directed by the Engr- in- charge
Deployment of manpower / tools etc for carrying out Preventive Maintenance / routine maintenance as 'B' check norms for DG Set of capacity 400 KVA to 625 KVA ( Make:- Kirloskar / Cummins / Greaves / Ruston) through authorised / approved agency by OEM, comprising Inspection and checking as per B-check parameter i.e. lubrication service, lube oil filter, cooling system, fuel system, fuel filter, servicing of air filter and bypass filter, servicing and testing carried out of batteries, engine including replacement of oil filters, fuel filters, air filter, 'O' rings and drain out the old engine oil and filling up with the new engine oil including testing of diesel generator complete all as specified and directed by the Engr- in- charge
Note For Item No 1 to 4: (i) Engine oil, spares parts will be measured and paid separately as supply only under relevant items of this BOQ. (ii) Cleaning & maintenance of Radiator & Oil cooler will be measured and paid separately under relevant items of this BOQ. (iii) The contractor shall submit documentary evidence that maintenance / servicing done by OEM of DG set and same shall be defaced by Engineer-in-Charge.
Supply & Filling inhibitor corrosion anti freeze coolant filling in DG set of capacity 7.5 to 625 KVA complete all as specified and as directed by the Engineer-in-Charge.
Supply only Engine oil 20W/40 complete all as specified and directed by Engr-in-charge. Make :- Castrol / Servo / Indian Oil
Supply only air cleaning element inner and outer with necessary ‘O’ rings suitable for DG Set of capacity 7.5 to 40 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only air cleaning element inner and outer with necessary ‘O’ rings suitable for DG Set of capacity 55 to 100 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only air cleaning element inner and outer with necessary ‘O’ rings suitable for DG Set of capacity 125 to 250 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only air cleaning element inner and outer with necessary ‘O’ rings suitable for DG Set of capacity 400 to 625 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only fuel filter with ‘O’ rings suitable for DG Set of capacity 7.5 to 40 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only fuel filter with ‘O’ rings suitable for DG Set of capacity 55 to 100 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only fuel filter with ‘O’ rings suitable for DG Set of capacity 125 to 250 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only fuel filter with ‘O’ rings suitable for DG Set of capacity 400 to 625 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only Lub Oil filter with ‘O’ rings suitable for DG Set of capacity 7.5 to 40 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only Lub Oil filter with ‘O’ rings suitable for DG Set of capacity 55 to 100 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only Lub Oil filter with ‘O’ rings suitable for DG Set of capacity 125 to 250 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Supply only Lub Oil filter with ‘O’ rings suitable for DG Set of capacity 400 to 625 KVA as per existing make and model complete all as specified and as directed by the Engineer-in-Charge.
Phase II
M&L for disconnecting the oil cooler from DG Set of capacity 7.5 to 40 KVA (Make:- Kirloskar / Cummins / Greaves / Ruston) from the the existing locations by removing of all mechanical connections and taking down from the engine for complete servicing, opening into parts and cleaning thoroughly by using chemical cleaning and pressure testing, refixing back to its original positions with 'O' rings / gaskets complete all as specified and directed by the Engg- in- Charge
M&L for disconnecting the oil cooler from DG Set of capacity 55 to 100 KVA (Make:- Kirloskar / Cummins / Greaves / Ruston) from the the existing locations by removing of all mechanical connections and taking down from the engine for complete servicing, opening into parts and cleaning thoroughly by using chemical cleaning and pressure testing, refixing back to its original positions with 'O' rings / gaskets complete all as specified and directed by the Engg- in- Charge
M&L for disconnecting the oil cooler from DG Set of capacity 125 to 250 KVA (Make:- Kirloskar / Cummins / Greaves / Ruston) from the the existing locations by removing of all mechanical connections and taking down from the engine for complete servicing, opening into parts and cleaning thoroughly by using chemical cleaning and pressure testing, refixing back to its original positions with 'O' rings / gaskets complete all as specified and directed by the Engr- in- Charge
M&L for disconnecting the oil cooler from DG Set of capacity 400 to 625 KVA (Make:- Kirloskar / Cummins / Greaves / Ruston) from the the existing locations by removing of all mechanical connections and taking down from the engine for complete servicing, opening into parts and cleaning thoroughly by using chemical cleaning and pressure testing, refixing back to its original positions with 'O' rings / gaskets complete all as specified and directed by the Engg- in- Charge
M&L for disconnecting all the incoming and out going rubber hoses and drain out the water from the choked radiator assembly of DG sets of capacity 7.5 to 40 KVA, taking down the radiator assembly by unscrewing all mechanical connections from the existing mounting, transporting the same to civil workshop for carrying out Chemical cleaning, opening the top and bottom covers of the radiator assembly cleaning thoroughly the chocked pipe of the radiator, cleaning of all the deposited sediments in the pipes / tubes including arresting of leakage by means of soldering, brazing and re-fixing the same to its original position with suitable size of nut, bolt and washers etc, complete all as specified and directed Engineer-in-Charge.
All as per item No 23 above for carrying out all the work mention under item No 23 above and including replacement of old unserviceable copper core and fins completely with new Copper Core and fins, pressure testing, complete all as specified and directed Engineer-in-Charge. Note : - (i) Repair maintinance of rediater work shall be carried out through authorised agency by OEM. (ii) The contractor shall submit documentary evidence that maintenance / servicing done by OEM of DG set and same shall be defaced by Engineer-in-Charge.
M&L for disconnecting all the incoming and out going rubber hoses and drain out the water from the choked radiator assembly of DG sets of capacity 55 to 100 KVA, taking down the radiator assembly by unscrewing all mechanical connections from the existing mounting, transporting the same to civil workshop for carrying out Chemical cleaning, opening the top and bottom covers of the radiator assembly cleaning thoroughly the chocked pipe of the radiator, cleaning of all the deposited sediments in the pipes / tubes including arresting of leakage by means of soldering, brazing and re-fixing the same to its original position with suitable size of nut, bolt and washers etc, complete all as specified and directed Engineer-in-Charge.
All as per item No 25 above for carrying out all the work mention under item No 25 above and including replacement of old unserviceable copper core and fins completely with new Copper Core and fins, pressure testing, complete all as specified and directed Engineer-in-Charge. Note : - (i) Repair maintinance of rediater work shall be carried out through authorised agency by OEM. (ii) The contractor shall submit documentary evidence that maintenance / servicing done by OEM of DG set and same shall be defaced by Engineer-in-Charge.
M&L for disconnecting all the incoming and out going rubber hoses and drain out the water from the choked radiator assembly of DG sets of capacity 125 to 250 KVA, taking down the radiator assembly by unscrewing all mechanical connections from the existing mounting, transporting the same to civil workshop for carrying out Chemical cleaning, opening the top and bottom covers of the radiator assembly cleaning thoroughly the chocked pipe of the radiator, cleaning of all the deposited sediments in the pipes / tubes including arresting of leakage by means of soldering, brazing and re-fixing the same to its original position with suitable size of nut, bolt and washers etc, complete all as specified and directed Engineer-in-Charge.
All as per item No 27 above for carrying out all the work mention under item No 27 above and including replacement of old unserviceable copper core and fins completely with new Copper Core and fins, pressure testing, complete all as specified and directed Engineer-in-Charge. Note : - (i) Repair maintinance of rediater work shall be carried out through authorised agency by OEM. (ii) The contractor shall submit documentary evidence that maintenance / servicing done by OEM of DG set and same shall be defaced by Engineer-in-Charge.
M&L for disconnecting all the incoming and out going rubber hoses and drain out the water from the choked radiator assembly of DG sets of capacity 400 to 625 KVA, taking down the radiator assembly by unscrewing all mechanical connections from the existing mounting, transporting the same to civil workshop for carrying out Chemical cleaning, opening the top and bottom covers of the radiator assembly cleaning thoroughly the chocked pipe of the radiator, cleaning of all the deposited sediments in the pipes / tubes including arresting of leakage by means of soldering, brazing and re-fixing the same to its original position with suitable size of nut, bolt and washers etc, complete all as specified and directed Engineer-in-Charge.
All as per item No 29 above for carrying out all the work mention under item No 29 above and including replacement of old unserviceable copper core and fins completely with new Copper Core and fins, pressure testing, complete all as specified and directed Engineer-in-Charge. Note : - (i) Repair maintinance of rediater work shall be carried out through authorised agency by OEM. (ii) The contractor shall submit documentary evidence that maintenance / servicing done by OEM of DG set and same shall be defaced by Engineer-in-Charge.
S&F in repair battery cable leads of copper conductor single core, multistranded, 25 Sqmm, PVC insulated, with copper lugs at both ends and connecting from battery bank to self starter (Apprx. 1.00 m long) complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair battery cable leads of copper conductor single core, multistranded, 35 Sqmm, PVC insulated, with copper lugs at both ends and connecting from battery bank to self starter (Apprx. 1.00 m long) complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair battery cable leads of copper conductor single core, multistranded, 50 Sqmm, PVC insulated, with copper lugs at both ends and connecting from battery bank to self starter (Apprx. 1.00 m long) complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair battery cable leads of copper conductor single core, multistranded, 75 Sqmm, PVC insulated, with copper lugs at both ends and connecting from battery bank to self starter (Apprx. 1.00 m long) complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair battery cable leads of copper conductor single core, multistranded, 95 Sqmm, PVC insulated, with copper lugs at both ends and connecting from battery bank to self starter (Apprx. 1.00 m long) complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of alternator of DG Set of capacity 7.5 to 40 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of alternator of DG Set of capacity 55 to 100 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of alternator of DG Set of capacity 125 to 250 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of alternator of DG Set of capacity 400 to 625 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of Water pumps of DG Set of capacity 7.5 to 40 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of Water pumps of DG Set of capacity 55 to 100 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of Water pumps of DG Set of capacity 125 to 250 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of Water pumps of DG Set of capacity 400 to 625 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of Fan of DG Set of capacity 7.5 to 40 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of Fan of DG Set of capacity 55 to 100 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of Fan of DG Set of capacity 125 to 250 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair V Belt of Fan of DG Set of capacity 400 to 625 KVA as per existing size complete all as specified and as directed by the Engineer-in-Charge.
M&L for taking out / dismantling of Turbo charger from DG sets of capacity 7.5 to 40 KVA and carrying out maintenance wks i.e. opening, cleaning and replacement of turbo charger kit ( i.e. shaft, O ring, bearing / bush and nut bolts) clamps hoses including calibration of turbo charger, through authorised agency / work shop by OEM and refixing Turbo charger in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismantling of Turbo charger from DG sets of capacity 55 to 100 KVA and carrying out maintenance wks i.e. opening, cleaning and replacement of turbo charger kit ( i.e. shaft, O ring, bearing / bush and nut bolts) clamps hoses including calibration of turbo charger, through authorised agency / work shop by OEM and refixing Turbo charger in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismantling of Turbo charger from DG sets of capacity 125 to 250 KVA and carrying out maintenance wks i.e. opening, cleaning and replacement of turbo charger kit ( i.e. shaft, O ring, bearing / bush and nut bolts) clamps hoses including calibration of turbo charger, through authorised agency / work shop by OEM and refixing Turbo charger in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismantling of Turbo charger from DG sets of capacity 400 to 625 KVA and carrying out maintenance wks i.e. opening, cleaning and replacement of turbo charger kit ( i.e. shaft, O ring, bearing / bush and nut bolts) clamps hoses including calibration of turbo charger, through authorised agency / work shop by OEM and refixing Turbo charger in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismentling of self starter from DG sets of capacity 7.5 to 40 KVA and carrying out maintenence wks i.e. opening, cleaning and replacement of starter winding, turbo bushes and bearings through authorised agency / work shop by OEM and refixing self starter in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismentling of self starter from DG sets of capacity 55 to 100 KVA and carrying out maintenence wks i.e. opening, cleaning and replacement of starter winding, turbo bushes and bearings through authorised agency / work shop by OEM and refixing self starter in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismentling of self starter from DG sets of capacity 125 to 250 KVA and carrying out maintenence wks i.e. opening, cleaning and replacement of starter winding, turbo bushes and bearings through authorised agency / work shop by OEM and refixing self starter in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismentling of self starter from DG sets of capacity 400 to 625 KVA and carrying out maintenence wks i.e. opening, cleaning and replacement of starter winding, turbo bushes and bearings through authorised agency / work shop by OEM and refixing self starter in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismentling of alternator assembly from DG sets of capacity 7.5 to 40 KVA and carrying out maintenence wks i.e. opening , cleaning, replacement of starter winding, carbon bushes , bearings and diodes through authorised agency / work shop by OEM and refixing self starter in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismentling of alternator assembly from DG sets of capacity 55 to 100 KVA and carrying out maintenence wks i.e. opening , cleaning, replacement of starter winding, carbon bushes , bearings and diodes through authorised agency / work shop by OEM and refixing self starter in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismentling of alternator assembly from DG sets of capacity 125 to 250 KVA and carrying out maintenence wks i.e. opening , cleaning, replacement of starter winding, carbon bushes , bearings and diodes through authorised agency / work shop by OEM and refixing self starter in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / dismentling of alternator assembly from DG sets of capacity 400 to 625 KVA and carrying out maintenence wks i.e. opening , cleaning, replacement of starter winding, carbon bushes , bearings and diodes through authorised agency / work shop by OEM and refixing self starter in same position after repairs, testing and commissioning complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
Supply & Fix in repair Hinges of door of acoustic enclosure of DG Set of any capacity by removing old hinges and welding new hinges as per existing pattern for smooth opening of door complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
M&L for taking out / desmentling of unserviceable auto mains failures unit from DG set of capacity 7.5 KVA to 40 KVA and replace by new wiring harness via 2 Nos connectors of suitable capacity / specification of existing AMF unit installed at site including complete installation, testing and commissioning wks carried out through authorised agency / work shop complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge
All as per item No 61 above but DG Set of capacity 55 to 100 KVA complete all as specified and directed by the Engr- in- charge.
All as per item No 61 above but DG Set of capacity 125 to 250 KVA complete all as specified and directed by the Engr- in- charge.
All as per item No 61 above but DG Set of capacity 400 to 625 KVA complete all as specified and directed by the Engr- in- charge.
M & L for taking out / desmentling / dismounting of fuel injector pump from DG Set, transporting to workshop for calibrating and replacement of worn out parts like TD piston,service kit including all types of filter and including filling of new engine oil 15W40 required, compressor spring, cam bush, alternator bush, supplier pump, TR pin bush, and packing kit including pressure setting, connecting to Lathe work and replacing unserviceable AVR complete with control wiring and refixing the same and complete installation, testing and commissioning wks carried out through authorised agency / work shop for the capacity of DG sets 7.5 to 40 KVA complete all as specified and directed Engineer-in-Charge.all as specified and directed by Engr-in-charge.
All as sl item No 65 but capacity of DG Set 55 to 100 KVA complete all as specified and directed by the Engr- in- charge
All as sl item No 65 but capacity of DG Set 125 to 250 KVA complete all as specified and directed by the Engr- in- charge
All as sl item no 65 but capacity of of DG Set 400 to 625 KVA complete all as specified and directed by the Engr- in- charge
Material and Labour for supply, fabricate, installation, testing and Commissioning LT Indoor panel, weather proof, dust / vermin proof, powder coated, made out of 2.0 mm thick CRCA Sheet, double openable door and necessary hinges, IE-65 distribution pillar CPRI approved manufacturer, IP-65 Protection, 415 V with necessary double compression Copper, SS gland for incoming and outgoing cable suitable size PCC (1:2:4) TYPE B1 (Using 20 mm Graded aggregate) raised base with control internal wiring etc and Comprising of Cooling fan and other accessories as mentioned below:-
(a) Air Circuit Breaker 800 Amps with Microprocessor , 3 pole, 415 Volts, 50 Hz ICU 50 KA thermally adjustable between 70-100% - 01 Nos.( Incoming for 500 KVA Dg Set) Make- Havells Cat Part No.-IHATE1E080** or Equivalent cat No of Make C&S, L&T
(ii) Indication lamp 22.5 mm dia LED type, 240 Volts AC at the incommer of the unit to show 3 phase availability at the outgoing of incommer with back up protection by 2 Amp MCB.
(iii) Inspection lamp 50 Watt with movable non ferrous chromium plated arm fitted on topside of inner shell.
Note- The unit rate includes the PCC work for the foundation and fixing the panel at requisite location all as Specified and directed by Engr-in-charge.
M&L for overhauling of DG set of capacity 125 to 250 KVA (Make of Engine: Greaves and Make of Alternator:Stamford) by opening complete engine replacing worn- out / unserviceable parts like connecting rod, piston, piston rings, gear and Pinnion set etc, and reassembling the engine, coupling engine with alternator including alignment and testing and commissioning of DG set complete all as specified and directed by Engr-in-charge.
Note:- (i) Engine oil, spares parts will be measured and paid separately as supply only under relevant items of this BOQ. (ii) Cleaning & maintenance of Radiator & Oil cooler will be measured and paid separately under relevant items of this BOQ. (iii) Overhauling shall be carried out by authorised agency by OEM, the contractor shall submit documentary evidence for the same and same shall be defaced by Engineer-in-Charge.
(iv) The Quoted rate shall be deemed to be inclusive of engine head grinding, intake and exhaust valve grinding/ seating , testing and calibration of fuel injection pump and injectors
(v) Diesel for testing purpose shall be supplied by the contractor without any extra cost to department
Supply only following spares parts for the DG set of capacity 125 to 250 KVA complete all as specified and directed Engineer-in-Charge. Make of Engine: Greaves and Make of Alternator:Stamford
Piston Set of 4
Piston Ring (comprising oil ring & compression ring) Set of 4
Cylinder liner set of 4
Cylinder liner 'O' ring set of 4
Connection rod Bearing
Upper Gasket
Sump Gasket
Air Filters
B check Filters kit
Radiators hose
Clamps for radiators hose
Cooler Hose
Water Safety Switch
Valve Intake
Valve Exhaust
Valve seat guide (Intake/Exhaust)
Valve Guide
Valve Collet (Locks)
Injector Sleeve
Injectors 'O' ring
Engine top
Head Wall
Connecting Rod
Injector Pipe
M&L for taking out / desmentling / dismounting Accoustic Doors / panel (Top, Left, right), and supply & fix new Accoustic Doors / panel fabricated with CRCA Sheet & FR Acoustic Foam, and Pure Polyester Powder coting on exposed face, including all fitting & fixture, hinges, locking arrangment complete for DG set of any capacity all as directed by Engineer-in-Charge.
S&F in repair microprocessor based speed control units for DG sets of capacity 7.5 to 40 KVA, including supply, installation, commissioning and testing of of this units at existing site and offer precise (+/- 0.25%) speed control with fast response to transient load changes in isochronous, Droop & Variable Operation, Starting Fuel & Speed Ramping Adjustument, Soft Coupling, Lead Circuit Auxiliary Input & 10V Supply Overspeed Contact complete all as specified and directed Engineer-in-Charge. Note- The item should be made Governers america Cop or equvallent approved by GE.
All as sl item No 73 but DG Set capacity of 55 to 100 KVA complete.
All as sl item No 73 but DG Set capacity of 125 to 250 KVA complete.
All as sl item No 73 but DG Set capacity of 400 to 625 KVA complete.
Supply & Fix in repair Magnetic Pick up Mpu set for DG set of capacity 7.5 to 40 KVA having resistance value 300 ohms max, Temperature range in between -55 Degree celsius to 105 Degree celsius, made of metal material, with ideal output of 1.5 volts AC main and Max output 30 voltage AC complete all as specified and directed Engineer-in-Charge. Note- The item should be made Governers america Cop or equvallent approved by GE.
All as sl item No 77 but DG Set capacity of 55 to 100 KVA complete.
All as sl item No 77 but DG Set capacity of 125 to 250 KVA complete.
All as sl item No 77 but DG Set capacity of 400 to 625 KVA complete.
Supply & Fix in repair Microprocessor based Automatic Mains Failure Controller, for AMF panel of DG set of capacity 125 to 250 KVA, comprising following alarms through LED / LCD (a) Mains fail, (b) LLOP (c) High cylinder / water temperature, (d) Over speed, (e) Under speed, (f) Alternator fault, (g) DG fail to start, (h) DG fail to stop, (i) Overload, (j) Fuel low, (k) Fuel very low (for stopping of engine), (l) Battery Voltage low, (m) DG fault (common for any DG fault), (n) Canopy door open, (o) Fire Alarm, (p) Canopy temperature high, (q) Low water level (for water cooled sets), (r) Over / Under voltage, (s) Over / Under frequency, fixed in position in AMF panel and connecting with copper conductor cable & lugs complete all as specified & directed by Engineer-in-Charge.
All as per Item No 81 above but AMF panel of DG set of capacity 400 to 625 KVA and ditto.
M&L for repairs to LT panel boards of any size with necessary welding works to doors, replacement of unserviceable hinges and all drop bolt and painting with one coat of synthetic enamel paint of approved color internally and externally complete all as specified and as directed by Engineer-in-Charge
Supply & fix in repair 6 mm thick mild steel plain / chequered plate cut to size and fixed as in cable duct cover complete all as specified and as directed by Engr-in-charge.
M&L for Steel water tubing light grade of dia 50 mm galvanized with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable complete including taking down old pipe all as specified and directed by Engr-in-Charge.
M&L for Steel water tubing light grade of dia 80 mm galvanized with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable complete including taking down old pipe all as specified and directed by Engr-in-Charge.
Excavation in trenches, in hard desse soil, not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr in depth, for foundation & similar work etc complete all as specified and all as directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick, using excavated soil complete all as specified and as directed.
Removing of excavated soils to a distance not exc. 50 metre and depositing where directed at a level n.exc 1.5m above the starting point.
M&L for Plain cement concrete 1:4:8, type D-2 (using 40mm graded crushed stone aggregate) as in foundations, filling and mass concrete including demolition of old damaged PCC, complete all as specified and as directed.
M&L for PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate as in platform for Panel, VCB, transformer & similar work including weathering, slightly rounded or chamfered angles as directed with form work and finishing of all exposed surfaces complete including demolition of old platform all as specified and as directed.
S&F 0.50 mm thick Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall or roof, fixed with self tapping / drilling screws as specified and as directed by Engineer-in-charge
Supply & fix in repair X Cell POWER PACK (Genset Starting Unit), comprising 2 Nos pure lead tin Maintenance Free Valve Regulated (MF-VRLA) Battery, 12V - 32Ah, and built in Constant Voltage (SMPS) charger having output 24 Volt, Amps with, AC under & Over Voltage protection, Output Short Circuit protection, Overload protection, Output over voltage protection and High Temperature protection, fxed in position and connecting including taking down old power pack and deposit in the storyard of AGE E&M complete all as specified and directed by Engr-in-charge Make :- HBL Model No.DG2XL500 or equivalent make approved by GE.
Supply & fix in repair X Cell POWER PACK (Genset Starting Unit), comprising 2 Nos pure lead tin Maintenance Free Valve Regulated (MF-VRLA) Battery, 12V - 80Ah, and built in Constant Voltage (SMPS) charger having output 24 Volt, Amps with, AC under & Over Voltage protection, Output Short Circuit protection, Overload protection, Output over voltage protection and High Temperature protection, fxed in position and connecting, including taking down old power pack and deposit in the storyard of AGE E&M complete all as specified and directed by Engr-in-charge. Make :- HBL Model No.DG2XL750 or equivalent make approved by GE.
Supply & fix in repair Lead acid Battery, Maintenance free, high charge characteristic having battery capacity 90 AH, 12 V, filled and factory charged for Diesel Generator Set of any capacity, including taking down old battery and deposit in the storyard of AGE E&M complete all as specified and directed by Engr-in-charge. Make :- Exide Model No.- Exide Genplus (GP110D31L) or Equivalent model No of Make Okaya, Luminous Note- Contractor shall submit 2 year manufacturer warrantee to Engineer-in-Charge.
Supply & fix in repair Lead acid Battery, Maintenance free, high charge characteristic having battery capacity 130 AH, 12 V, filled and factory charged for Diesel Generator Set of any capacity, including taking down old battery and deposit in the storyard of AGE E&M complete all as specified and directed by Engr-in-charge. Make :- Exide FIO0-INVAMORE1300 or Equivalent model No of Make Okaya, Luminous Note- Contractor shall submit 2 year manufacturer warrantee to Engineer-in-Charge.
Supply & fix in repair Lead acid Battery, Maintenance free, high charge characteristic having battery capacity 180 AH, 12 V, filled and factory charged for Diesel Generator Set of any capacity, including taking down old battery and deposit in the storyard of AGE E&M complete all as specified and directed by Engr-in-charge. Make :- Exide Inva plus FIMOMI-1800 or Equivalent model No of Make Okaya, Luminous Note- Contractor shall submit 2 year manufacturer warrantee to Engineer-in-Charge.
M&L for cleaning the carbon deposits inside the stack / cachiminy of exhaust manifold and repairing / welding of outer damage surge and insulated the same with asbestos rope complete all as spd and directed by Engr-in charge.
S&F in repair damage / wornout old exhaust manifold for DG set of capacity upto 500 KVA including painting and insulation with asbestos rope complete all as spd and directed by Engr-in charge.
M/s Jaipal Associates
M/S KHAN ENTERPRISES
M/s GHULAM NABI HAJAM
M/S LATIF AHMAD MIR
M/S M.Y Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .