Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.7 LAccepted-AOC | L1 | Accepted-AOC Awarded | |
| 2 | L2₹42.9 L+₹3.3 L (8.25%)Rejected-AOC 171 NARAYAN PETH PUNE PUNE MAHARASHTRA 411030 | PUNE | MAHARASHTRA | 411030 | L2 | Rejected-AOC Rejected | |
| 3 | L3₹43.2 L+₹3.6 L (9.03%)Rejected-AOC | L3 | Rejected-AOC Rejected | |
| 4 | L4₹43.7 L+₹4.0 L (10.2%)Rejected-AOC | L4 | Rejected-AOC Rejected | |
| 5 | L5₹46.6 L+₹6.9 L (17.5%)Rejected-AOC | L5 | Rejected-AOC Rejected |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
20 Jul 2023, 6:00 pmClosed
Garrison Engineer North Ahmednagar
Military Engineer Services Garrison Engineers (North) Nagar Pathardi Road Ahmednagar Fort Ahmednagar 414 002
Repair/Replacement of existing LT Electrical system including LT/UG cables LT overhead lines MCCBs LT panel Changeovers switches and other allied works in Stn units and KK Ranges are under GE (N) Ahmednagar
2023_MES_605298_1
8769 / E8
Open Tender
Miscellaneous Works
Item Rate
180 days
Garrison Engineer North Ahmednagar
Class D Cat b(i)
8 documents required · 8 mandatory
₹500
Garrison Engineer(North) Ahmednagar
₹98,000
Yes
10 Aug 2023
23 Jun 2023
22 Jul 2023
23 Jun 2023
20 Jul 2023
6 Jul 2023
Amount
Supply & Fixing and testing of LT cable 1100 volts grade XLPE insulated screened PVC bedded galvanised steel strip or wire aRMoured electric power cable (heavy duty) with aluminium conductor suitable for earthed system of size 240 sq mm 3.5 core in trenches, on poles and in ducts complete all as specified and directed by Engr in charge.
All as per item No. 01 above but size 150 sq mm 3½ core
All as per item No. 01 above but size 120 sq mm 3½ core
All as per item No. 01 above but size 95 sq mm 3½ core
All as per item No. 01 above but size 70 sq mm 3½ core
All as per item No. 01 above but size 50 sq mm 3½ core
All as per item No. 01 above but size 35 sq mm 3½ core
All as per item No. 01 above but size 25 sq mm 4 core
All as per item No. 01 above but size 16 sq mm 4 core
All as per item No. 01 above but size 10 sq mm 4 core
All as per item No. 01 above but size 16 sq mm 2 core
All as per item No. 01 above but size 10 sq mm 2 core
Excavation in trenches nexc 1.5 mtr in depth and not exceeding 1.5 Mtr wide for laying of cable/pipe etc and getting out in any type of soil complete all as specified nad directed.
All as per Item No.13 above but exceeding 1.5 mtr & not exceeding 3 mtr in depth.
Returning filling in trenches excavated soil including spreading levelling watering and well ramming in layers n.exc 25 cm thick EACH layer as in soil complete all as specified nad directed..
Removing excavated materials n.exc 50 mtr depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified nad directed.
Supply & laying of HDPE pipe ISI mark of outer dia 110 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable icluding coupler and bends etc complete all as specified and directed by Engineer-in-Charge Make : Supreme / Infra / Astral/Prince/jain irrigation
Supply & laying of HDPE pipe ISI mark of outer dia 63 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable icluding coupler and bends etc complete all as specified and directed by Engineer-in-Charge Make : Supreme / Infra / Astral/Prince/jain irrigation
Supply & laying of HDPE pipe ISI marked outer dia 50 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable icluding coupler and bends etc complete all as specified and directed by Engineer-in-Charge Make : Supreme / Infra / Astral/Prince/jain irrigation
M/L for GI Tubes, of size 40mm dia Medium grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed.
M/L for GI Tubes, of size 50mm dia Medium grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed.
M/L for GI Tubes, of size 80mm dia Medium grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed.
M&L for road cutting upto 300mm deep and 200mm wide for crossing GI pipe line through road including making good the disturbed surface by filling mass concrete( 1:2:4) etc complete all as specified and directed by Engineer-in-Charge. Note : Rate of mass concrete is included in quated rate.
Demolation of u/s cement concrete in coppings etc complete all as specified and directed by Engineer-in-Charge.
M & L for PCC(1:2:4) type C-2 using 20mm grade stone aggregates for coping and similar work all as specified and directed.
S&F PVC Junction box of size 200x175x100mm, IP 66 with hinged door including locking arrangment and MCB SP 6 Amp with necessary nut,bolt etc and including TPN aluminium bus bar mounted on insulators with suitable holes to provide incoming and outgoing LT cables and street light MCB complete all as specified and directed
Supply and fixing wiring for circuit/submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, Three core cable in surface/recessed as required 2x 1.5 sq. mm + 1 x 1.5 sq. mm earth wire (From PVC Junction box to Security light)
Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 500 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater,internal wiring with suitable size of copper wire,panel should be dust proof,veRMin proof,powder coated,locking should be screw type,mechanical type,inter locking,should have danger notice for 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and stainless steel glands Nuts & Bolts complete all as specifid and directed.(Main Panel)Note: All MCCB Shall be TheRMal and Magnetic adjustable type as per IEC 6047-II
(i) Incoming MCCB 4P, 250 Amp, 50 KA,theRMal and magnetic adjustable -01 No ( Ics = 100% Icu) (ii) Outgoing MCCB 4P, 160 Amp, 36 KA,theRMal and magnetic adjustable -01 No ( Ics = 100% Icu) (iii) Outgoing MCCB 4P 100 Amp,36 KA -02 Nos ( Ics = 100% Icu) (iv) Outgoing MCCB 4P 63 Amp, 25 KA -02Nos ( Ics = 100% Icu) (v) Digital voltmeter & Ammeter with necessary CTs (vi) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm (vii) Phase indicating LED lamps (R-Y-B) -01 SET (viii) Spare chamber for MCCBs - 01 Nos
Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 250 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater,internal wiring with suitable size of copper wire,panel should be dust proof,veRMin proof,powder coated,locking should be screw type,mechanical type,inter locking,should have danger notice for 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and stainles steel glands Nuts & Bolts complete all as specifid and directed.Note: All MCCB Shall be TheRMal and Magnetic adjustable type as per IEC 6047-II
(i) Incoming MCCB 4P 100 Amp, 36 KA -01 No ( Ics = 100% Icu) (ii) Outgoing MCCB 4P 63 Amp, 25 KA -02Nos ( Ics = 100% Icu) (iii) Digital voltmeter & Ammeter with necessary CTs (iv) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm (v) Phase indicating LED lamps (R-Y-B) -01 SET (vi) Spare chamber for MCCBs - 01 Nos
Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 300 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater,internal wiring with suitable size of copper wire,panel should be dust proof,veRMin proof,powder coated,locking should be screw type,mechanical type,inter locking,should have danger notice for 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and glands Nuts & Bolts complete all as specifid and directed.Note: All MCCB Shall be TheRMal and Magnetic adjustable type as per IEC 6047-II
(i) Incoming MCCB 4P 125 Amp, 36 KA -01 No( Ics = 100% Icu) (ii) Outgoing MCCB 4P 100 Amp, 25 KA -01 No ( Ics = 100% Icu) (iii) Outgoing MCCB 4P 63 Amp, 25 KA -01 No ( Ics = 100% Icu) (iv) Digital voltmeter & Ammeter with necessary CTs (v) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm (vi) Phase indicating LED lamps (R-Y-B) -01 SET (vii) Spare chamber for MCCBs - 01 Nos
M & L for fabrication of bus bar chamber suitable for 415 volts 3 phase 4 wire system , outdoor type, double door, with pedestal mounted, weather and veRMin proof fabricated out of 3.15 mm thick MS CRCA sheet with anti corrosive coating & finally epoxy polyster powder coating of flint grey shade including 3 nos. phase indicating lamps, insertion of suitable cable glands for all incoming and out going cable including grouting of panel board 60 cm above & 30 cm below ground level duly supported on 50x50x6mm angle iron frame & welding 45 cm long angle iron legs of size 50x50x6mm on all the four corners embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm depth complete all as specified and directed by Engineer-in-Charge Comprising of 4 nos. Aluminium bus bar 200 Amp for phases & 50 Amp for neutral mounted on DMC/ porcelain insulator support complete all as specified and directed.Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II
M & L for fabrication of bus bar chamber suitable for 415 volts 3 phase 4 wire system , outdoor type, double door, with pedestal mounted, weather and veRMin proof fabricated out of 3.15 mm thick MS CRCA sheet with anti corrosive coating & finally epoxy polyster powder coating of flint grey shade including 3 nos. phase indicating lamps, insertion of suitable cable glands for all incoming and out going cable including grouting of panel board 60 cm above & 30 cm below ground level duly supported on 50x50x6mm angle iron frame & welding 45 cm long angle iron legs of size 50x50x6mm on all the four corners embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm depth complete all as specified and directed by Engineer-in-Charge Incoming MCCB : 200 AMps ,4P,25 KA Busbar Capacity : 400 AMps mounted on DMC/ porcelain insulator support Outgoing : one MCB/MCCB mounted chanel slotted 500 mm long
Notes:- For Item No 28, 29,30,31,32 1. The Panel Should be approved by CPRI. 2.The rates Quoted shall include for earth work,Plinth protection around the panel apprx 75cm and excavation for angle iron frame for foundation of panel board up to 0.50 m below GL in any type of soil and PCC 1:4:8 type D2 filling in foundation. The ground clearance of panel board shall be 0.40 M from GL to the bottom of panel board.
Supply M&L for earthing complete with galvanized steel earth plate electrode of size 60cm X 60 cm X 6 mm buried directly in ground (earth pit not less than 2.25m deep below the noRMal ground level) with top edge of plate not less than 1.5 m below the noRMal ground level connected to GI earth strip 32 X 6 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, protected by GI pipe light grade 40mm bore all as shown on electrical plate No 3 of SSR Part-I connected to earth test point electrode, PCC pit with RCC cover, funnel with wire mesh, watering pipe 20mm dia protection pipe etc and testing on completion complete all as specified and directed. Note No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I. Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
Supply M&L for earthing complete with galvanized steel earth plate electrode of size 60cm X 60 cm X 6 mm buried directly in ground (earth pit not less than 2.25m deep below the noRMal ground level) with top edge of plate not less than 1.5 m below the noRMal ground level connected to GI earth strip 25 x4 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, protected by GI pipe light grade 40mm bore all as shown on electrical plate No 3 of SSR Part-I connected to earth test point electrode, PCC pit with RCC cover, funnel with wire mesh, watering pipe 20mm dia protection pipe etc and testing on completion complete all as specified and directed. Note No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I. Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
M & L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead of 4mm dia galvanised iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion Note No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I. Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
Dismantling carefully the existing LT overhead line ACSR conductor with cross aRM of any size from its position by necessary disconnecting of conductor and removing complete all as specified and as directed
Dismantling stay assembly complete all as specified and directed
Dismantling of unserviceable existing cross aRMs made from channels, angles and unserviceable FI clamps, nuts, bolts etc from OH line and removing complete all as specified and as directed
S&F LT cable route indicator of Cast iron not less than 100 mm dia fixed through welding angle iron supoort of size 25 mm x 25mmx5mm thick ,600mm long including two coats of synthetic enamel paint(yellow in colour) over a coat of red oxide primer planted in a PCC foundation (PCC 1:3:6) , The whole assembly of PCC iron will be planted in ground upto 30 cm complete all as specified and directed.Note : Rate of PCC foundation included in quated rate
M&L for prunning and removing of tree branches touching to electric over head lines wild growth around LT /HT over head lines and around pole and stay complete to make clear span of 2 Mtr of tree both side of the OH line with JCB, Cutter and all tools, plants etc all as directed by Engineer-in-Charge. Note : (i) Distance between pole to pole will be measured and paid. (ii) Contractor has to take upmost care to avoid damage to existing lines/structures if Any breakdown of line caused during punning shall be made good without any extra cost. (iii) The contractor has to ensure the proper safety of the tradesmans to avoid any mishappening. If any mishappening occures the contractor will be solely responsible for it.
Supply, erecting and fixing in replacement of true vertical position of steel tubular swaged pole, 9 mtr long complete with cast iron base plate, finial taper plug, bolt, nuts and screws as specified and of type 410 SP-31, confoRMing to relevant IS, including one primer coat of red oxide and two coats of aluminium paint and two coats of bituminous paint inside and outside of botton portion up to 1.8 mtr length all as specified and provide circular bend 1 No of length 2 m including taking down existing complete all as specified and directed. (Excavation and earth work , foundation concrete and PCC coping shall be measured and paid separately)
M & L for replacement of Pin type, porcelain, vitreous, white,brown or green insulator including one galvanised mild steel spindle,two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade
M & L for replacement of shackle Type, Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers,insulator bolts, washers and nuts, 100mm height and 115mm dia including two nos of galvanised steel strap of size 31x5mm fitted with 14mm dia bolts and nuts all as per directed.
Supply, fixing and stringing ACSR conductor (Weasel/ Ferret) for over head line securing on pole complete including binding wire, jointing sleeves aluminium tap and PG clamp etc of any size all as specified and as directed. (Note :- (a)jumper on cutout point/2 pole structer/4 pole structure shall be provided with PVC insulated sleeve. (b) Rate is inclusive of jumpers materials & tree branch cutting to make a safe distance from over head line.)
M & L for repair of LT Panel board of any size with replacing the damagable angle iron frame, unserviceable MCCB,MCB,switch fuse unit , change over ,Busbar,etc jointig cable with proper lugs ,nut , bolt and washers, cleaning the panel by using of CRC Soluation and repairing thhe panel door by using hinges and repairing the lock system, welding etc painting the LT Panel wit one coat of primer & two coat of synthetic enamel paint as approved or as per direction of Engr-in-Charge. Note:(i) MCCB,MCB,Switch fuse unit and change over switch measured and paid separately. (ii) Labour for MCCB, MCB, Switch fuse unit and change over switch measured and paid separately. (iii)Rate of new Busbar, lugs,CRC Solution,nut,bolt, painting, panel lock etc and washers are deemed to be included in quoted rates.
Supply and fixing in replacement of MCB TPN 63 Amps with breaking cap 16 KA and connecting all as directed . Make : Legrand/ L&T/Siemens.
Supply and fixing in replacement of MCB DP, 40 Amps with 10 KA breaking / rupturing capacity including neccssary connection complete all as directed. MAKE: Legrand/ L&T/Siemens.
Supply and fix in replacement MCB, SP, 6 to 32 Amps 10 KA breaking / rupturing capacity capacity including necessary connection with suitable size of copper cable complete all as directed. MAKE: Legrand/ L&T/Siemens..
Supply and fixing in existing panel board for replacement MCCB, 4 Pole, 400 Amps , with breaking capacity 36 KA , TheRMal and magnetic adjustable (Ics=100%Icu) 415 volt ,50 HZ confoRMing to IEC:60947-II/IS:13947-II and connecting all as directed.
All as per item No 49 here in above but 200 Amps 25 KA breaking capacity.
All as per item No 49 here in above but 250 Amps 25 KA breaking capacity.
All as per item No 49 here in before but 160 Amps 25 KA breaking capacity.
All as per item No 49 here in before but 100 Amps 25 KA breaking capacity.
All as per item No 49 here in before but 63 Amps 25 KA breaking capacity.
Supply and fix in repairs on load change over switch existing panel, wall or LT pole of any size and any type on load type, four pole , 63 Amps, 415 V, 50 Hz front handle operated, including connecting and testing all as directed. MAKE: Indoasian/L & T/Havells
Supply and fix in repairs on load change over switch existing panel, wall or LT pole of any size and any type on load type, four pole , 100 Amps, 415 V, 50 Hz front handle operated, including connecting and testing all as directed. MAKE: Indoasian/L & T/Havells
Supply and fix in repairs on load change over switch existing panel, wall or LT pole of any size and any type on load type, four pole , 200 Amps, 415 V, 50 Hz front handle operated, including connecting and testing all as directed. MAKE: Indoasian/L & T/Havells
M & L for painting of Street light poles of any type (with hydrolic vehicle / ladder) including cross aRMs, channel, flat iron clamps etc 9 mtr long in two coats of aluminium paint and one coat of red oxide as primer including writing of pole nos (Yellow circle and Number in black) and providing 3 Nos of radium with width 50 mm size band / strap with Red, Yellow, Green colour 300 mm apart from plinth block around the pole etc complete as all as specified and directed in Engr-in- Charge. Note:- Hydrolic Vehicle / Ladder for painting is responsibility of contractor and rate of Hydrolic vehicle and ladder including in quoted rate.
M&L Heat shrinkable straight through joint, with including jointing materials and necessary earth work suitable for 1100 Volts , XLPE LT cable of size 16-25 sq.mm , 3.5/4 core, including fixing, jointing and testing complete all as specified and as directed.
M&L Heat shrinkable straight through joint, with including jointing materials and necessary earth work suitable for 1100 Volts , XLPE LT cable of size 35-95 sq.mm , 3.5/4 core, including fixing, jointing and testing complete all as specified and as directed.
M&L Heat shrinkable straight through joint, with including jointing materials and necessary earth work suitable for 1100 Volts , XLPE LT cable of size 120-240 sq.mm , 3.5/4 core, including fixing, jointing and testing complete all as specified and as directed.
M & L for aluminium cable lugs of size upto 50 sqmm flat head in Aluminium conductor/cable fixing with Nuts, bolts & washers to junction point as directed. (Note-To be measured only, fixed at places other than with heat shrink joints) Make - Dowells or equivalent.
M & L for aluminium cable lugs of size upto 70,95,120,150,185, 240,300 sqmm flat head in Aluminium conductor/cable fixing with Nuts, bolts & washers to junction point as directed. Make - Dowells or equivalent.
Supply and fix in repair of jumper with PVC shealeded aluminium single core power cable of size 70 Sqmm,11KV, with heat shrinkle sleeve at both ends confiRMing to IS 8098 including taking down unsv cable complete all as specified and directed.Make : Havells/Polycab/KEI
M & L for cement concrete type C2 (1:4:8)) using 20 mm graded stone aggregate in foundations, filling as mass concrete etc complete all as specified and directed by Engineer-in-Charge
Supply and fixing in replacement of HRC fuse of rating 2 to 63 Amps bolted/din type of breaking capacity 80 KA,500 v,AC ,50 HZ complete all as specified and directed . Make : Indoasian/Havells/Legrand
Supply and fixing in replacement of HRC fuse of rating 80 to 250 Amps bolted/din type of breaking capacity 80 KA,500 v,AC ,50 HZ complete all as specified and directed . Make : Indoasian/Havells/Legrand
Supply and spreading in electrical outdoor installation yard, stone aggregate of size 20 mm at 11KV substations / Near DP structures after through cleaning, anti grass treatment etc all as per pecified and as directed.
Supply and laying of bricks surrounding the stone aggregate at sub station including necessary excavation,returning and removing complete all as specified and directed.
S& F in replacement sign boards for MES installations of size 1200x 900mm made out with angle iron 40x40x 6mm as framing covered both side with 2 mm thick aluminium sheet rivetting on frame covered with retro reflective sheet & 100mm high letters as diredcted. Th sign board to be fixed on 2 No. 40x40x6mm angle iron legs embedded in PCC(1:4:8) using 40mm graded stone aggregate including necesary excavation complete at the installation etc complete all as specified and directed by Engr-in-charge Note : Matter on sign board supplied by Engr in Charge
Supply and fixing in replacement of powder coated pin type panel lock of size 25 mm /existing at site complete all as specifeid and directed
Taking out existing unserviceable UG Cable of any size by disconnecting all connections including excavation,returning & refilling complete all as specified and directed by engr in charge.
Dismantling of unserviceable insulator of any type complete from its position and removing all as specified and as directed
An amount of Rs 92,317.00 shall be deducted from BOQ on account of schedule of credit
KESARI AND SONS
R. T. Saluji
Maruti Abhiyantriki
Mahindra Electric Stores
Shining Star Electricals
KAMINS CARE
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .