HQ CWE (AF) Chakeri, Kanpur
PROVISION OF FIRE DETECTION AND ALARM SYSTEM AT VARIOUS LOCATIONS AT 7 AFH KANPUR
2026_MES_795833_1
CANO. CWE(AF)CHK/EM/T-04OF 2026-27 82484/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) E/M Chakeri
As per tender docus
7 documents required · 7 mandatory
₹1,000
GE (AF) E/M Chakeri
₹1.4 L
Yes
26 Oct 2026
26 Oct 2026
2 Dec 2026
26 Oct 2026
24 Nov 2026
17 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, commissioning and testing of analogue addressable type Fire alarm control panel along with network interface card and with Lead acid battery back up for 08 hours normal operation and 15 minutes alarm operation. (The control panel, battery charger, etc shall be UL/LPCB/Vds listed) complying with EN 54,IS2189(latest edition),NBC2016(part4) single loop panel with 99 detectors & 99 modules & upto 200 detectors and module complete all as specified and directed.
Notes:
(i) The housing of panel shall be minimum of 1.2 mm thick steel construction with minimum ingress protection to IP30 and dust and vermin proof type.
(ii) The logic circuitry shall be based on high noise immunity solid state hardware with logic cards of epoxy fiberglass construction.
(iii) It shall operate satisfactorily from 02 degree to 50 degree centigrade and at 92% humidity.
(iv) It shall monitor the status for fire, short-circuit fault, open-circuit fault, incorrect addressing, unauthorised device removal or exchange, alert or device maintenance condition and shall have LED indications.
(v) It shall be capable of providing alarm sounder facility that can be programmed, either by device, zonal or common system basis.
(vi) It shall have manual push button and shall be mounting type and shall be provided with aluminium chain and hammer attached. | 9 | Each | - | - |
| 2 | Supply, fixing and testing of Detectors complying with and type certified to EN-45, addressable type multisensor detector with heat and smoke combination with two alarm LEDs on each detector. The LEDs shall be controlled by the fire alarm control panel independently of the device. Detectors shall have five response modes which cover a range of sensitivities and response times complete all as specified and directed.
Note: Detectors are to be provided below and above false ceiling (if any) all as specified and directed at site. | 418 | Each | - | - |
| 3 | Supply, fixing and testing of addressable electronic sounder cum horn/ storbe rated at 82 dBA @ 3 M for audible annunciation and 75 cd flashing at 1 Hz for visual indication complete all as specified and directed. | 418 | Each | - | - |
| 4 | Supply, fixing and testing of analogue addressable fault isolator module for each circuit capable of monitoring shorted loop circuit fault, alarm circuit fault, device removal fault, earth fault, battery fault, mains failure and automatically restore communications when all conditions are corrected complete all as specified and directed. | 418 | Each | - | - |
| 5 | Supply, fixing and testing of analogue addressable control module for each circuit which shall be capable of providing DPDT contact rated at 24 C, DC, 2A complete all as specified and directed. | 45 | Each | - | - |
| 6 | Supply, fixing and testing of addressable single action manual call point having an integrally mounted addressable module that monitors and reports contact status complete all as specified and directed. | 21 | Each | - | - |
| 7 | Supply, laying and testing of 2 core 1.5 sqmm FRLS armoured copper cable on wall/ roof/ false ceiling/ floors with necessary clamps/ saddles complete all as specified and directed. | 3,210 | RM | - | - |
| 7.01 | General Notes for Ser Item No 01 to 07:
(i) Contractor shall submit a system schematic wiring diagram from fire alarm specialist supplier to dept prior to commencement of work.
(ii) The complete fire detection and alarm system shall be designed, tested and commissioned by the Fire system specialist and a certificate to this effect shall be submitted to the dept along with test certificates of the system.
(iii) The Contractor shall be responsible for providing the complete programming sheets to the fire alarm specialist supplier to enable the manufacturer to programme the control panel correctly.
(iv) Contractor shall test the fire alarm and detection system for audibility test of the alarm devices, manual call points, heat and smoke detectors for correct operation, mains failure test to verify correct operation of the backup battery system in presence of Engr-in-chg.
(v) Contractor shall provide and install a fire zone chart from fire alarm specialist supplier showing plans of the building with all fire alarm control and equipment with marked colour codes on a minimum sized A3, coloured frame and shall to be handed over on completion of the works for each location.
(vi) The Contractor shall include for the specialist fire alarm supplier to carry out first three quarterly (3 monthly) inspections and tests as per BS 5839 after the date of completion of the contract. Rate of the same is deemed to be included in quoted rates by contractor. | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.44 MB
TenderT04.pdf
Tender Documents • 1.20 MB
BOQ_892599.xls
BOQ • 14.20 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .