Loading…
New: tenders and results on WhatsApp
New: Find tenders, results and companies on WhatsApp, by text or voice note
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹51.6 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹51.8 L+₹20,620 (0.40%)Admitted-Finance FLAT NO 101 2ND FLOOR RAGHAVENDRA RESIDENCY PLOT NO 1 2 3 SURVEY NO 27 PICKET SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | L2 | Admitted-Finance | |
| 3 | L3₹55.7 L+₹4.1 L (8.04%)Admitted-Finance | L3 | Admitted-Finance | |
| 4 | L4₹56.1 L+₹4.5 L (8.78%)Admitted-Finance | L4 | Admitted-Finance | |
| 5 | L5₹56.5 L+₹4.9 L (9.42%)Admitted-Finance | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | L and S ENTERPRISES L2 | Mavee Syndicate L8 | SANJEEV CONSTRUCTIONS L6 | srisaienterprises L5 | vvcenterprises L1 | sree venkateswara enterprises L7 | M Shyam Sunder L4 | Srinivash Engineers L3 | GANGARAJU ENTERPRISES L9 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 600 Amps rating for phase and neutral 4 strips with colour | 1 | Each job | 1,89,000 ₹1,89,000 | 1,90,000 ₹1,90,000 | 1,80,000 ₹1,80,000 Lowest | 1,90,000 ₹1,90,000 | 2,10,000 ₹2,10,000 | 1,80,000 ₹1,80,000 Lowest | 1,98,000 ₹1,98,000 | 1,98,000 ₹1,98,000 | 2,10,000 ₹2,10,000 |
| 1.01coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- | ||||||||||||
| 1.02On load Change Over switch of capacity 400 Amps with 2 incoming and one outgoing -01 nos | ||||||||||||
| 1.03On load Change Over switch of capacity 200 Amps with 2 incoming and one outgoing -01 nos | ||||||||||||
| 1.04MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) | ||||||||||||
| 1.05MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Outgoing) | ||||||||||||
| 1.06MCCB 4pole, 250 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 03 No (Outgoing) | ||||||||||||
| 1.07MCCB 4pole, 100 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) | ||||||||||||
| 1.08Digital Ammeter 0 to 500Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set | ||||||||||||
| 1.09Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set | ||||||||||||
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
29 Sept 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (UTILITY) SECUNDERABAD
GE UTILITY SECUNDERABAD MUDFORT SECUNDERABAD-500003
REPAIR/ REPLACEMENT AND MAINTENANCE OF LT SWITCH GEARS LT PANELS APFC PANELS, LT CABLES AND CONNECTED ALLIED WORK AT CDM UNDER AGE NO I OF GE(U) SECUNDERABAD
2026_MES_788060_1
GE (U)/SEC/TOKEN/M55 OF 2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
SECUNDERABAD
As per Tender Documents
8 documents required · 8 mandatory
₹500
GE (UTILITY) SECUNDERABAD
₹98,000
Yes
11 Nov 2026
5 Sept 2026
6 Oct 2026
5 Sept 2026
29 Sept 2026
22 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 600 Amps rating for phase and neutral 4 strips with colour | 1 | Each job | 99 | ₹99 |
| 1.01 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- | - | - | - | - |
| 1.02 | On load Change Over switch of capacity 400 Amps with 2 incoming and one outgoing -01 nos | - | - | - | - |
| 1.03 | On load Change Over switch of capacity 200 Amps with 2 incoming and one outgoing -01 nos | - | - | - | - |
| 1.04 | MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) | - | - | - | - |
| 1.05 | MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Outgoing) | - | - | - | - |
| 1.06 | MCCB 4pole, 250 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 03 No (Outgoing) | - | - | - | - |
| 1.07 | MCCB 4pole, 100 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing) | - | - | - | - |
| 1.08 | Digital Ammeter 0 to 500Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set | - | - | - | - |
| 1.09 | Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set | - | - | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.16 MB
M55_8661_Tender.pdf
Tender Documents • 0.46 MB
BOQ_883258.xls
BOQ • 0.34 MB
Datecorr_M55.pdf
PDF • 0.12 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .