EE
Electrical Division No.II, HPPWD, U.S. Club, Shimla-01.
Providing addition and alteration of IHC lab room No. 408 department of pathology medical college at IGMC Shimla. SH Providing E.I. therein.
2026_PWD_135507_2
882 dated 02-06-2026
Open Tender
Electrical Works
90 days
Shimla
Please refer to tender documents. Eligibility criteria is mentioned at page No. 6-7, 9-10 of GCC. Documents mentioned in eligibility criteria must be uploaded to qualify the bid.
7 documents required · 7 mandatory
₹350
₹6,100
5 Jun 2026
5 Jun 2026
15 Jun 2026
5 Jun 2026
12 Jun 2026
5 Jun 2026
Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with 5 Amp Modular Plate And Switch and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required.
Group C
supplying and fixing of suitable size GI box with modular plate and cover in front on surface/recess including providing and fixing 25 amps modular socket outlet Sp Mcb “C” curve including connections painting ect. As required.
supplying and fixing of suitable size GI box with modular plate and cover in front on surface/recess including providing and fixing 6 pin 5/6 amp &15/16 amp moduler socket and 15/16 amps modular switch connection As required
supplying and fixing following modular base & cover plate on existing modular mattal boxes ect. As required
12 module
3 module
6module
8 module
supplying and fixing following modular switch & socketon the exising modular plate & switch box incuding connection but excluding modular plate etc. As required.
5/6 amps switch
3 pin 5/6 a socket outlet
15/16 amps switch
15/16 a socket outlet
Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-supplying and fixing of suitable size GI box with modular plate and cover in front on surface/recess including providing and fixing
Single pole. Cat-A.
Wiring for circuit/sub-main along with earth wire following size.HRFRLS/PVC insulated single core copper conductor cable surface/recessed steel conduit in medium class steel conduit as required
2x1.5 Sq. mm.+1x 1.5 sq mm earth wire
2x4.0 Sq. mm.+1x 4 sq mm earth wire
4x4 Sq. mm +2x 4 sq mm earth wire
Wiring for circuit/sub-main along with earth wire following size .HRFRLS/PVC insulated single core copper conductor cable surface/recessed medium class steel conduit as required.2X6 sq mm +1X6 Sq mm earth wire
Providing and installation of exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required:-
Exhaust Fan, Heavy Duty 300 mm sweep 1400/900 RPM
Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:-
Double door-12way
Providing and installation of stationary storage type Electric water heater (Geyser) of various sizes by means of Expansion bolt with nuts and washers. Including embedding of expansion bolts in the wall , providing and fixing of Non-return valve. Dead weight safety valve, 2 no. C.P connections rods 18" long making good the damage , electrical connections , safety valves connection , testing and commissioning etc. as required:-
15 Liter capacity water heater (Cat-A)
S/E of LED Batten with polycarboante body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:
Wattage of LED fittings - As per following parameter.
Total lumens of the fittings - as per wattage
Diffuser - Polycarbonate diffuser/PMMA
Operating voltage - 140 V to 270 V, AC supply or better.
Input frequency - 50 Hz + 1 Hz
Power factor - Minimum 0.90
Luminaire efficacy - ≥100 lm/w
Color rendering index - CRI shall be greater than 80
Working/ operating temperature - 00 to + 450c or better
Color temperature - 60000K + 10%
Electronic Driver
Drive current (LED) - As per OEM.
Operating voltage - 140 V to 270 V, AC supply or better.
Type of driver - Constant current output driver
THD - Less than 10%
Surge Protection - 2.5 KV minimum
Efficiency Driver - ≥85%
Protection - Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver - 2 years against manufacturing defect.
Fixture - Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model - Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED - 25000 burning hours at 70% lumen maintenance
Lumen output of the fitting
LED Batten Light ≥2000Lumens.
S/E of LED Panel with PDC body and polycarbonate /Acrylic diffuser to be mounted in recess The job includes carriage, erection, making connections testing and commissioning of the fittings.2 * 2 feet
Specification of LED fittings:
Wattage of LED fittings - As per following parameter.
Total lumens of the fittings - as per wattage
Diffuser - polycarbonate/acyrlic diffuser UGR <30
Operating voltage - 140 V to 270 V, AC supply or better.
Input frequency - 50 Hz + 1 Hz
Power factor - Minimum 0.90
Luminaire efficacy - ≥110 lm/w
Color rendering index - CRI shall be greater than 80
Working/ operating temperature - 00 to + 450c or better
Color temperature - 60000K + 10%
Electronic Driver
Drive current (LED) - As per OEM.
Operating voltage - 140 V to 270 V, AC supply or better.
Type of driver - Constant current output driver
THD - Less than 10%
Surge Protection - 2.5 KV minimum
Efficiency Driver - ≥85%
Protection - Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver - 2 years against manufacturing defect.
Fixture - Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model - Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED - 50000 burning hours at 70% lumen maintenance
Lumen output of the fitting
LED Panel Light 2'x2' ≥3300Lumens.
S/E of LED Downlighter round type surface with CRCA/PDC body and diffuser The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
Wattage of LED fittings - As per following parameter.
Total lumens of the fittings - as per wattage
Diffuser - Polycarbonate diffuser/PMMA
Operating voltage - 140 V to 270 V, AC supply or better.
Input frequency - 50 Hz + 1 Hz
Power factor - Minimum 0.90
Luminaire efficacy - ≥100 lm/w
Color rendering index - CRI shall be greater than 80
Working/ operating temperature - 00 to + 450c or better
Color temperature - 60000K + 10%
Electronic Driver
Drive current (LED) - As per OEM.
Operating voltage - 140 V to 270 V, AC supply or better.
Type of driver - Constant current output driver
THD - Less than 10%
Surge Protection - 2.5 KV minimum
Efficiency Driver - ≥85%
Protection - Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver - 2 years against manufacturing defect.
Fixture - Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model - Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED - 50000 burning hours at 70% lumen maintenance
Lumen output of the fitting
LED Down Light ≥2400Lumens.
providing & laying of one no. aluminium conductor PVC insulated ans PVC sheathed armoured XLPE power cable 1.1 KV grade of following size on wall surface as Required
armoured Cable 16sq mm (2 Core)
S/E of MCCB 4 Pole 415 Volt. with Adjustable thermal and magnetic for overload and short circuit protection breaking Capacity (Ics=100% Icu with positive isolation) with/ without Spreader/ Rotary Handle.
MCCB 40- 100 Amp. 36 ka 4 Pole Release without rotary handle
MCCB 160 Amp. 36 ka 4 Pole Release without rotary handle
Providing and installation of 1.5TR hot and cold Split Type AC 4 star with R32 Refrigerent, Rated Power supply single Phase 50 Hz 220-240V, Rate Capacity (Heating/ Cooling) 5.0/5.5 KW, Cooling Capacity (Min-Max) 1.5 ~ 5.75 KW, Heating Capacity (Min~Max) 1.3- 6.6 KW, Rates ISEER 5.20, Rated Annual Power Consumption 743.95 KWh,Operating Current (Cooling/ Heating) 5.63/5.77 A, Patented Swing Compressor, Ambient Temperature Range Cooling (Min-Max) 10° C - 54 °C, Heating (Min-Max) -15°C~ 24 °C making connections , testing etc.complete in all Respect with best satisfaction of engineer -in- Charge. Make:-DAIKIN /o -general / Mitsubishi
1.5 TR Split AC Hot and Cold 4 Star
Providing and fixing of copper tube for refrigrent size (6.4 mm -12.7mm) for 2.0 T.R. Split AC unit as required complete in all respects and as per direction and satisfaction of Engineer in charge.
Providing and fixing of Nitrile Tubular Insulationac indoor to outdoor for COPPER PIPING as required complete in all respects and as per direction and satisfaction of Engineer in charge.
Providing and laying of communication wire 2.5 Sq.mm. (4 core) as required complete in all respects and as per direction and satisfaction of Engineer in charge.
Supplying and fixing of 25mm dia of PVC drain pipe along with the accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required complete in all respects and as per direction and satisfaction of Engineer in charge.
Providing and fixing of MS Galvanised cable tray of size 100mm x 50mm as required complete in all respects and as per direction and satisfaction of Engineer in charge.
Providing and fixing of MS Pre-fabrication condensing unit stands as required complete in all respects and as per direction and satisfaction of Engineer in charge.
Providing and fixing Galvanised sheet Monkey Protection for Out door Unit as required complete in all respects and as per direction and satisfaction of Engineer in charge.