| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹2.2 CrAccepted-AOC OPP DAGA HOSPITAL GANDHIBAGH NAGPUR 440002 INDIA | NAGPUR | MAHARASHTRA | 440002 | ₹2.2 Cr | L-1 | Accepted-AOC Lowest Bidder |
| 2 | L-2₹2.2 Cr+₹2 L (0.92%)Rejected-Finance | ₹2.2 Cr+₹2 L (0.92%) | L-2 | Rejected-Finance L-2 |
| 3 | L-3₹2.3 Cr+₹16 L (7.37%)Rejected-Finance 146 CP COLONY 7 NO CHOURAHA KALPANA NAGAR MORAR GWALIOR 474006 | GWALIOR | MADHYA PRADESH | 474006 | ₹2.3 Cr+₹16 L (7.37%) | L-3 | Rejected-Finance L-3 |
| 4 | L-4₹2.4 Cr+₹22 L (10.1%)Rejected-Finance 241 SWAMI NARAYAN NAGAR 1 OPP SWAMIVIVEKANA ASHRAM BEHIND HALAR HOUSE JAMNAGAR JAMNAGAR GUJARAT 361001 | JAMNAGAR | GUJARAT | 361001 | ₹2.4 Cr+₹22 L (10.1%) | L-4 | Rejected-Finance L-4 |
| 5 | L-5₹2.8 Cr+₹67 L (30.8%)Rejected-Finance 1 IIND PADMA TOWER RAJENDRA PLACE WEST DELHI CENTRAL DELHI DELHI 110008 | WEST DELHI | DELHI | 110008 | ₹2.8 Cr+₹67 L (30.8%) | L-5 | Rejected-Finance L-5 |
Tender Value
₹4.0 Cr
EMD Value
₹7.9 L
Closing Date
6 Oct 2020, 6:00 pmClosed
AGM (E-E), AAI
Office of Asstt General Manager Electrical Jabalpur Airport Project
Up gradation of Jabalpur Airport to make it Suitable for Operation of AB 320 Type Aircraft Apron Isolation Bay Flood Lighting Perimeter Lighting Ring Main System for Power Supply and Associated works
2020_AAI_57833_1
AAI/JGM/E-E/JBP/P/05.3/2019-20
Open Tender
Electrical Works
Tender cum Auction
365 days
Jabalpur Airport Project
Please refer the NIT and Tender document
18 documents required · 18 mandatory
₹1,120
Airport Authority of India
₹7.9 L
30 Dec 2020
18 Sept 2020
15 Oct 2020
19 Sept 2020
6 Oct 2020
19 Sept 2020
19 Sept 2020 - 27 Sept 2020
Amount
Supply, installation, testing,& commissioning of 20 M high mast in two sections suitable for wind speed as per IS: 875 part-III,with head frame,winch mounting bracket, luminaries carriage suitable to install minimum 11 nos luminaries in symmetrical arrangement, top pully arrangement complete with dip galvanised finished,civil RCC foundation with excavation in soil, foundation bolts,anchor plates nuts,washers, anchor plate complete in all respects I/C electrically operated raising lowering system double drum winch, 6mm diameter SS wire rope, ,multi core copper conductor cable (Trailing cable(EPR)) of suitable current carrying capacity between top carriage and the base terminal (inside mast),including provision of outdoor type double doors feeder pillar made out of 14 SWG,CRCA sheet with powder coated paint comprising of rating one number incomer 63 A TP MCCB of 25KA and two numbers out going circuits with Suitable TP MCBs of 10KA innterconnecting copper wiring,Auto/manual Switch,0-24 hr .timer & suitable contactor including suitable PCC foundation etc. as required suitable for operation on 415 V, 3 phase, 50HZ, AC power supply. connector, integral power tool motor, manual handle, junction box, lightening finial,including Two number LED Aviation Obstruction Lights shall be on the existing lantern carriage including wiring of all luminaires with all wiring material like PVC insulated PVC sheathed flexible cable of suitable copper conductor cores of 1.5 sqmm junction box of lantern carriege to individual light fitting, lugs,mounting accessories and all labour etc. including 1.1 KV power cables from feeder pillars to individual mast distribution box all complete as required as per technical specification attached.
Supply ,assembly and erection of 2.6 Mtr height (height above ground is 2.75 mtr. as per the drawing attached), G.I Octagonal pole suitable to withstand wind speed as per IS -875 made out of HT steel confirming to grade S355J0 or equivalent with single arm bracket made out of suitable dia GI pipe EN 8 grade foundation bolt,base plate with Fe 410 confirming to IS 226 / IS 2062 etc. with complete accessories.The poles shall be hot dip galvanised as per IS 2629 /IS 2633 /IS 4759 standards with average coating thickness of 70 micron.The poles shall be provided with a vandal resistant and weather proof/water proof flush door of 500 mm length(Approx.) at a height of 500 mm from base plate with proper strenghtening to cut out of the door opening. An outdoor IP66 rated junction box/ looping box with heavy duty single phase and neutral connector with 6 amp. DP MCB shall be provided inside the cutout.Poles shall be provided with two earth studs at the bottom Poles shall be fixed to foudation with a set of four foundation bolts etc as required as per technical specification attached.
Erection of Octagonal pole provided in item no. 2 (SH-II Sr. no 1) above in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation refilling providing 2 no X 50 mm dia DWC Pipes for cable entery etc. as required
Above 1 metre and upto 6.5 metre
Supply,installation,testing commissioning of high pressure die cast aluminium LED Flood light luminaire with toughened glass/Borosilicate glass lense with minimum system lumen output of 38500 lumens & minimum system efficiency of 110lm/w and as per technical specification attached etc.complete as required..
Supply,installation,testing commissioning of high pressure die cast aluminium LED Flood light luminaire with toughened/Borosilicate glass lense with minimum system lumen output of 33000 lumens & minimum system efficcancy of 110lm/w and as per technical specification attached etc. complete as required..
Supply,installation,testing commissioning of high pressure die cast aluminium LED street light luminaire with toughened glass with minimum system lumen output of 1500 lumens & minimum system efficcancy of 110lm/w and as per technical specification attached etc. as complete required..
Supply of following size of 1.1 kv grade FR aluminium conductor XLPE insulated and PVC sheathed armoured cable as per IS: 7098:1988 (Part-I) with upto date amendments.
3½ core X 400 Sq.mm. A2XFY
3½ core X 120 Sq.mm. A2XFY
3½ core X 25 Sq.mm. A2XFY
Supply of following size of 1.1 kv COPPER grade Armoured PVC Control Cable IS:1554(PT-I)-1988
6 CX2.5 Sqmm
Main distribution Panel(F/P-1)(For Panel Detail Ref Item NO 9) Consisting of following
Incomers:
i) 2 No. 600 Amps. 4P MCCB 50KA, Icu=Ics with Microprocessor based release having O/L ,S/C earth fault protection & necessary equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED screen as per specs. with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA Class1.0 metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 600 Amps. 4P MCCB 50 KA, Icu=Ics with Microprocessor based release having O/L ,S/C protection.
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 600 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to withstand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C,E/F followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C,E/F protection with On, off trip indications of following capacity and rating,50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class ‐ 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 2 Nos. ‐ Thermal Magnetic 250 Amp. 4P MCCB (LLZ) F/P-5
ii)2 Nos. ‐ Thermal Magnetic 250 Amp. 4P MCCB,(DVOR & GP) F/P-3
(iii) 2no.- Thermal magnetuc 125 Amp. 4P MCCB,(Perimeter Light F/P-4)
(iv) 2no.- Thermal magnetuc 125 Amp. 4P MCCB,(Apron high mast F/P-2)
(v) 4no.- Thermal magnetuc 100 Amp. 4P MCCB,(Spare)
Necessary interlocking shall be successfully operational in all possible combinations.
High mast feedar pillar panel -2 (For Panel Detail Ref Item NO 9) Consisting of following
Incomers:
i) 2 No. 125 Amps. 4P MCCB 50KA, Icu=Ics with thermo magnetic based release having O/L ,S/C earth fault protection & necessary equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED screen as per specs. with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA Class1.0 metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 125 Amps. 4P MCCB 50 KA, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 200 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to withstand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C,E/F followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C,E/F protection with On, off trip indications of following capacity and rating, 50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class ‐ 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 4 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCCB, ( High mast feedar piller)
ii)2 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCB, ( Spares)
Necessary interlocking shall be successfully operational in all possible combinations.
DVOR &GP feedar Panel-3(For Panel Detail Ref Item NO 9) Consisting of following
Incomers:
i) 2 No. 250 Amps. 4P MCCB 50 KA, Icu=Ics with thermo magnetic based release having O/L ,S/C earth fault protection & necessary equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED screen as per specs. with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA Class1.0 metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250 Amps. 4P MCCB 35 KA, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 300 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to withstand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C,E/F followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C,E/F protection with On, off trip indications of following capacity and rating, 50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class ‐ 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 2 Nos. ‐ Thermal Magnetic 125 Amp. 4P MCCB, ( GP)
i) 2 Nos. ‐ Thermal Magnetic 125 Amp. 4P MCCB, ( DVOR)
ii)4 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCCB, ( Spares)
iii) 2 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCCB with 20 Amp. 4P contactor ( perimeter Light)
Necessary interlocking shall be successfully operational in all possible combinations.
perimeter light feedar pillar panel -4 (For Panel Detail Ref Item NO 9) Consisting of following
Incomers:
i) 2 No. 125 Amps. 4P MCCB 50KA, Icu=Ics with thermo magnetic based release having O/L ,S/C earth fault protection & necessary equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED screen as per specs. with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA Class1.0 metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 125 Amps. 4P MCCB 50 KA, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 200 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to withstand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C,E/F followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C,E/F protection with On, off trip indications of following capacity and rating, 50KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class ‐ 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 2 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCCB with 20 Amp. 4P contactor ( perimeter Light)
ii)2 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCB, ( Spares)
Necessary interlocking shall be successfully operational in all possible combinations.
LLZ Panel: 5 feedar Panel(For Panel Detail Ref Item NO 9) Consisting of following
Incomers:
i) 2 No. 250 Amps. 4P MCCB 50KA, Icu=Ics with thermo magnetic based release having O/L ,S/C earth fault protection & necessary equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED screen as per specs. with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA Class1.0 metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250 Amps. 4P MCCB 50 KA, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 300 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to withstand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C,E/F followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C,E/F protection with On, off trip indications of following capacity and rating, 50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class ‐ 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 2 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCB with 20 Amp. 4P contactor ( perimeter Light)
ii) 2 Nos. ‐ Thermal Magnetic 125 Amp. 4P MCCB (Isolation)
iii) 2 Nos. ‐ Thermal Magnetic 125 Amp. 4P MCCB, (ATS of LLZ)
iv)4 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCCB, ( Spares)
Necessary interlocking shall be successfully operational in all possible combinations.
Isolation bay feedar pillar panel -6 (For Panel Detail Ref Item NO 9) Consisting of following
Incomers:
i) 2 No. 125 Amps. 4P MCCB 50KA, Icu=Ics with thermo magnetic based release having O/L ,S/C earth fault protection & necessary equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED screen as per specs. with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA Class1.0 metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 125 Amps. 4P MCCB 35 KA, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 300 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to withstand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C,E/F followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C,E/F protection with On, off trip indications of following capacity and rating, 50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class ‐ 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
2 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCB, ( Hm-1 &Hm-2)
ii) 2 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCCB with 20 Amp. 4P contactor ( perimeter Light)
iii)2 Nos. ‐ Thermal Magnetic 63 Amp. 4P MCB, ( Spares)
Necessary interlocking shall be successfully operational in all possible combinations.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/HDPE DWC pipe as required.
Above 185 sq. mm and upto 400 sq. mm
Above 95 sq. mm and upto185 sq. mm
Upto 35 Sqmm
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required.
200 mm dia (OD-200 mm & ID-175 mm nominal)
120 mm dia (OD-120 mm & ID-103 mm nominal)
63 mm dia (OD-63 mm & ID-51 mm nominal)
Supplying and making indoor end termination with brass double compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ core X 400 Sq.mm.(82mm)
3½ X 120 sq. mm (45mm)
6C X 2.5 sqmm(19mm)
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal/ coke and salt ) as required
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Constructing brick masonry road gully chamber 75x75x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast cement mortar 1:4 (1 cement : 4 coarse sand) pre-cast R.C.C. horizontal grating with frame complete as per standard design : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Bidder Name
Amount in Words
Manish Electricals
Surya Roshni Limited
DOSHI ELECTRIC ENGG. CO.
Choubay And Co.(Agencies) Pvt.Ltd.
M R ELECTRICALS
Naagar Infrastructure Pvt Ltd
Ascent Electrification Engineers
TRANSRAIL LIGHTING LIMITED
PRASHANT ELECTRICALS
GAYATRI ELECTRICAL
Shakti Infrastructure
Surya Roshni Limited
Ascent Electrification Engineers
GAYATRI ELECTRICAL
M R ELECTRICALS
Manish Electricals
Choubay And Co.(Agencies) Pvt.Ltd.
Naagar Infrastructure Pvt Ltd
PRASHANT ELECTRICALS
TRANSRAIL LIGHTING LIMITED
DOSHI ELECTRIC ENGG. CO.
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .