Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.9 LAccepted-AOC COLABA MUMBAI | ₹40.9 L | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹43.9 L+₹3.0 L (7.25%)Rejected-Finance 340 11 M S NATIONAL ENGINEERING CORP 340 11 SATTI STREET ROORKEE ROORKEE HARIDWAR UTTARAKHAND 247667 | HARIDWAR | UTTARAKHAND | 247667 | ₹43.9 L+₹3.0 L (7.25%) | L2 | Rejected-Finance Higher bidder |
| 3 | L3₹53.0 L+₹12.1 L (29.6%)Rejected-Finance | ₹53.0 L+₹12.1 L (29.6%) | L3 | Rejected-Finance Higher bidder |
| 4 | Rejected-Technical | - | - | Rejected-Technical Eligibility Criteria Not Fulfilled |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
18 Sept 2021, 6:00 pmClosed
SH A K SINGH SE CWE NAVY VASCO
CWE NAVY VASCO VASCO DA GAMA GOA 403802
REPLACEMENT OF BER TRANSFORMER AND NEUTRAL GROUNDINGS RESISTORS INSTALLED AT VARIOUS ELECTRICAL SUB STATION UNDER AGE EM II OF GE NW VASCO
2021_MES_465558_1
85467/E8
Open Tender
Civil Works
Item Rate
180 days
CWE NAVY VASCO
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
Yes
GE NW VASCO
₹78,000
Yes
18 Dec 2021
5 Aug 2021
21 Sept 2021
5 Aug 2021
18 Sept 2021
30 Aug 2021
Amount
Supply, installation, testing and commissioning of outdoor type oil filled transformer of capacity 100 KVA as per IS-1180 Part-1: 2014 with off load tap changer on primary side to vary secondary voltage with in limit (+) 5% to (-) 7.5% in step of 2.5%. The transformer shall be provided with cable termination box to terminate Outdoor type termination of suitable size on HT side 11 KV& LT side 1100volt. Transformer step-down ratio of 11000volt /433volt, 3 phase 4 wire, impedance as per IS. Oil type ONAN cooled suitable for outdoor installations and double wound core type with cold rolled grain oriented silicon shell insulated laminations and clamped to minimize vibrations and noise. The winding I be of copper and shall be designed for full load current and to withstand the thermal and electromagnetic stresses arising due to the to the through fault current vector group shall be DYN 11 including supply of all standard fitting/fixture and comprising of the followings -
(a) HT cable termination box (b) LT cable termination box (c)Rating & Diagram Plate. (d) Earthing Terminals. (e) Lifting Lugs. (f) Oil Level Indicator with minimum level marking (g) Thermometer Pockets. (h) Conventional Conservator with oil filling hole with cap and drain plug. (i) Air Release Plug. (j) Silica gel breather. (k) Off Circuit Tap Changer (l) Bi-directional Rollers. (m) Jacking Pads. (n) Radiators. (Epoxy Painted) Note : (i) Transformer shall be fixed over the platform of size not less than 3 m (Length) X 3 m (Width) X1.5 m (height) above ground level made by PCC 1:3:6, as mass filling and PCC 1:2:4 at top with 30 cm thickness. Civil work required for installation of transformer deemed to be included into quoted rates.
All as per Item No. 1 here in before but of capacity 250 KVA transformer complete all as specified and as directed
All as per Item No.1 here in before but of capacity 315 KVA transformer complete all as specified and as directed
S&F Cable jointing kit suitable for 11KV (Earthed) grade cable for outdoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and as directed
S&F Cable jointing kit suitable for 11 KV (Earthed) grade cable for outdoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as specified and as directed
S&F Cable jointing kit for 1.1KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and as directed
S&F Cable jointing kit for 1.1KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as specified and as directed
M&L for XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts earthed,grade cross sectional area 95 sqmm 3 core complete all as specified and as directed
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) stranded aluminium conductor, 1100 volts grade, of size 3.5 core of 95 sq mm complete all as specified and as directed
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) stranded aluminium conductor, 1100 volts grade, of size 3.5 core of 240 sq mm complete all as specified and as directed
M & L for earthing complete with Gl earth plate, electrode,600 x 600 x 6.0 mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) filled with common salt and charcoal and connected to Gl earth strip 32x 6 mm thick dia by means of Gl nuts, bolts, & washers as shown in electrical plate No. 3 of SSR Part-1 and connected to earthing test point all as specified and including necessary PCC earth pit chamber of 1:3:6 and chamber cover of 50mm thick PCC 1:2:4 with 6mm dia mild steel reinforcement of 10 cm c/c spacing both ways in lieu of Cl cover, watering arrangement shall be made with Gl pipe medium grade of 20mm dia including funnel and protection to earth lead shall be provided with Gl pipe. light grade 40 mm dia unto 7.5 from the earth plate electrode & refilling of soil etc including necessary excavation & earth work in any strata and PCC chamber all as specified and directed by Engineer-in-Charge including demolish existing earth pit taking out old materials. Note: GI earth strip 32 x 6 mm upto 7.5 RM is included in the unit rate quoted
S&F Gl pipe light grade of sizes 100 mm dia for cable protection in trenches/ at PCC poles for loop-in/ loop-out of cable and cable entry at panel/equipment end complete all as specified and as directed
NATIONAL ENGINEERING CORPORATION
MARINE ELECTRICAL AGENCIES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .