Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.9 LAccepted-AOC H NO 190 S 4 CHODANKAR RESIDENCY NEAR GANPATI TEMPLE CENTRAL HORTA AQUEM BAIXO NAVELIM SALCETE GOA 403707 | SOUTH GOA | GOA | 403707 | ₹7.9 L Quoted ₹8.2 L | L1 | Accepted-AOC Found reasonable for acceptance |
| 2 | L2₹9.5 L+₹1.3 L (16.2%)Rejected-Finance 364 4 FIRDAUS SHABANA MARKET NEW SABZI MANDI JK COLONY ROAD KANPUR 07 | KANPUR NAGAR | UTTAR PRADESH | 208001 | ₹9.5 L+₹1.3 L (16.2%) | L2 | Rejected-Finance L1 being accepted |
| 3 | L3₹10.7 L+₹2.5 L (30.9%)Rejected-Finance SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | ₹10.7 L+₹2.5 L (30.9%) | L3 | Rejected-Finance L1 being accepted |
| 4 | L4₹13.4 L+₹5.2 L (64.1%)Rejected-Finance | ₹13.4 L+₹5.2 L (64.1%) | L4 | Rejected-Finance L1 being accepted |
Tender Value
₹12 L
EMD Value
₹24,000
Closing Date
13 Mar 2023, 6:00 pmClosed
GE (P) Navy Mandovi
GE (P) Navy Mandovi Military Engineer Services INS Mandovi
As per tender documents
2023_MES_580568_1
8479/E8 GE (P) NAVY MANDOVI
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
Mandovi
As per tender documents
7 documents required · 7 mandatory
₹500
GE (P) Navy Mandovi
₹24,000
Yes
23 Mar 2023
13 Feb 2023
15 Mar 2023
13 Feb 2023
13 Mar 2023
27 Feb 2023
13 Feb 2023 - 25 Feb 2023
Amount
M & L for taking out LT UG cable of following sizes complete all as specified and directed.
120 sqmm 3.5 core
95 sqmm 3.5 core
70 sqmm 3.5 core
50 sqmm 3.5 core
35 sqmm 3.5 core
25 sqmm 4 core
16 sqmm 4 core
M & L for providing LT UG XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, heavy duty electric power cables of following sizes, with multistranded aluminium conductor, 1100 volts grade, confirming to IS 7098 Part-1 1988, including centre glands, lugs, jointing materials etc, laid in trenches and connecting with LT panel / MCCB / busbar box etc alongwith LT cable route indicator for every 100 RM length of cable, testing and commissioning complete all as specified and directed. Note: Excavation, PCC, covers and cushions shall be measured and paid separately under relevant items of this schedule
3.5 core 120 sqmm
3.5 core 95 sqmm
3.5 core 70 sqmm
3.5 core 50 sqmm
3.5 core 35 sqmm
4 core 25 sqmm
4 core 16 sqmm
S & F 2.5 sqmm 3 core copper cable (for phase, neutral & earthing) run through and including 20 mm dia PVC conduit properly clamped to pole from DB to fitting through bracket complete all as specified and directed. Note: 01 run of 3 core copper cable and 01 run of PVC conduit shall be measured as unit length
Excavating in trenches, not exceeding 1.5 m wide and n exc 1.5 m in depth and getting out in soft disintegrated rock for laying and taking down UG cable complete all as specified and directed.
M & L for providing cement concrete 1:3:6, type C2, using 40 mm graded stone aggregate as in foundations, filling and mass concrete complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick using excavated soft disintegrated rock complete all as specified and directed.
Removing excavated material to a distance n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
Supply and laying fine dry river sand to entire width of trench as cable cushion in trenches complete all as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover for cable protection, class LV, type I, flat, size 250mm x 150mm x 40mm, ISI marked complete all as specified and directed.
Supply and lay GI tubing of following sizes, light grade, ISI marked, galvanised, laid in trenches for cable protection including fittings such as bends, elbows, reducers etc including taking down existing GI pipe complete all as specified and directed.
80mm dia bore
50mm dia bore
40mm dia bore
S & F spreader terminals suitable for MCCB of following capacities complete all as specified and directed.
For MCCB upto 100 Amp
For MCCB above 100 upto 250 Amp
For MCCB above 250 upto 400 Amp
S & F fuse wire of 20 amp capacity complete all as specified and directed.
Supply only binding wire 0.9mm dia, aluminium complete all as specified and directed.
Supply and fix in repairs cable lugs suitable for cables of following sizes complete all as specified and directed.
16 sqmm 4 core
35 sqmm 3.5 core
50 sqmm 3.5 core
70 sqmm 3.5 core
95 sqmm 3.5 core
120 sqmm 3.5 core
185 sqmm 3.5 Core
240 sqmm 3.5 Core
M & L for preparation of old cement coated surfaces of RCC LT pole above ground level including coping and applying two coats of cement based paint over a coat of cement primer including writing pole numbers/ letters in 12 cm height, with white paint on black background and applying blue tinted paint on bottom of pole as per existing, complete all as specified and directed.
S & F straight through jointing kit suitable for cables of following sizes complete all as specified and directed.
LT cable 185 sqmm 3.5 core Make: Raychem Cat part no EPKJ0144 or any other equivalent make as specified in List of Manufacturers
LT cable 95 sqmm 3.5core Make: Raychem Cat part no EPKJ0137 or any other equivalent make as specified in List of Manufacturers
LT cable 70 sqmm 3.5 core Make: Raychem Cat part no EPKJ0137 or any other equivalent make as specified in List of Manufacturers
S & F in repairs TPN 4-pole busbar box, outdoor type, made out of 3.15 mm thick MS sheet of suitable size with 4 Nos aluminum bus bars of 200 Amp capacity for connecting heavy duty cables upto 3.5 core 150 sqmm as incoming and two outgoing cables along with 125 amps MCCB including lugs, glands, nuts, bolts & washers of suitable sizes, proper insulation, fixing 50 cm above ground level on pole / angle iron frame of suitable size, necessary excavation and PCC work complete all as specified and directed.
S & F in repairs danger notice plate 20 x 15 cm size, made of 1.6 mm thick mild steel sheet, vitreous enamelled white; with letters, figures and conventional skull and bones in single red colour and fixed with M.S. clamps, bolts and nuts of suitable size, for LT pole/ equipments/ lines complete all as specified and directed.
M & L for earthing complete with steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground, vertically (earth pit not less than 2.25 mtr below ground level) with top edge of plate not less than 1.5 mtr below ground level connected to GI earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers etc including 15mm dia protection pipe upto 7.5m length, connecting the earth lead to earth connection in the main distribution box with lugs and GI nuts, bolts etc as shown on electrical plate No 3 of SSR part 1 including neccessary excavation in disintergrated hard rock, filling earth upto 15 mm thick and providing earth pit, 20mm dia GI funnel, PCC earth chamber, 100mm thick precast RCC cover with suitable precast RCC frame and earth test point and testing including taking out old earthing complete all as specified and directed. Note:- On testing after completion if the desired earth resistance is not obtained, earthing shall be redone at no extra cost.
kay pee construction
Shree Ayyappa Engineering
S and G Constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .