Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.7 LAccepted-AOC 143 INDUSTRIAL AREA PHASE 2 PANCHKULA HARYANA | PANCHKULA | PANCHKULA | HARYANA | L1 | Accepted-AOC Accept | |
| 2 | L2₹1.9 L+₹21,870 (12.8%)Rejected-AOC | L2 | Rejected-AOC Reject | |
| 3 | L3₹2.0 L+₹27,820 (16.3%)Rejected-AOC GAUSHALA MARKET TEHSIL NARNAUL NARNAUL 123001 | NARNAUL | NARNAUL | HARYANA | 123001 | L3 | Rejected-AOC Reject |
Tender Value
₹2.0 L
EMD Value
₹3,960
Closing Date
28 Oct 2024, 1:00 pmClosed
XEN M/GARH W.S MECH. DIVISION, NARNAUL
Executive Engineer M/Garh W/S Mech. Divn. Narnaul.
Special Repair and servicing of VCB Panels Starters Panel at Pump House MB-1 to MB-3 of Madhogarh Branch under MGarh WS Mech. Division, Narnaul.
2024_HRY_404461_10
4383-96/9-A Dated 11/10/2024
Open Tender
Pumps/Motors
Works
45 days
XEN M/GARH W.S MECH. DIVISION, NARNAUL
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
₹3,960
Yes
20 Jan 2025
16 Oct 2024
28 Oct 2024
16 Oct 2024
28 Oct 2024
16 Oct 2024
Amount
Servicing & Repair of existing LT Panels/ Starter Panel of Various Makes and of different capacity in amps. with all accessories installed at various Pump Houses under W.S Mech. Division, Narnaul which includes following Activities : - A. Servicing and Repair of ACB/MCCB/Contactors 1. Removal of Dust and Foreign Matter, carbon deposit from Panel Box with a vacuum cleaner/Air Blower and Wiping with a clean, dry cloth and cleaning agent. 2. Applying layer of Grease and Oiling of all Mechanical Parts and main contacts of for Smooth operation. 3. Checking of All the Connections and tightening them as per standard practice. B. Replacement of defective control wiring with suitable size PVC copper wire (if any) C. Replacement of defective Indicating Lamps and Push Buttons. D. Replacement of Locking System of Panel. E. Measurement of Insulation Resistance b/w Main conductor (R, Y, B) and Ground with 1000V Megger. Note:- (i) Only fixing in replacement of all the defectiveparts such as metering devices, relays, control devices, indicators,charging motors, mechanical gears/handle,rotary switches,bushes,control fuses,contactors,MCB's, etc or all any leftover items as shown in separate schedule of this tender on cost basis and separate payment shall be made on approved rates after approval by competent authority with maintaining proper record in document. (ii) The new parts shall be measured and paid separately under appropriate item schedule part-II as supply only mentioned herein after. (iii) Small items such as nut, bolts, screws & washers required at site are deemed to be included in the quoted rates by the contractor.
Re-Erection of existing Cable by providing suitable size Aluminium Thimbles, Compression Gland for 3.3KV/1.1KV Cables at Motor end as per the Requirement of Site and fixing of cable box plates with suitable nuts and bolts.
Providing & fixing in replacement of Motor protection relay (MPR 200) of any type & any capacity as per existing LT Panel of various size and make
Providing of Suitable Bus Bar at LT Motor End of diff. capacities made of Suitable size Aluminium/Copper Strip and on Insulated Base including terminal bolts of suitable size.
Supply only indicator lamps LED type as per existing colour code RYB complete for VCB 3.3 KV as per existing complete of approved make..
Credit of old IRON scrap (Actual weight of old scrap will be measured by the committee) Old scrap/parts shall be property of firm.
Credit of old Copper scrap (Actual weight of old scrap will be measured by the committee) Old scrap/parts shall be property of firm.
SAINI ELECTRIC STORE (BID ID -1153040)
Shree Shyam Associates (BID ID -1156028)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .