Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹77.0 LAccepted-AOC A 303 VEENA CGHS LTD PLOT NO 5D SECTOR 22 DWARKA NEW DELHI 110077 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110077 | L1 | Accepted-AOC AOC | |
| 2 | L2₹81.7 L+₹4.7 L (6.11%)Rejected-AOC 67 KAILASH VIHAR TIWARIPUR BAGIA JAJMAU KANPUR 208010 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208010 | L2 | Rejected-AOC L2 | |
| 3 | L3₹86.7 L+₹9.7 L (12.6%)Rejected-AOC | L3 | Rejected-AOC L3 |
Tender Value
Refer Docs
EMD Value
₹1.5 L
Closing Date
29 Nov 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE(AF) Tughlakabad
HQ CWE(AF) Tughlakabad
PROVN OF 11 KV ADDITIONAL INDEPENDENT FEEDER AT AF STN GURGAON UNDER GE(P) AF GURGAON
2021_MES_483881_2
CA NO. CWE/TKD/GUR/TOKEN-45/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE(P) AF GURGAON
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
Yes
GE(P) AF GURGAON
₹1.5 L
Yes
18 Dec 2021
10 Nov 2021
1 Dec 2021
10 Nov 2021
29 Nov 2021
17 Nov 2021
60 days
Amount
Supply, installation, testing and commissioning the following indoor type, 11 KV, 3 phase, 50 cycle (50 Hz) 630 Amps capacity triple pole totally enclosed, patern , vermin proof vertical draw out type with grounded neutral system vaccum circuit breaker, floor mounted with common copper tinned bus bar complete all as specified and directed including the following details :- (a) One set of 3 phase 1250 Amps air insulated tinned copper bus bar with insulated colour coating. (b) One set of side frame for housing of circuit breaker carriage. (c) One 630 Amps tripple pole minimum 350 MVA (3 sec) rupturing capacity with latest issue of IEC recommandation: IEC 62271-100, vaccum restrike free, stored energy oprated type,mechanical anti pumping should be built in future of circuit breaker. VCB with automatic drop out and motor operated spring closed mechanism complete with auxiliary switches trunk type meachanically ON/OFF indicator. (d) The breaker is to be mounted on trunk carriage complete with self contained motor charged spring closing mechanism to be operated on DC motor 24V/30V operated fully interlocked raising and lowering mechanism. (e) Cable box for reception for suitable size XLPE 3 core UG cable 11000 volt pressure. (f) CT details:- (i) Single phase, 2 core CT with 100-50/5-5-03 Nos Core I Class-1, 15 VA Core II Class 5P10, 15 VA (g) Digital intelligent panel meter indicaating line current , line voltage, power factor, KVAR, KVA, frequency, voltage and current harmonics etc with accuracy 1.0 for active energy. (h) Micro processor based numerical relay for over current and earth fault protection, self powered type with inbuilt software, USB port, SCADA compatible for remote communications with provision of recording of at least 15 faults . (j) Provn of 24 V/ 3 Phase DC tripping system with SIREN/HORN and accept switch and over voltage under voltage protection
RELAY. (k) One No Volt Coil to trip the VCB on failure of electric supply. (l) 230 volts, AC, single phase, 80 watt rated strip heater with switch and thermostate for space heating. (m) Breaker panel indication lamps shall be providedd for following functions:- (i) Breaker ON-01 No Green colour (ii) Braker OFF-01No Red Colour (iii) Auto Trip Indication-03 Nos Blue colour (iv) Hand operated/charged independent closing/spring tripping, trip free, operating meahcnism with mannual closing & tripping push button & mechanical breaker" closed/Open" spring charged/discharged indications. (n) Switches and other accessories:- (i) Circuit breaker control switch-01 No (ii) Alarm Bell-01 No (iii) Heater with heater switch & thermostate-01 No (iv) Cubical illumination lamp-01 No (v) 15A, 230V, 3Pin Plug & socket-01 No (o) Mechanical operation counter. (p) Shunt trip coil of 24/30 Volts DC as ordered/required at site. (q) Breaker operated auxilliary switches (NO&NC)-04 Nos (r) One set of potential transformer as per latest IS horizontal draw out type with suitable capacity of HT PT fuse 11000 V of appropriate current for 3 phase, 11 KV vacume circuit breaker including all electrical connection and connected works NOTE:- Any addition/alternation or VCBs of existing switch gears required to install the new VCB including required bus bar, connecting pieces, anodised brass nuts & bolts, B/R work of plinth, ducting work and any other alteration to the existing B/R work shall deemed to be included under the same item and No additional payment will be made to the contractor.
Supply, installation,testing and commissioning the following indoor type, 11KV 3 phase, 50 cycle (50HZ) 400 Amps capacity tripple pole totally enclosed, pattern, vermin proof draw out type with grounded neutral system vacuum circuit breaker, floor mounted with common copper tinned bus bar complete all as specified and directed including the following details :- (a) One set of 3 phase 1250 Amps air insulated tinned copper bus bar with insulated colour coating. (b) One set of side frame for housing of circuit breaker carriage. (c) One 400 amps triple pole minimum 250 MVA (3Sec) rupturing capacity with latest issue of IEC recommandation : IEC 62271-100, vaccum restrike free, trip free, stored energy oprated type, mechanical anti pumping should be built in feature of circuit breaker. VCB with automatic drop out and motor operated spring colsed mechanism complete with auxiliary swithces trunk type meachaniclly ON/OFF indicatior. (d) The breaker is to be mounted on trunk carriage complete with self contained motor charged spring closing mechanism to be operated on DC motor 24V/30V operated fully interlocked raising and lowering meachanism. (e) Cable box for reception for suitable Size XLPE 3 core under ground cable 11000 volts pressure. (f) CT details:-(i) Single phase, 2 core CT with 50-20/5-5-03Nos Core I : Class-1, 15 VA Core II : Class 5P10,15 VA (g) Digital intelligent panel meter indicating line current, line voltage,power factor, KVAR, KVA, frequency, voltage and current harmonics etc. with acuracy 1.0 for active energy. (h) Micro processer based numerical relay for over current and earth fault protection, self powerd type with inbuilt software, USB port, SCADA compatible for remote communications with provision of recording of at least 15 faults. (j) Prove of 24/30 V/3 Phase DC tripping system with SIREN/HORN and accept switch and over voltage under voltage protection
RELAY. (k) 01 No Volt Coil to trip the VCB on failure of electric supply. (l) 230 volts, AC, single phase, 80 watt rated strip heater with switch and thermostate for space heating. (m) Breaker panel indication lamps shall be providedd for following functions:- (i) Breaker ON-01 No Green colour (ii) Braker OFF-01No Red Colour (iii) Auto Trip Indication-03 Nos Blue colour (iv) Hand operated/charged independent closing/spring tripping, trip free, operating meahcnism with mannual closing & tripping push button & mechanical breaker" closed/Open" spring charged/discharged indications. (n) Switches and other accessories:- (i) Circuit breaker control switch-01No (ii) Alarm Bell-01 No (iii) Heater with heater switch & thermostate-01 No (iv) Cubical illumination lamp-01 No (v) 15A, 230V, 3 Pin Plug & socket-01 No (o) Mechanical operation counter. (p) Shunt trip coil of 24/30 Volts DC as ordered/required at site. (q) Breaker operated auxilliary switches (NO&NC)-04 Nos (r) One set of potential transformer as per latest IS horizontal draw out type with suitable capacity of HT PT fuse 11000 V of appropriate current for 3 phase, 11 KV vacume circuit breaker including all electrical connection and connected works NOTE:- Any addition/alternation or VCBs of existing switch gears required to install the new VCB including required bus bar, connecting pieces, anodised brass nuts & bolts, B/R work of plinth, ducting work and any other alteration to the existing B/R work shall deemed to be included under the same item and No additional payment will be made to the contractor.
Supply, Installation testing & commissioning of copper wound step down ISI marked & BEE star labelled transformer Outdoor type complete with standard fitting ,HT 11 KV 3 Phase ,LT 433 Volt 3 Phase 4 wire with Off load tap changer having tapping range + 7.5 % in steps of 2.5 % rating of 250 KVA capacity as per IS 1180:2014 and IS 2026:2011 with total losses @ 50% load 980W & total losses @ 100% Load 2930W. The transformer shall be complete with all standard fitting and accessories gauges first fill of transformer oil upto appropriate level etc, jointing materials connected with elect system earthing etc complete all as specified and directed comprising following accessories : (a) Primary HT side having HT porcelain bushing 3 Nos with brass gun metal bushing rods complete with nuts and washers. (b ) One cable box on LT side for mounting two LT cable consisting of 4 Nos. porcelain with brass bushing rods complete with nuts and washer with two nos. cable gland suitable for LT UG cable providing with bimetallic lugs . (c) Oil conservator with filler type drain valve and oil level gauge. (d) Dehydrating breather with first fill of dehydrating transformer oil. (e) Explosion vents. (f) Thermometer pocket on tank cover including thermometer. (g) Rating plate and terminal marking plate. (h) The earthing terminal two nos. to tank to facilitate fixing to earth strip. (i) Oil level gauge. (j) Lifting lugs (k) Oil filling hole with cap / plug with connection plate complete. (l) Air relief valve plug. Note- (i) Transformer should be tested on factory before dispatch to site. (ii) The Transformer shall be complete with standrad fittings all as specified conforming to IS : 1180 (Part) 2014, IS 2026:2011 and manufacturer shall hold licence/certificate from BIS to this effect . (iii) The Transformer will have its initial oil filling to appropriate level ( cost of oil including testing with desired dielectric strength is included) (iv) All fittings required to install the transformer in the 4 pole structure shall deemed to be included in this item.
Supply, transporting to site, erecting and fixing in position, pre-stressed cement concrete poles, conforming to IS-1678, of size 11 mtr long with minimum cross section 152mm X 152mm at top and coss section 152mm X 260 mm at bottom, class 9 including painting 03 nos band/strips with fluorescent post office red synthetic enamel paint at a distance of 30 cm from plinth block and numbering of poles. Note : Excavation, earth work and PCC will be measured and paid for separately under respective item of Schedule ‘A’.
M&L for cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate as in foundation, filling & mass concrete (below pole) complete all as specified and directed.
M&L for cement concrete 1:2:4 type B-2 using 40mm graded stone aggregate for foundation of stay assembly/ struts/pole etc. (around the poles in pit) complete all as specified and directed.
M&L for providing cement concrete 1:3:6 type C-1 using 20mm graded aggregate as in roof padding, kerbs or mud stops, rounded or chamfered on edges complete all as specified and directed.
M&L for cross arms, bracing, supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed including applying two coats of synthetic enamel paint/aluminium paint over a coat of primer complete all as specified and directed.
Supply and laying cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area 120 sqmm 3 Core complete complete all as specified and directed.
Excavation in trenches in soft/loose soil , not.exc 1.5 mtr wide and not.exc 1.5 mtr deep and getting out in soft/loose soil for laying of cable/foundation of pole and stay etc in complete all as sepecified and directed.
Returning filling including spreading, levelling, watering and well ramming in layers n.exc 25 cm, soft/loose soil complete all as sepecified and directed.
Removing excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above ground level from starting point complete all as sepecified and directed.
M&L for sand cushioning in trenches for protection of HT under ground cable including watering and consolidation complete all as sepecified and directed.
Supply and laying reinforced precast concrete cable cover ISI marked, class HVP type 1 with peak size 300mm×180mm×40mm complete all as sepecified and directed.
Supply and fixing cable route indicater sheet metel circular type with discription 'HT cable' to 25x25 mm MS angle iron not less than 0.45m length complete all as specified and directed. Note - Necessary execavation and PCC will be measured and paid under respective item of this schedule.
Supply and fixing danger notice plate made of 1.6 mm thick mild steel sheet , vitreous enameled white, of size 20 x 25cm with figures, letter, and conventional skull bones in signal red colour conforming to IS : 2551 and fixed with mild steel clamps made of 25 x 3 mm MS flat iron, nuts, bolts and washers etc for HT poles/transformers etc with voltage and danger indicated in Hindi and English complete all as sepecified and directed.
M&L for cable jointing kit of 11 KV(Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm complete all as sepecified and directed.
M&L for cable jointing kit of 11KV(Earthed) grade cable for Straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable size 120 Sqmm complete all as sepecified and directed.
M&L for earthing complete with galvanised steel earth plate electrode 600X600X6 mm thick, burried directly in ground,earth pit not less than 2.25 meter deep below ground level with top edge of earth plate not less than 1.5 meter below ground level, steel earth plate connected with 32 x 6 mm GI strip by means of bolts, nuts, check nuts and washer of galvanised iron or steel as shown in electrical plate No. 5 connected to earth test point all as described in MES schedule part II including excavation earth work concreate pit with 50 mm thick RCC cover in RCC 1:2:4 type B-I duly reinforced with MS bars 6 mm dia @ 150 C/C both ways and pit chamber in PCC 1:2:4 type B-I with 2 Nos suitable lifting handles of 12 mm MS bar and GI protection pipe of suitable size,and watering pipe 20 mm dia with water funnel test point and extra length up to 7.5 meter connected to electrical equipment complete all as sepecified and directed.
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32 x6 mm galvanised iron strip complete all as sepecified and directed.
Supply and laid in trenches / fitting with wall etc.for cable protection steel tubes , light grade, galvanised with all fitting 100 mm dia of bore complete all as sepecified and directed.
M&L for laying of cable by trenchless technology under the road, path, culvert etc including HDPE/PPR pipe 100/150 mm bore as a cover to protect cable complete all as sepecified and directed. . Note :- (i) Cable will be measured and paid separately under respective item of Sch. (ii) Work will be carried out in civil area under the Old Delhi Gurgaon Highway starting from defence area and termnating to defence area. Any approval required to lay the trenchless cable will be obtained by the contractor from the respective department of State Govt and no extra payment will be made to the contractor on this account. The cost for approval from the Sate Govt shall be bear by the contractor. The documents required for the above approval shall be provided by the MES.
Supply and fixing compact air insulated rising main with copper busbar 630 Amps,breaking capacity of 35 KA and IP 54 protection complete all as sepecified and directed. Note:-This item includes any modification (Civil work/Electrical work) to add this busbar to the existing 11 KV busbar.
Supply, installation, testing and commissioning DC battery bank complete enclosed in a sheet metal enclosure size not less than 2mm thick duly compartmentalise for battries, charging system and control system with LED indicator lamps and toggle switch and push button ON/OFF system for charging, discharging etc as per requirement, front openable and locable with proper ventilation as per latest IS, suitable for supply of 24 Volt DC 100/120 AH duly banked with 2 volt led acid maintenance free batteries inlcuding float and trickle battery charging system suitable for input single phase 220 volt/ 3 phase 440 V 50 Hz AC supply including all electrical and control connections upto existing socket for charging and DC supply to the existing VCBs upto 10 Nos. The connection of incoming and outgoing battery bank to VCBs will be made by stranded copper conductors size not less than 2.5 Sqmm for each core in case of multi core cable or single core cable PVC insulated unseathed cable duly drawn into medium grade PVC conduite on floor/wall complete all as sepecified and directed.
M&L for MS Plates (plain or chequered) channels, Fe 410-W (Gde-E- 250) quality-A, square cut or notched forming holes, without any attachment made to shape for duct cover complete all as sepecified and directed.
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as sepecified and directed.
Supply, installing, testing and commissioning lightening arrester expulsion type complete with all fittings, transmission class of discharge capacity 65 Kiloamps suitable for 11000 volts complete all as sepecified and directed.
Ashirwad Contractor and Supplier
Rajindera Enterprises
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .