Office of The Executive Engineer, TLMD-VIII, Jammu
Office of The Executive Engineer, TLMD-VIII, JKPTCL, Ambedkar Chowk, Jammu.
Replacement of 220/132/33 KV Control and Relay Panel (Line Panel, transformer, Bus Coupler, Capacitor Bank Panel and Auxiliary Panel) Grid Station Bishnah
2026_PDD_313412_1
e nit no TLMD-VIII/J/T/10 of 2026-27 dated-23/06/2026
Open Tender
Electrical Works
Turn-key
180 days
220/132/33 KV Grid Station Lalyana, Bishnah
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,000
Executive Engineer, TLMD-VIII, JKPTCL, Jammu
₹8.3 L
Office of The Executive Engineer, TLMD-VIII, Jammu
3 Sept 2026
25 Jun 2026
1 Aug 2026
25 Jun 2026
30 Jul 2026
25 Jun 2026
4 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Design, engineering and Supply of material | |||||
| 1.01 | 220KV Control and Relay Panel for Line/Feeder,
simplex/duplex as per requirement, completely wired including Substation automation supporting IEDs/numerical relays of make ABB/SIEMENS/GEMICOM/ALSTOM/SCHNEIDER with IEC 61850
compatibility, with two Distance Protection Main 1 & main 2 shall be of two different make or of same make with two different platforms with same specifications] | 3 | no. | - | - |
| 1.02 | 220KV Control and Relay Panel for Bus coupler cum Bus
Bar, simplex/duplex as per requirement, completely wired
including Substation automation supporting
IEDs/numerical relays of make ABB/SIEMENS/GE
MICOM/ALSTOM/SCHNEIDER with IEC 61850
compatibility, with Bus-Bar Protection suitable for min 20
bays. Non Directional O/C & E/F Protection and Local
Breaker Backup (LBB) Protection. | 1 | no. | - | - |
| 1.03 | 220KV Control and Relay Panel for Transformer Bay simplex/duplex as per requirement, completely wired including Substation automation supporting IEDs/numerical relays of make ABB/SIEMENS/GEMICOM/ALSTOM/SCHNEIDER with IEC 61850
compatibility, including Differential Protection , Restricted Earth Fault Protection Directional O/C & E/F Protection , Over Fluxing Protection and Local Breaker Backup (LBB) Protection separate relays for primary and backup protection | 2 | no. | - | - |
| 1.04 | 132KV Control and Relay Panel for Line/Feeder simplex/duplex as per requirement, completely wired including Substation automation supporting IEDs/numerical relays of make ABB/SIEMENS/GEMICOM/ALSTOM/SCHNEIDER with IEC 61850
compatibility, including Distance Recorder and under Frequency Relay. (Ist Line Protection) Distance Protection Directional O/C & E/F Protection (Back Up Protection), Local Breaker Backup (LBB) Protection | 2 | no. | - | - |
| 1.05 | 132KV Control and Relay Panel for Bus coupler
simplex/duplex as per requirement, completely wired including Substation automation supporting IEDs/numerical relays of make ABB/SIEMENS/GE MICOM/ALSTOM/SCHNEIDER with IEC 61850
compatibility,including Bus bar Protection suitable for
min 15 No bays | 1 | no. | - | - |
| 1.06 | 132KV Control and Relay Panel for Transformer bay simplex/duplex as per requirement, completely wired including Substation automation supporting IEDs/numerical relays of make ABB/SIEMENS/GE MICOM/ALSTOM/SCHNEIDER with IEC 61850
compatibility, including Differential Protection, Directional O/C & E/F Protection (on HV & LV side), numerical communicable REF protection relay, Over Fluxing Protection Local Breaker Backup (LBB) Protection separate relays for primary and backup
protection | 4 | no. | - | - |
| 1.07 | 132KV Control and Relay Panel for Incomer bay simplex/duplex as per requirement, completely wired including Substation automation supporting IEDs/numerical relays of make ABB/SIEMENS/GE MICOM/ALSTOM/SCHNEIDER with IEC 61850
compatibility, including Differential Protection, Directional O/C & E/F Protection (on HV & LV side), numerical communicable REF protection relay, Over Fluxing Protection Local Breaker Backup (LBB) Protection separate relays for primary and backup
protection | 2 | no. | - | - |
| 1.08 | supply of 2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete | 500 | MTR | - | - |
| 1.09 | supply of 5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete | 1,000 | MTR | - | - |
stage.html
html • 0.02 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.27 MB
SBD10.pdf
Tender Documents • 2.07 MB
BOQ_1014355.xls
BOQ • 0.43 MB
Extension2NIT10.pdf
PDF • 0.65 MB
ExtensionNIT10.pdf
PDF • 0.65 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .