Electrical work
2024_CSIR_204083_1
50(32)/2024-25/W
Open Tender
Electrical Works
Item Rate
180 days
Nagpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹6,000
23 Oct 2024
7 Aug 2024
19 Aug 2024
7 Aug 2024
17 Aug 2024
7 Aug 2024
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group A.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Wiring for circuit/ submain wiring alongwith earth wire with the 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
Wiring for circuit/ submain wiring alongwith earth wire with the 2 X 4 sq. mm + 1 X 4 sq. mm earth wire sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
Supplying indoor type downlighther LED luminaire not more than 15 watts with fitting made from aluminium housing complete with 230 V, driver (SMPS). A. C. supply with necessary materials, Square/rectangular /round shape having cut out 163 mm, high translucent frosted diffuser, spring loaded toggle mounting clamp, CCT-5500K.
Supplying LED industrial luminaire for surface mounting type not more than 18/20 watts tube with box type batten / fitting (white vitreous enamelled/ powder coated) made from CRCA sheet with one no. LED T8 tube lamp complete with 230 V, driver (SMPS). A. C. supply with necessary materials and guarantee for two years.
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
Supplying exhaust fan A. C. 230 V. of 300 mm sweep. Air Delivery 19 CMM, 55 Watts, 900 RPM, Dynamically balanced blades for vibration free rotation, aluminium die-cast body to ensures long life & all accessories etc. (With two years guarantee)
Supplying of outdoor louvers / shutters: Providing louvers / shutters of size 300 mm made up of GI sheet of size 0.7 mm thick, and required frame, necessary arrangement for lifting of louvers.
Installation of exhaust fan in the existing opening, including making good the damage and by providing proper covering to remaining required portion, connection, testing, commissioning etc. as required upto 450 mm sweep.
Fixing the louvers /Shutters complete with frame for a exhaust fan of all sizes
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of Single pole in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 25 A rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of Triple pole in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required.
Supplying armoured cable 4 core 25 Sq mm: Armoured cable of XLPE insulated (cross linked polythelene) PVC sheathed, armoured with galvanised round / strip steel, 1100 V. grade conforming to I.S. 1554 (part-1) & IS :7098 (part-1), 4 core 25 Sq. mm. stranded aluminium conductor. Contractor should submit return cable test report duly certified from OEM/ Govt lab. Institute before installation.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Upto 35 sq. mm size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Upto 35 sq. mm (clamped with 1mm thick saddle) size on wall surface as required.
Supplying and making end termination with brass compression gland and aluminium lugs for 4 X 25 sq. mm (28mm) size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
Supplying and laying of 40 mm dia (OD-40 mm & ID-32 mm nominal) size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
Supplying and fixing 4 way (4 + 12), Double door, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for 3½ X 95 sq. mm size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
Underground cable fault detection using cable fault detector machine, including excavation of soil & riffiiling the same. As required.
Supplying armoured cable 4 core 95 Sq mm: Armoured cable of XLPE insulated (cross linked polythelene) PVC sheathed, armoured with galvanised round / strip steel, 1100 V. grade conforming to I.S. 1554 (part-1) & IS :7098 (part-1), 4 core 95 Sq. mm. stranded aluminium conductor. Contractor should submit return cable test report duly certified from OEM/ Govt lab. Institute before installation.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and installing 300 mm width X 50 mm depth X 1.6 mm thickness size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
KAMAL AND SONS ELECTRICAL SERVICES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .