Construction of 33 KV feeder from 220/33 KV Substation Awas Vikas to 33/11 KV S/S Harihar Pur
2020_MVVNL_514119_1
17/EUCC(V)/LESA/2020-21
Open Tender
Electrical Works
180 days
220/33 KV Substation Awas Vikas to 33/11 KV S/S H
As per tender documents
2 documents required · 2 mandatory
₹3,540
A/c. No. 10101985364,IFSC CODE No. SBIN0003347,SBI
₹67,000
6 Nov 2020
23 Sept 2020
30 Sept 2020
23 Sept 2020
29 Sept 2020
23 Sept 2020
Amount
Dragging, loading, carriage and unloading of following store materials with proper stacking from ESC Daliganj to JE dumps store and from JE dump store to work site within municipal area.
STP 11 M long
33 KV pin insulator
Top chanel 100X50 MM 10 kg / mtr
MS angle 65x65x6MM 5.8 kg / mtr
33 KV pin with nut
M S Earthing Rod 20x2500 mm
Single core PVC Cable 1X400
33KV 3x300 sq mm XLPE cable
33KV ST/Th C/J kit 3x300 sq mm
33KV End termination O/Door 3x300 sq mm
33 KV Feeder control Panel
33 KV VCB
33 KV CT 400/100/1 A
33 KV Bus Isolator
33 KV Line Isolator
MS Channel 125x65 mm
MS Angle 75x75x6 mm
Isolator Structure-Fabrication of Isolator structure minimum 3.5 mtr overall height and 2.5 mtr above ground level as per RESSPO drawing, with help of M.S channel 125x65 mm two pieces of M.S channel joined to each other by M.S flat 50x6 mm, diagonally at the interval of 0.5 mtr and top & bottom of the structure. Grouting of Isolator structure in CC (cement ,coarse sand and stone grit of 20 mm gauge) including supply of necessary T&P and painting os structure complete.(only M.S channel and angle provided by the deptt)
Lightning Arrestor/ CT structure/ PT structure : - Fabrication of lightning arrestor/CT structure/ PT structure as per RESSPO drawing with the help of 2 nos M.S channel 125x65 mm minimum 3.5 mtr long grouting 1 mtr deep from ground level in cc in ratio 1:4:8. complete in all respect.
Fabrication of structures, grouting, plinthing and painting of structures for following equipment.
Cable stand
Mounting of accessories/equipment on fabricated structure complete work with making proper alignment and tightening the work includes fabrication work if required for proper operation of equipment .
33 KV VCB
Bus/Line Isolator
Dragging of 33 KV T/F/ Feeder Control Panel from unloading place upto control room and placement, erection, and grouting commissioning of the same as per RESPO Norms
Construction of cable trench of size 150 mm wide 300 mm deep with brick work along with provision trench cover M.S strip at the interval of 0.30 M and M.S angle at both the edge of the trench.
Construction and fixing of trench cover0.5 M wide 0.75 mm thick with cement, coarse sand & stone grit in ratio 1:2:4 for covering of cable trench150 mm wide with provision of M.S Angle and MS Bar as per RESPO Norms
Laying of copper control cable of following sizes its proper dressing ,ferruling and connection with the system.
2x2.5 sq mm
4x2.5 sq mm
6x2.5 sq mm
Earthing of Substation equipment by way of boring and lowering of G.I pipe 1.5" dia up to water level and minimum 20 M deep from the ground level connection in between GI pipe and equipment with GI strip of size 50x6 mm.
Jumpering of Complete line bay by ACSR Panther conductor with the help of connectors and PG clamp
Fabrication of teniss net type switchyard fencing with toe wall with help of wiremesh10 SWG (37mmx50mm) as per drawing along with Fabrication of one number gate made of MS Angle, MS Channel, MS Flat together with locking arrangement, its Installation including the cost of civil material, angle 50x50x6mm, Channel Etc
Laying of Interlocking tiles at yard area as per norms
Fabrication & erection of 33 KV cable exposure type double pole with the provision of separate bus bar for each cable with fixing of necesory clamps and other acessories like danger board,number plate,barbed wire, 9 no. pin insulators with pins,2 no. channels 125x65 mm (1600mm each),1 no.MS channel 125x65mm(3200mm in length) and 2 no.MS angle 65x65x6 mm (each 3200mm in length ) for supporting the hoisting of cable & poles.its jumpering by single core PVC aluminium cable with proper size of lug. (all material arranged by contractor except steel,pole,PVC aluminium cable & insulator).as per RESPO norms.
Laying of 33 KV XLPE Cable.
Making proper markig of cable by markig tape/marking tag at proper interval (every 0.5 mtr underneath) marking tape /tag provided by contractor
In normal soil in double circuit by digging of trench 1050 mm, deep, 750 mm wide including supply of required material, 1st class bricks, stone pad. The inter axial spacing between two cable should be in between 0.25 M to 0.40 M the two cable must be separeted by a partition to single brick. (All the material required for laying will be supplied by the contractor except 33 KV XLPE cable)
In normal soil Single circuit by digging of trench 1050 mm, deep, 650 mm wide including supply of required material, 1st class bricks, stone pad.(All the material required for laying will be supplied by the contractor except 33 KV XLPE cable)
In HDPE Pipe
In RCC pipe NP-4 single circuit.
In GI pipe single circuit.
Laying in already existing trench S/C
Laying of 33 KV XLPE Cable single circuit by HDD method with HDD machine
Laying of 33 KV XLPE Cable single circuit by HDD method in GI pipe with HDD machine at Railway X-ing
Digging of pit of size 3x2.5x1 mtr. for making straight through joint 33 KV work included filling of soil leveling and ramming of the same .( S/Th Provided by department)
Plotting of cable layout rute on graph paper (i.e. depth underneath and distance from either side from prominent reference fixed point ) the reference point must not be more than 100 mtr.
Grouting,Plinting and Painting of new erected 11M long ST poles of single pole support,double pole cable exposures and end type poles of 33 KV lines
Digging of Pit in kachcha/Pakka land in depth upto 1/6 length of Pole, Dragging of STP from near by place/Dump, Erection of Single pole along with stone pad in bottom with proper alignment of line for 33 KV line on 11 M long ST Pole and refilling with ramming of earth.
Grouting of pole in depth of 1/6 the length of pole in ratio 1:4:8 in cement sand and brick balast as per RESPO norms.
Construction of pole plinth 300mm x 450 mm above ground level in 1:2:4 in cement, coarse sand and stone gritt as per RESPO norms.
Painting of new erected ST pole with two coat of red oxide paint,PO red paint at top of pole 2 M & balance by two coats of best quality aluminium paint ISI of Burger/Nerolac/Asian mark as per norms.
High Pressure Testing of 33 KV Cable XLPE cable.Testing equipment arranged by contractor
Fixing of Cable marker on cable route and dipitching of feeder name and voltage onn cable marker
Hoisting of 33KV XLPE cable on double pole/existing structure with MS pipe of size 5/6" dia 3 M long including its jumpering complete with clamps, nuts and bolts(all material arranged by contractor).
Hoisting of 33KV XLPE on cable stand including its jumpering complete with clamps, nuts and bolts(all material arranged by contractor).
CHAUHAN ELECTRICALS
ARIHANT ELECTRIC COMPANY
NATIONAL CONTRACTOR & GENERAL ORDER SUPPLIER
RAJ ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid