Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC | ₹1.3 Cr | L1 | Accepted-AOC work allotted |
Tender Value
₹1.1 Cr
EMD Value
₹2.1 L
Closing Date
6 Dec 2019, 5:00 pmClosed
Raja Nagender Singh
Executive Engineer Electrical Division PWD B and R Karnal
Up-gradation of 50 Bedded Hospital into 100 Bedded Hospital at Nilokheri Distt. Karnal (Pdg. EI, Sub Station and Security light only)
2019_HRY_107228_2
PWD/Elect-KNL/Elect-KNL/16616
Open Tender
Construction Works
Works
600 days
Karnal
Please refer Tender documents.
3 documents required · 3 mandatory
₹15,000
Executive Engineer Elect. Division PWD B and R
₹2.1 L
31 Aug 2020
23 Nov 2019
9 Dec 2019
23 Nov 2019
6 Dec 2019
23 Nov 2019
Amount
Supply and erection of PVC copper insulated and sheathed 2-core circular flexible wire. 31.9 Size 1.50 sqmm ( 48 / 0.20mm). 31.9 (i) d
Supply and erection of moulded case circuit breakers on wall or on existing pedestal including bonding to earth and necessary connections. 31.12 (c) 15 amp.to 60 amp. 415 V ,10 KA 3-phase. 31.12 c (i)
100 amp.to 220 amp.415 V,10 KA 3-phase. 31.12 c (ii)
300 amp. to 400 amp. 415 V , 35 KA 3-phase. 31.12 c (iv)
500 amp. to 600 amp. 415 V , 35 KA 3-phase. 31.12 c (v)
Supply and erection of M.S. angle iron frame duly welded for housing M.S. sheet & main switches etc. on it, fixed on wall by means of suiteble size of rag bolts with cement concrete ,duly painted with three coats of approved paint including one coat of red oxide. 31.13 Size 40 mm x 40 mm x 6 mm. 31.13(ii)
Supply and erection of 3 mm thick mild steel sheet duly welded on existing M.S. angle iron frame for fixing the main switches etc. as required, duly painted with three coats of approved paint including one coat of red oxide. 31.14 (i)
Supply and erection of sheet steel enclosure 2 pole / 3 pole with earth plug and socket suitable for incorporating single pole / triple pole MCB on wall / on existing pedestal complete with necessary connections etc. 31.15 S.P.N. enclosure for single pole MCB 20 amp. 31.15 (ii)
Supply and erection of miniature circuit breaker / isolator 240 /415 V in the existing distribution board including making necessary connections. 31.17 SP MCB of 9 KA breaking capacity 6 amp. to 32 amp. 31.17a) (ii)
TPN MCB of 9 KA breaking capacity 6 amp. to 32 amp. 31.17(a) (ii)
TPN MCB of 9 KA breaking capacity 40 amp. to 63 amp. 31.17(a) (iii)
Supply and erection of Fittings and Accessories. 31.18 Call bell 220 / 230 volts A.C. bakelite with double coil. 31.18 (vii)
Switch 5 amp. On existing sheet. 31.18 (xii)
Wall socket 5 amp. On existing sheet. 31.18 (xiii)
Bakelite sheet including fixing with brass screws and washers. 31.18 (xviii) 5 mm thick . 31.18 (xviii) (a)
Supply and erection of rectangular bulk head fitting of size 17 cm x 14 cm, aluminium casted with aluminium colour out side and white stove enamelled inside/complete with guard, glass etc. secured by brass screws suitable upto 100 watts lamp with B.C. lamp holder but without lamp. 31.18 (xx)
Erection only of 1x40 watts or 2x40 watts 1220 mm long / 1x20 watts or 2x20 watts ,610 mm long fluorescent tube fitting directly on wall including necessary connections with 0.75 sqmm ( 24 / 0.20 mm ) PVC copper flexible cable for connecting the tube with the adjecent point. 31.18 (xxiv)
Supply and erection of hexagonal M.S. box 1.60 mm thick having each side 8 cms , 7.5 cms deep top covered with M.S. lid by means of screws including 10 mm dia 30 cm long mild steel rod made into suitable suspension hook and erected in RCC slab for erection of fan , the bottom covered with 3 mm thick bakelite sheet with suitable holes , painting etc. complete with all labour and material required to complete the job. . 31.18 (xxvi)
Erection of ceiling fan complete with necessary earthing of fan and regulator including carriage from local railway station /goods transport /PWD store to the site of work. 31.20 (i)
Erection of exhaust fan complete with necessary earthing of fan and regulator including carriage from local railway station /goods transport /PWD store to he site of work. 31.20 (iii)
Making suitable hole in the wall upto 450 mm sweep exhaust fan including finishing the same and fixing of wire mesh duly fixed with Deodar wood frame of section 40 mm x 25 mm thick. 31.20 (v)
Pdg. and fixing of required size of deodar wood frame of section 50 mm x 32 mm for fixing exhaust fan upto 450 mm sweep. 31.20 (vi)
Supply and erection of pipe for wiring purposes including bends inspection boxes etc. where necessary and painting as required. 31.21 Heavy guage welded conduit pipe 20 mm dia 1.60 mm thickness flushed. 31.21 (xxi)
Heavy guage welded conduit pipe 25 mm dia 1.60 mm thickness flushed. 31.21 (xxii)
Galvanised iron flexible pipe comlete with socket nipples and checknuts etc. at both ends ( upto length of 1 metre.) 31.21(xxvii) Size 25 mm dia. 31.21 (xxvii) (c)
Supply and erection of cast iron pipe laid 1 metre below ground level including digging and refilling of the trench completing with jointing with jute and cement etc. 31.21(xxix) Cast iron pipe 120 mm dia. 31.21(xxix) (a)
Earthing 31.22 Earthing with GI earth pipe 4.5 m long and 40 mm dia with masonry enclosure on the top etc. as required . 31.22(i)
Extra for using salt and charcoal / coke for pipe earth electrode as required. 31.22(ii)
Earthing with tinned copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) comlete as equired. 31.22(iv)
Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode. 31.22(v)
Supplying and laying of 25 mm x 5 mm G.I. Strip at 0.50 metre below ground level as strip earth electrode including soldering etc. as required . 31.22(viii)
Pdg. and fixing 25 mm x 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required . 31.22(x)
(b) Lightning conductor Galvanised iron. 31.24 Excavation of earth pit 180 cm. round at top and 90 cm. at bottom 4.5 metres deep and refilling the same in plains including supply of necessary charcoal / coke and salt mixture. 31.24 (ii)
Supply and erection of 60 cm. X 60 cm. X 6 mm thick galvanised Iron plate including nacessary bolts and nuts to G.I. tape . 31.24 (iv)
Pdg. Standard watering tank including down pipe and C.I. cover with locking arrangement etc. 31.24 (v)
Supply and erection of 20 mm x 3 mm thick lightning conductor G.I. tape fixed with suitable G.I. stapples of same size. 31.24 (vi)
Supply and erection of 25 mm dia meter 1.5 metre long lightning G.I. tube rod tapered in to a point at the top with 16 cm. X 16 cm x 3 mm thick G.I. base plate and necessary nuts and bolts with washer. 31.24 (viii)
Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections . 31.26 240 Sq. mm 3.5 Core Cable . 31.26 (xxxiii) Ard.
400 Sq. mm 3.5 Core Cable . 31.26 (xxxv) Ard.
16 Sq. mm 4 Core Cable . 31.26 (xI) Ard.
35 Sq. mm 4 Core Cable . 31.26 (xIii) Ard.
50 Sq. mm 4 Core Cable . 31.26 (xIiii) Ard.
Supply and erection of suitable compression type brass cable glands for underground Cable. 31.28 10 Sqmm to 16 Sqmm Cable 2 to 4 Core . 31.28 (ii)
25 Sqmm to 50 Sqmm Cable 2 to 4 Core. 31.28 (iii)
70 Sqmm to 95 Sqmm Cable 3 to 3.5 Core . 31.28(iv)
240 Sqmm Cable 3 to 3.5 Core . 31.28 (vi)
300 Sq mm to 400 Sqmm Cable 3 to 3.5 Core . 31.28 (vii)
Supply and erection of metal clad bus bar chamber made from 1.6 mm thick M.S.sheet fixed with rag bolts on wall or on existing pedestal / angle iron frame including bonding to earth , detatchable top and bottom painting and necessary connections etc.(Copper bars duly tinned ). 31.31 200 amp. 4 bars of 100 cm each (cross section 25 mm x 5 mm) chamber over all size 1.10 m x 45 cm x 18 cm . 31.31 (a) (v)
400 amp. 4 bars of 55 cm each (cross section 50 mm x 5 mm) chamber over all size 60 cm x 55 cm x 23 cm . 31.31 (a) (ix)
Wiring in 1.5 sq.mm PVC Insulated Copper conductor cable in 1.6 mm thick conduit pipe. 31.36 Fan Point 31.36 (I) Short point (a)
Medium Point (b)
Long point. (c)
Light Point 31.36 (II) Short point (a)
Medium Point (b)
Long point. (c)
Call bell point including M.S box of size 180 mmX100 mmX 60 mm deep for Call bell. 31.36 (VI) Long point. (c)
3 pin 5 amp. plug point including earthing the 3rd. pin etc. 31.36 (VII) Short point (a)
Medium Point (b)
Long point. (c)
3 pin15 amp. plug point with 4 sq mm PVC insulated Copper conductor cable- including earthing the 3rd. pin etc. 31.36 (VIII) Long point. (c)
Supply and erection of PVC unsheathed copper conductor cable single core 1100 volts grade in pipe of suitable size excluding cost and erection of pipe . 31.4 Size 1.5 sqmm ( 3/0.81 ) 31.40 (i)
Size 2.5 sqmm ( 3/1.05 ) 31.40 (ii)
Size 4 sqmm ( 7/0.85 ) 31.40 (iii)
Size 6 sqmm ( 7/1.05 ) 31.40 (iv)
Size 16sqmm ( 7/1.70 ) 31.40 (vi)
Supply and erection of Double door sheet steel enclosure distribution boards suitable for MCB's & ELCB's recessed in wall including bonding to earth complete with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 31.41 4-way , TP&N ( Horizontal) (8+12) 31.41 (v)
8-way , TP&N ( Horizontal) (8+24) 31.41 (vi)
Supply and erection of PVC pipe ISI marked ( Medium ) recessed in wall / ceiling etc. including the cost of PVC bends , inspection boxes , iron hooks and cement concrete etc. complete in all respect upto the entire satisfaction of Engineer-in-charge of work. 31.44 25 mm dia. 31.44 (ii)
Supply and erection of MS box made of 16G MS Sheet recessed in wall, with arrangement of fixing brass screws including cost of 2 Nos. checknuts of required size and one no. PVC bush for each pipe including all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer-in-charge of work. 31.49 With 2 coats of primer 31.49 (i)
Supply & erection of Socket size rotary step type Electronic regulator for A.C. ceiling fan Anchor make Delux model No. 50440 ISI / SSK make PC 561 operated on 120/280 V A.C. Supply complete including cutting of existing Bakelite sheet and making necessary connection etc. up to the entire satisfaction of the Engineer-in-Charge of the Work. 31.55
Supply installation testing and commissioning of wall / free standing floor mounting dust & vermin proof compartmentalized cubical panel made out of 2mm thick CRCA sheet, required hardware, 3mm thick bakelite sheet provided all along the bus bar and cable alley separating switches compartment and supporting suitable channel, dully painted by 2 coat of zinc / Red oxide primer followed by 2 coats of powder coating in grey or required shade after rinsing. The panel having PU / Neoprene rubber gasket of not less than 3mm thickness, separate detachable gland plate MS base channel, hinged door with inter locking arrangement for equipment / switch gear. 31.63 Transparent acrylic sheet shall be provided in front of bus bar compartment to prevent direct access to bus bar bakelite sheet 3mm thick for separately cable alley to BBC from switch chember. Extended solid copper bars up to cable alleys shall be provided for outgoing connection which shall be paid as extra items. Side walls and cable alley compartments shall be having bolted type doors with detachable extension type structure. The panel will be complete with control wiring (copper) and fuse protection. (only outer area on all sides shall be measured).
Supplying and fixing of Copper bus bar duly tinned by means of SMC/DMC type insulator high tensile nuts and bolts spring washers fixing to same in existing panel including bending , cutting in required shape and size and insulation with colour coding heat shrinkable PVC insulation Complete in all respect. 31.64
Supply & fixing of rotary handle for on / off operation of existing MCCB in the LT panel including fixing the same in position with all labour and material required to complete the job in all respect. 31.66 (i)up to 125A MCCB
(ii)Above 125A MCCB
S/E of mark double walled corrugated (DWC) HDPE pipe laid 1 mtr. below ground level including diging and refilling of earth including cost of suitable size socket / cuppler for HDPE pipe including the cost of labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-incharge of the work 31.67 (ii)HDPE pipe 90 / 75mm outer dia / inner dia.
(iii)HDPE pipe 145 / 123mm outer dia / inner dia.
Supply and erection of MS box of size 8'' x 10'' x 4'' (20cmx25cm) and 10cm deep made of 1.6mm thick M.S. sheet covered with 5mm thick bakelite sheet for fixing of 4 Nos. socket and switch of 6 amp. and one No. of multi socket and switch of 15 amp. including fixing of one No. fuses unit and indicator off another make. the M.S. box is recessed in wall including cost of necessaru cement and mixture required to complete the job in all respect upto entire satisfaction of the Engineer-in-charge of work. NS
Supply and erection of LED Flood Light 160W Luminaires of Makes: Bajaj / GE / Philips / Wipro with Pressure die cast aluminium housing with lens and accessories required to complete the job in all respect including erection on existing pole for fixing including connection of the same upto the entire satisfaction of Engineer in Charge of the work. NS
Electric Substation & DG set Supply, Receiving, Unloading, Shifting, Installation, Testing & Commissioning of indoor type floor mounted, dust, damp and vermin proof, cubicle HT. Metering Panel made out of 14 gauge CRCA sheet steel complete with 5Amp electronic trivector meter, C.T.'s of 40/5Amp, 0.5 Class, 10VA Burden, and P.T's of 11KV/ /3, 110V/ /3, 100 VA conforming to relevant IS Standards and complete as required. H.T. Metering cubicle along with C.T.'s, P.T.'s and trivector meter shall be got tested and approved from local electricity supply authority. The GA drawing shall be got approved by ELECTRICITY BOARD authorities before fabrication NS H.T. Metering Panel described as above
11 KV HT ISOLATOR UNIT- (OUTDOOR TYPE) NS Supply of 11 KV, 630A, Out Door Type HT Isolator unit with overcurrent, earthfault & short circuit protection as per technical specification and as required. (Make ABB, Siemens , Schneider).
Supply, Erection, testing and commissioning of Crompton/ Bharat Bijli /Kirloskar/ NGEF/ Alstom make/ Transformer-750 KVA 11/0.433 K. V.3 Phase-50 cycles copper wound out oor type up to the entire satisfaction of the Engineer-in-charge of work as per detailed specification given as under: No. load voltage ratio 11/0.433 K V. No. of Phase = 3 Frequency cycles = 50HZ Type- double wound core type copper wound Cooling = ONAN Duty = Indoor Vector group/ISS-DYN 11/IS- 2026/77 Tapping on HV Compensation +5.0% To - 15% in steps of 1.25% ON LOAD TAP CHANGER with RTCC Panel. Temperature rise (oil/Res = 0C) 50/55C Attitude= upto 1000metres above M.S.L. Fitting/Accessories Provided. Bucholez relay. OFF Circuit tape changer, Externally hand operated. Oil conservator with Filling hole & cap. Plain oil level guage with minimum Level marking Thermometer pocket 4Nos. plain roller uni directional 1Nos dial type thermometer. Silica-Gel Breather 1st Filling of oil. Drain cum filter value Rating & diagram plate Two earthing terminal Lifting arrangement Explosion vent Air releases Plug. Diagram & rating plate Termination: - HV=3 pole single glands Cable box suitable for reception of 1 no. 3 core up to 120 sqmm H.T.XLPE cable including cost of copper lugs/thimble. 4 Pole 3 Glands cable box suitable for 3 No. 400 sq.mm 3.5 core poly vinyl chloride cable having extended copper bars of requisite capacity from L. T. bushing for making connection with cable including cost of copper lugs/ thimbles. LV: Neutral suitable cable box for earthing Provided. NS
Erection of 'H' pole (double pole) structure of PCC pole 11m long including excavation including the cost of 150mm thick 1:3:6 PCC at bottom including supplying and fixing cross bracings made out of 75 x 40 x 4.7mm channel incluidng clamps from 50m x 6m flat, angle and flat irons etc. in accordance with the specification and drawings complete as required and painting (All bolts, nut of GI) including treatment of burried portion in ground with silicate. NS
Supply and erection of stay set complete (galvanised) with 19/20mm dia x 1.8 meters long stay rod, anchor plate of size 45 cm x 45 cm x 7.5mm, GI Thimble, stay clamps, bow lightener, 7/400mm dia, GI stay wire and strain insulator etc. in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling etc. as required. NS
Supply and erection of 100 x 50 x 6mm channel iron cross arm on M.S. pole complete as below with suitable MS clamp of 50mm x 6mm angle iron with GI bolts nut and washers including painting etc. as required (for earth wires and guards). NS 2.8 mtr. in length
Supplying and erection of 11 KV brown glazed pin type porcelain insulator complete with galvanised spindle nuts, washer etc. complete as required as per specifications. NS
Supplying and erection of anti-climbing device to be fixed on 11m long M.S. pole as per specification. NS
Supplying and erection of following rating 11KV TP gang operated Air break isolator vertically mounted on MS channel of size 75mm x 40mm x 6mm duly provided on PCC poles structure with 3 insulator per phase titling type jaw type self aligning hard PB contacts having positive clipping action to prevent undue heating, arching horn and fitted with brown glazed porcelain insulator of approved make on channel base having 762mm phase distance and 300mm leakage distance clamp type solder less connector to accommodate ACSR conductors DOG completely fabricated and tested in accordance with relevant IS code including all mechanism 25mm dia. GI pipe operating handle 25mm square guage bar universal joints galvanized guides etc. and having locking arrangements at "OFF" and "ON" position of switch complete as required including making connection to OH line/ fuse etc. as required with ACSR conductor and providing suitable bracket made out of 75 x 40 x 4.4mm with necessary clamps for fixing operating handle on structure painting of all metallic brick, clamps etc. earthing complete as per specification. (Note: all channels and clamps required for above installation deemed to be included and nothing extra is payable). 400 amp NS
Supplying and erection of 11KV pallet type lightning arrestor on cross arm including supplying and fixing of suitable bracket of MS channel / angle iron with clamps with GI bolts and nuts with washers etc. including making connections to OH line and to earth etc. as required per specifications (For 3 phase) NS
Providing and fixing of H.T. danger notice plate of 250mm x 200mm made of mild steel, atleast 2mm thick and vitererous enammelled while on both sides & with inscription in single red colour on front side as required. NS
Providing and fixing of outdoor type CT, PT and tri-vector meter on H-pole structure as per guideline of UHBVN as complete as required. NS
11 metres long 152 mm x 203 mm at top and 152 mm x 368 mm at bottom with working load of 360 Kg. burried 2.20 m in ground. HSR-31.30 (VI) (iii) (NOTE - ITEM NO 1.1, 1.2, 1.3 & 2.0 SHALL BE SUPPLIED ONLY AFTER APPROVAL FROM STATE ELECTRICITY BOARD).
Design, Manufacturing, Supply, Installation, Testing and Commissioning of Radiator Cooled DG sets of following capacity (rating in kVA) compact packaged silent type, with acoustic enclosure (outdoor type) to reduce the noise level as per requirements of central pollution control board, (72 db from 1 mtrs.) 415Volts, 3 phase, 50 Hz AC alternator coupled to diesel engine with electronic governer suitable for auto load sharing and auto AMF complete with all accessories, standard specifications tool kits, service manual, self starting device, fly wheel, coupling with guard, V velt, radiator, instrument panel, AMF Panel (starting switch with key, Water Temperature indicator gauge, Lub OIl Pressure gauge, Lube oil temperature gauge, Battery Charging Ammeter, indicating lamp, hour counter etc.), residential type silencer, common bed plate, anti vibration isolation pads, grouting bolts, first charge of engine oil, gear oil, high speed diesel oil, 24 volt chargeable battery set with Trickle/Boost Battery charger, PCC or equivalent controller complete as required including erecting, testing and commissioning of following type 415 Volts, 3 phase, 50 Hz. AC alternator coupled to Diesel Engine complete with all accessories. AMF Panel shall be supplied with D.G. Set with required switchgear and all accessories. Make Engines: Cummins, Greaves Cotton, Kirloskar, Ruston, Make Alternators : Crompton, Jyoti, Kirloskar, NGEF, Stamford. NS Supply, Installation, Testing & Commissioning of DG set associated works as per CPCB-2 norms etc. with all necessory accessories and also getting approval / sanction from the Pollution Control Board. 250 KVA D.G. Set with suitable capacity of fuel Tank
Supply and erection of moulded case circuit breakers on wall or on existing pedestal including bonding to earth and necessary connections. (Make Siemens , Schneider, ABB, Legrand) 31.12 (c) 15 amp.to 60 amp. 415 V ,10 KA 3-phase. 31.12 c (i)
100 amp.to 220 amp.415 V,10 KA 3-phase. 31.12 c (ii)
Supply installation testing and commissioning of wall / free standing floor mounting dust & vermin proof compartmentalized cubical panel made out of 2mm thick CRCA sheet, required hardware, 3mm thick bakelite sheet provided all along the bus bar and cable alley separating switches compartment and supporting suitable channel, dully painted by 2 coat of zinc / Red oxide primer followed by 2 coats of powder coating in grey or required shade after rinsing. The panel having PU / Neoprene rubber gasket of not less than 3mm thickness, separate detachable gland plate MS base channel, hinged door with inter locking arrangement for equipment / switch gear. Transparent acrylic sheet shall be provided in front of bus bar compartment to prevent direct access to bus bar bakelite sheet 3mm thick for separately cable alley to BBC from switch chember. Extended solid copper bars up to cable alleys shall be provided for outgoing connection which shall be paid as extra items. Side walls and cable alley compartments shall be having bolted type doors with detachable extension type structure. The panel will be complete with control wiring (copper) and fuse protection. (only outer area on all sides shall be measured). 31.63
Supplying and fixing of Copper bus bar duly tinned by means of SMC/DMC type insulator high tensile nuts and bolts spring washers fixing to same in existing panel including bending , cutting in required shape and size and insulation with colour coding heat shrinkable PVC insulation Complete in all respect. 31.64
Supply & fixing of rotary handle for on / off operation of existing MCCB in the LT panel including fixing the same in position with all labour and material required to complete the job in all respect. 31.66 (i)up to 125A MCCB
(ii)Above 125A MCCB
STREET LIGHT. S&E of single arms bracket made of 50mm dia GI pipe B class 1.50 mtr. Long with 25mm dia bottom pipe GI with coller pipe (GI) 100mm dia 60cm Long with MS nipple as required for fixing of fitting duly welded at end of bracket top covered with ornamental cap duly welded, painted 2 coats of aluminium paints on bracket and golden paint of ornamental cap including the cost of labour and petty material etc. complete in all respect upto the entire satisfaction of Engineer-incharge. NS
Supply and erection of LED Street Light 90W Luminaires of Makes: Bajaj / GE / Philips / Wipro with Pressure die cast aluminium housing with lens and accessories required to complete the job in all respect including erection on existing pole for fixing including connection of the same upto the entire satisfaction of Engineer in Charge of the work. NS
Supply and erection of LED Flood Light 160W Luminaires of Makes: Bajaj / GE / Philips / Wipro with Pressure die cast aluminium housing with lens and accessories required to complete the job in all respect including erection on existing pole for fixing including connection of the same upto the entire satisfaction of Engineer in Charge of the work. NS
Construction of RCC foundation for 12.5 / 16 / 20 mtr. high mast complete in all respect as per the appended design including the cost of digging sand filling 6" lean concrete 1:8:16 / bricks souling, Bar binding cement concret (M-20) shuttering, fixing of foundation bolts, refilling, carrying and erection of High Mast on foundation including petty material to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. (Foundation bolts and template to be supplied by department). NS
Supply / installation MS enclosure made of 16G MS sheet duly painted etc. for MCCB up to 100A. 4 pole including inter connection and fixing the same in existing MS pedestal complete with all labour and material required for the same up to the entire satisfaction of Engineer-in- Charge of the work. NS
HSR items. Supply and erection of PVC copper insulated and sheathed 2-core circular flexible wire. 31.9 Size 2.50 sqmm ( 80 / 0.20mm). 31.9 (i) e
Supply and erection of sheet steel enclosures distribution boards suitable for MCBs etc. on wall/ existing boards / pedestal with rag bolts including bonding to earth . 31.12 (D) SPN Distribution board 2-way. 31.12(D ) (ii)
Supply and erection of miniature circuit breaker / isolator 240 /415 V in the existing distribution board including making necessary connections. 31.17 Miniature circuit breakers of 9 KA breaking capacity. (a) SP MCB of 9 KA breaking capacity 6 amp. to 32 amp. 31.17a) (ii)
Earthing 31.22 Earthing with GI earth pipe 4.5 m long and 40 mm dia with masonry enclosure on the top etc. as required . 31.22(i)
Extra for using salt and charcoal / coke for pipe earth electrode as required. 31.22(ii)
Supply and erection of 20 mm x 3 mm thick G.I. tape fixed with suitable G.I. stapples of same size. 31.22(xix)
Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections. 31.26 10 Sq. mm 2 Core Cable . 31.26 (iv) Ard.
16 Sq. mm 4 Core Cable . 31.26 (xI) Ard.
M.S.pedestal of size 750 mm wide , 900 mm high , 300 mm deep and bottom totally open , duly embeded in cement concrete block of size 900 mm x 450 mm x 200 mm above ground level duly plastered with 12 mm thick 1:4 cement plaster , having a base of size 1050 mm x 600 mm x 250 mm below ground level . 31.33 (ii)
S/E of mark double walled corrugated (DWC) HDPE pipe laid 1 mtr. below ground level including diging and refilling of earth including cost of suitable size socket / cuppler for HDPE pipe including the cost of labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-incharge of the work(i)HDPE pipe 63 / 50mm outer dia / inner dia. 31.67
Supply & Erection of Hot dip Galvanized octagonal pole of 3 mm thickness, with base plate including cost of nut and bolts and all accessories as supplied by the manufacturer including cost of foundation accessories etc. The foundation bolts as per manufacturer design should be hot dipped galvanized pole complete with door locking arrangement terminal plate consisting of 2 nos 100 Amp 4 pole natural links including connection etc. with suitable connecting arrangement for 2 nos MCB / Kit Kat including cost of R.C.C. 1:1.5:3 for foundation of size 0.7 M X 0.7 M X 1.8 M with minimum 8 nos 12 mm dia longitudinal MS reinforcement rods with rings of 8 mm dia not more than 200 mm C.C for fixing the pole with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineerin-charge of the work. (i)7 Mtr Long pole with top dia 70 mm and bottom dia 130 mm with base plate of size 220x220x12mm. HSR-31.68
Supply and erection of module case circuit breaker single pole/ 4 pole on wall /on existing pedestal including bounding to earth and making necessary connection required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. v 4 pole MCCB 100 amp 31.69
Supply and erection of metal clad bus bar chamber made from 1.6 mm thick M.S.sheet fixed with rag bolts on wall or on existing pedestal / angle iron frame including bonding to earth Copper bars 63 amp. 415volt 4 bars of 325mm each (Cross section 20x3mm) duly tinned over all size of the chember 375mmx295mmx140mm. 31.76
Supply, installation, Testing and commissioning of 16 Mtr. long High Mast manufactured from B.S.E.N. 10025 or equivalent grade material in, 2 (two) section hot dip, galvanized inside and outside in single dip, suitable for wind velocity as per IS 875 Part-3 suitable for 6 Nos. Luminaire loading fully motorized with starter & cable complete along with standard accessories supplied by the manufacturer with 3 nos. steel wire rope double drum system and twin dome aviation light with LED without foundation but including cost of set of foundation nut and bolts, installation at site complete in all respeect upto entire satisfaction of Engineer-in-Charge. Thickness of Top Section = 3mm (Minimum) Bottom Section =4mm (Minimum) Top Dia = 150mm Bottom Dia = 410mm Thickness of Galvanization = Top = 65micron (Min.) Bottom = 85micron (Min.) 31.83 (ii)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .