Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 33 RUSHIKESH INGOLE NAGAR MODERN CO OPERATIVE HOUSING SOCIETY WARDHA ROAD NAGPUR MS 440 005 | NAGPUR | NAGPUR | MAHARASHTRA | 440005 | Admitted-Finance |
| 3 | Admitted-Finance B 248 BASEMENT BLOCK B CHITTARANJAN PARK NEW DELHI 110019 11 SOUTH DELHI DELHI 110019 | SOUTH EAST DELHI | DELHI | 110019 | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance OFFICE E2 MANALI ARCADE NEAR D MART PADMAVATI PUNE SATARA ROAD PUNE MAHARASHTRA 411009 PUNE MAHARASHTRA 411009 | PUNE | MAHARASHTRA | 411009 | Admitted-Finance |
Tender Value
₹5.9 L
Closing Date
23 Sept 2021, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Admin Officer
Aruna Asaf Ali Marg Post Box 10502 New Delhi
Providing Services for Conducting of Structural Analysis, STAAD modelling including Non-Destructive Tests for BH-I and Load Assessment Analysis for BH-III
2021_IUAC_646196_1
IUAC/NIT/18/HAR/2021-22
Open Tender
Civil Works
Works
60 days
IUAC Campus
As per tender documents
5 documents required · 5 mandatory
₹0
Exempted
11 Aug 2023
2 Sept 2021
24 Sept 2021
3 Sept 2021
23 Sept 2021
3 Sept 2021
3 Sept 2021 - 22 Sept 2021
Amount
Providing services for Conducting of Structural Analysis, STAAD modeling including Non-Destructive Tests for BH-I & Load assessment Analysis for BH-III
For BH-I Building (where door opening is proposed) Conducting detailed NDT's including required laboratory tests by following standard procedures/ specifications and instruction from client/ consultant/ expert on concrete wall of size approx. 0.9 meter thickness, slab thickness of building is 1 meter and approx. 8.0 meter height made for radiation shielding for the purpose of door opening. 1. Rebound Hammer test to assess the hardness of concrete and correlation with core compressive strength. Minimum Qty: 15 Nos. 2. Ultrasonic Pulse Velocity (UPV) as per IS-13311 Part-I, measurements on the RCC elements. Minimum qty: 10 Nos. 3. Core cutting test for compressive strength:- Take out the sample of cylindrical concrete core and lab test. Minimum Qty: 3 Nos. 4. Ferro scanning / Rebar Scan: To locate the RCC element in wall and also check the steel bars & its details i.e. spacing, cover & its estimation of diameter. Minimum Qty: 20 Nos. 5. Carbonation: To check thecorrosion in concrete. Minimum qty: 3 Nos. 6. Half-cell Potential Test to confirm the corrosion possibility in RCC members. Minimum Qty: 10 Nos. 7. Preparation of NDT Test Report and Remedial suggestions etc. Note:- The patch plastering/related repair work except for painting will have to be done by the bidder firm at their cost after conducting various tests, if any.
Preparation of detailed STAAD Modeling. Structural mapping and preparation of structural analysis report of whole building / structure (Beam Hall-I) as suggested by consultant/Expert. Overall size of Beam Hall-I is 25 meter x 25 meter x 8 meters. The slab thickness of building is 1 meter approx.
Preparation of all technical details, scope of work, bill of quantities, drawings, all work execution methodology and material specifications etc. as required for making proposed door entry in RCC wall of BH-I.
For BH-III Building (load assesment capacity of Slab/Floor is required) Conducting detailed visual survey of building (internally & Externally) by visual inspection to record observation of distressed part of building, level of deterioration, etc. and conducting following NDT's including required laboratory tests by following standard procedured/ specifications and instruction from client/ consultant/ expert on RCC Floor / slab of BH-III for the purpose of finding load bearing capacity of floor. Overall size Beam Hall-III is 15 meter x 30 meter x 6 meters. 1. Rebound Hammer test to assess the hardness of concrete and correlation with core compressive strength. Minimum Qty: 15 Nos. 2. Ultrasonic Pulse Velocity (UPV) as per IS-13311 Part-I, measurements on the RCC elements. Minimum qty: 10 Nos. 3. Core cutting test for compressive strength:- Take out the sample of cylindrical concrete core and lab test. Minimum Qty: 3 Nos. 4. Ferro scanning / Rebar Scan: To locate the RCC element in wall and also check the steel bars & its details i.e. spacing, cover & its estimation of diameter. Minimum Qty: 20 Nos. 5. Carbonation: To check thecorrosion in concrete. Minimum qty: 3 Nos. 6. Half-cell Potential Test to confirm the corrosion possibility in RCC members. Minimum Qty: 10 Nos. 7. Preparation of NDT Test Report, STAAD Modeling etc and Remedial suggestions etc. Note:- The patch plastering/related repair work except for painting will have to be done by the bidder firm at their cost after conducting various tests, if any.
Preparation of detailed STAAD Modeling, Structural mapping and preparation of structural analysis report of whole building / structure as suggested by consultant/Expert. Overall size of Beam Hall-III is 15 meter x 30 meter x 6 meters.
Preparation of all technical details, scope of work, bill of quantities, drawings, all work execution methodology and material specifications etc for structural safety purposr as required for making required modifications in BH-III floor slab for catering to installed and proposed machine loads. Overall size of Beam Hall-III is 15 meter x 30 meter x 6 meters.
Apensia Consultancy Services LLP
M/s ATOZ NDT SOLUTIONS PVT.LTD
INDIAN CONSULTING ENGINEERS PVT LTD
KBP Civil Engineering Servises
BECQUEREL INDUSTRIES PVT. LTD.
Nimmana Civil Structural Solutions Private Limited
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .