Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.8 LAccepted-AOC | L1 | Accepted-AOC Tender accepted due to lowest and quoted reasonable rates | |
| 2 | L2₹13.3 L+₹2.4 L (22.4%)Rejected-Finance | L2 | Rejected-Finance Higher side quoted amount | |
| 3 | L3₹13.3 L+₹2.5 L (22.7%)Rejected-Finance | L3 | Rejected-Finance Higher side quoted amount | |
| 4 | L4₹14.3 L+₹3.5 L (31.9%)Rejected-Finance | L4 | Rejected-Finance Higher side quoted amount |
| Sl No | Description | Qty | Unit | Vishav Karma Refrigeration and Electric Work L2 | M/S MALHI CONSTRUCTIONS L4 | JAI DURGA CONSTRUCTION CO L1 | M/S SINGHAL ENGINEERS L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | Disconnecting and dismantling/taking down existing BER VT pumping set 40/30 HP 3 phase, 415 volt, 50Hz, located at various water supply installation and shifting to MES store yard complete all as specified and as directed. | 3 | Each Job | 8,499 ₹25,497 | 20,000 ₹60,000 | 3,000 ₹9,000 Lowest | 8,499 ₹25,497 |
| 2.00 | Disconnecting and dismantling/taking down existing BER centrifugal pumping set 7.5 HP located at various water supply installation and shifting to MES store yard complete all as specified and as directed. | 3 | Each Job | 6,499 ₹19,497 | 3,000 ₹9,000 Lowest | 3,000 ₹9,000 Lowest | 6,499 ₹19,497 |
| 3.00 | Supply, fixing and installation submersible pump, electric driven 415 V, TP 40 HP, 6 stage, having discharge 80 Cum/Hours and having head not less than 96 meter complete all as specified and as directed. | 2 | Each | 1,48,499 ₹2,96,998 | 1,90,000 ₹3,80,000 | 1,35,000 ₹2,70,000 Lowest | 1,48,999 ₹2,97,998 |
| 4.00 | Supply, fixing and installation submersible pump, electric driven 415 V, TP 30 HP, 6 stage, having discharge 80 Cum/Hours and having head not less than 96 meter complete all as specified and as directed. | 1 | Each | 1,24,499 ₹1,24,499 Lowest | 1,75,000 ₹1,75,000 | 1,35,000 ₹1,35,000 | 1,24,999 ₹1,24,999 |
| 5.00 | Supply, fixing and installation centrifugal pumping set, electric driven cupled with 415 V, 7.5 HP, 3 phase induction motor 2880 RPM and having head not less than 32 meter complete all as specified and as directed. | 3 | Each | 54,499 ₹1,63,497 Lowest | 70,000 ₹2,10,000 | 75,000 ₹2,25,000 | 54,999 ₹1,64,997 |
| 6.00 | Supply, laying, connecting and testing in replacement submersible copper cable flat type, 1100 volt confirming to IS 694:1990 of size 16 Sqmm, 3 core complete all as specified and as directed. | 135 | RM | 719 ₹97,065 | 700 ₹94,500 | 350 ₹47,250 Lowest | 719 ₹97,065 |
| 7.00 | Supply, laying, connecting and testing in replacement submersible copper cable flat type, 1100 volt confirming to IS 694:1990 of size 6 Sqmm, 3 core complete all as specified and as directed. | 30 | RM | 289 ₹8,670 | 350 ₹10,500 | 250 ₹7,500 Lowest | 289 ₹8,670 |
| 8.00 | S&F in replacement automatic star delta starter with singal phase preventer having relay range 36-60 Amp, coil voltage 380 volt suitable for upto 40 HP 440 volt complete all as specified and as directed. | 2 | Each | 43,999 ₹87,998 | 48,000 ₹96,000 | 35,000 ₹70,000 Lowest | 43,999 ₹87,998 |
| 9.00 | S&F in replacement automatic star delta starter with singal phase preventer having relay range 30-50 Amp, coil voltage 380 volt suitable for upto 30 HP 440 volt complete all as specified and as directed. | 1 | Each | 39,999 ₹39,999 | 40,000 ₹40,000 | 32,000 ₹32,000 Lowest | 39,999 ₹39,999 |
| 10.00 | S & F in replacement automatic DOL Starter with singal phase preventer having relay range 20-32 Amp, coil voltage 360 volt suitable for upto 7.5 HP, 440 Volt complete all as specified and directed. | 3 | Each | 9,999 ₹29,997 | 4,500 ₹13,500 | 3,500 ₹10,500 Lowest | 9,999 ₹29,997 |
Tender Value
Refer Docs
EMD Value
₹32,240
Closing Date
13 Aug 2025, 6:00 pmClosed
GE(WEST)PATHANKOT
GE(WEST)PATHANKOT
SPL REPAIR TO REPLACE OLD UNSV BER PUMP SETS AND PROVN OF SIDE WALL AND ELECTRIC WIRING WORK IN SHED OF NAVDEEP OR INSTITUTE UNDER GE(WEST)PATHANKOT
2025_MES_720538_1
GE/PKT-27/2025-26
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (WEST) PATHANKOT
As per NIT and Tender Documents
9 documents required · 9 mandatory
₹500
GE(WEST)PATHANKOT
₹32,240
12 Sept 2025
15 Jul 2025
15 Aug 2025
15 Jul 2025
13 Aug 2025
29 Jul 2025
Amount
Disconnecting and dismantling/taking down existing BER VT pumping set 40/30 HP 3 phase, 415 volt, 50Hz, located at various water supply installation and shifting to MES store yard complete all as specified and as directed.
Disconnecting and dismantling/taking down existing BER centrifugal pumping set 7.5 HP located at various water supply installation and shifting to MES store yard complete all as specified and as directed.
Supply, fixing and installation submersible pump, electric driven 415 V, TP 40 HP, 6 stage, having discharge 80 Cum/Hours and having head not less than 96 meter complete all as specified and as directed.
Supply, fixing and installation submersible pump, electric driven 415 V, TP 30 HP, 6 stage, having discharge 80 Cum/Hours and having head not less than 96 meter complete all as specified and as directed.
Supply, fixing and installation centrifugal pumping set, electric driven cupled with 415 V, 7.5 HP, 3 phase induction motor 2880 RPM and having head not less than 32 meter complete all as specified and as directed.
Supply, laying, connecting and testing in replacement submersible copper cable flat type, 1100 volt confirming to IS 694:1990 of size 16 Sqmm, 3 core complete all as specified and as directed.
Supply, laying, connecting and testing in replacement submersible copper cable flat type, 1100 volt confirming to IS 694:1990 of size 6 Sqmm, 3 core complete all as specified and as directed.
S&F in replacement automatic star delta starter with singal phase preventer having relay range 36-60 Amp, coil voltage 380 volt suitable for upto 40 HP 440 volt complete all as specified and as directed.
S&F in replacement automatic star delta starter with singal phase preventer having relay range 30-50 Amp, coil voltage 380 volt suitable for upto 30 HP 440 volt complete all as specified and as directed.
S & F in replacement automatic DOL Starter with singal phase preventer having relay range 20-32 Amp, coil voltage 360 volt suitable for upto 7.5 HP, 440 Volt complete all as specified and directed.
S&F in replacement of cast iron sluice valve heavy duty 150 mm dia both side flanged PN-1.6 confirming to IS 14846 (ISI marked) with stainless steel spindle, CI gate with brass ring, non rising type and cast iron wheel, cast iron cap, with 3mm thick neoprene rubber gasket joint including, nuts and bolts complete all as specified and directed.
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
M&L for plain cement concrete 1:3:6, type C-2 (using 40mm graded crushed stone aggregate) , as in foundation filling and mass concrete complete all as specified and directed.
S&F in replacement of non return valve (NRV) heavy duty 150 mm dia both side flanged PN-1.6 confirming to IS 5312 (ISI marked) with gun metal sheet, both ends flanged and drilled, with 3mm thick neoprene rubber gasket joint including, nuts and bolts complete all as specified and directed.
S&F in replacement cast iron pipe with flanged ends/verticaly cast, class-A in any length of size 150mm dia complete all as specified and directed by Engg-in-Charge.
M&L for Cement concrete Type D-2 1:4:8 (using 40 mm graded graded crushed stone aggregate) in foundations, filling and mass-concrete
M&L for brick work with sub class ‘B’ brick, straight or curved on plan exc 6 m mean radius built in cement mortar 1:6 complete all as specified and directed..
M&L for rendering 15mm thick in CM 1:4 including mixing of liquid water proofing compound @2% by weight of cement or as per manufacturer instruction, on fair faces of brick work ,concrete surface of wall, finished surface even and smooth without using extra cement complete all as specified.
M&L for preparation of newly plastered surfaces of wall and applying two coats of Cement Base Paint over and including one coat of alkali resistant priming paint complete all as specified
M&L for Cement Concrete , 1:2:4, type B-1 using 20mm graded crushed stone aggregate as in lintel upto 1.50 m span, cills, steps, seismic and other silmilar bands, plinth courses, sring courses,lacing courses, parapets and railings upt 60 cm in height, copings, kneelers, apex stones, bed plates, water troghs and the like including weathering, slightly rounded or camphered angles and throating, complete all as specified and directed by Engr-in-Charge.
M & L for point wiring for light / fan controlled by one switch with 1.50 sqmm PVC insulated unsheathed multistrand copper conductor FRLS cable in existing PVC concealed conduit terminated in new anodise pressed steel sunken box of approved thickness with ISI marked bakelite laminated sheet fixed with cadmium plated screws and washers for switches and sockets, including 1.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS as earth continuity conductor connected to common earth dolly including, cutting chiseling for concealed boxes, including insulation test of point wiring and making good disturbed surface area and white wash/colour wash to matching with the existing colour complete all as specified .Note: colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellow, Earth- Green).
All as per Srl item No 21 here-in-befor but for 5 pin 5 amps socket outlet or independent board complete all as specified and directed.
All as per Srl item No 21 here-in-befor but for 3 pin 5 amps socket outlet on the same board with other switch complete all as specified and directed.
M & L for point wiring with 2.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS cable in existing PVC concealed conduit terminated in new anodised pressed steel sunken box approved thickness with ISI marked bakelite laminated sheet fixed with cadmium plated screws and washers for switches and sockets, including 2.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS as earth continuity conductor connected to common earth dolly including, cutting chiseling for concealed piping ,including insulation test of point wiring and making good disturbed surface area and white wash/colour wash to matching with the existing colour complete all as specified .Note: colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellow, Earth- Green).
S & F switch piano flush type one way 5 amps SP 240 volts complete all as specified and directed.
S & F switch piano flush type one way 15 amps SP 240 volts complete all as specified and directed.
S & F socket outlet 2 in 1, 3 pin 5 amps flush type 240 volts complete all as specified and directed.
S & F socket outlet 2 in 1, 5 pin, 5 and 15 amps flush type 230 volts complete all as specified and directed.
S & F ceiling fan regulator electronic socket type 5 stage speed variation ISI marked complete all as specified and directed.
S & F ceiling rose 65 x 50mm three terminals complete all as specified and directed.
S & F energy saving decorative LED 20W box type (4 Feet), frame , light fitting extruded aluminium housing provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver complete with all accessories prewired without tube and making connections with 3 core twisted flexible copper cable of suitable size from ceilling rose/PVC connector to light fittings complete all as spd and directed by Engr -in -charge.
S&F & testing ceiling fans complete with blades including fan remote, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) and connecting with flexible copper conductor of suitable sizeand including writing of MES No with black paint complete all as specified and as directed.
S & F sheet metal enclosure MCB distribution board, double door with IP-43 protection single phase 240 volts 8 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases in wall for fixing DB and making good the distributed wall surfaces to match with existing specification complete all as specified and directed.
M & L for MCB SP 240 volts any rating from 6 to 40 amps, 'C' cruve with rupturing capacity 10 KA, including providing thimble for out going cables complete all as specified and directed.
M & L MCB SPN 240 volts any rating from 6 to 40 amps, 'C' cruve with rupturing capacity 10 KA, including providing thimble for out going cables complete all as specified and directed.
S&F LED flood light fitting of 100 watts, energy saving, envirmental friendly, long life, exclusive innovative die-cast aluminium IP-65, with high power LEDs as light source, suitable for highlighting architectural features on existing high mast poles/wall/any position or place on existing/new place and making connection with provision of PVC insulated copper conductor of suitable size complete all as specified and directed by Engineer -in-charge.
S & F sheet metal enclosures distribution boards, double door three phase 415 volts 4 ways vertical TPN DB for comprising three phase four wire copper strip bus bar of appropriate capacity complete all as specified and directed and comprising of the following (a)MCCB FOUR POLE 63 AMPS AC 415 VOLTS 25 KA=01 NO as incoming and 12 nos. MCB SP 40 Amps, C series as outgoing. ( (i) MCCB, MCB and DB should be of same make. (ii) The DB shall be flush fixed ,and making good the disturbed surface matching with existing specifications shall be part of job at no extra cost.(iii)connection of theMCCBs/ MCBs with cable shall be made through appropriate size pin /bottle type thimble -properly crimped.(iv) all the vacant holes of the DB shall be provided with blank plates of appropriate size. (v) double continuous earth wire shall be provided for each three phase DB from earthing mains dolly.
Supply, laying and testing LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 16 sq. mm 2 core complete all as specified
Excavation in trenches, not exceeding 1.5 m wide and not exc 1.5 m in depth for laying of pipes/cable etc and not exceeding 10 sqm on plan etc and getting out in any type of soil, complete all as specified. and directed by Engr-in-Charge.
Excavating in trenches, n exc 1.5m wide and n exc 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5m in depth and getting out in soft/loose soil.
Returning, filling in trenches incl spreading and levelling, watering and well ramming in layers n.exc. 25 cm thick all as specified.
Removal of excavated soil to a distance n.exc. 50 mtr and depositing the same where directed at a level n.exc. 1.5 mtr above starting point complete all as specified
Sand cushioning with fine sand to under ground cables in trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable as specified in clause 19.75 of SSR Part-I complete all as specified and as directed by Engr-in-Charge. Note:-Punned thickness will be measured and paid
M&L for brick covering with width equal to length of brick as mechnical protection to cable with well burnt sub class 'B' bricks laid as directed.
M&L for GI tubing light grade including all fittings 40mm bore for cable protection laid in tranches in road crossing or fixed to wall /pole complete all as specified and directed by Engr-in-Charge.
M & L for earthing complete with galvanised steel earth plate electrode , 600 x600 x 6mm thick burried directly in the ground (earth pit not less than 2.25 mtr deep below ground level)with top edge of the plate not less than 1.5mtr below ground level connected to galvanised iron wire 4mm dia as earth lead by means of bolts, nuts and washers of GI up to test point , GI tubing 15 mm bore light grade protection pipe , GI watering pipe 20mm bore light grade with funnel and wire mesh , charcoal ,salt packed around the earth plate and precast PCC 1:2:4 (Nominal mix ) reinforced with XPM having weight not less than 4 kg /sqm including suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover including earth work in any type of soil , removal of surplus soil to a distance n.exc 50m and connecting , testing on completion complete all as shown on electric plate No 03 of SSR -2009 Part I complete all as specified and directed.(Note: Excavation and earth work is deemed to be included in the rates quoted).
Note:-The accepted amount will be arrived after deducting the Sch of credit i.e. Rs 12,120.00 and any other reduction if any from quoted amount.
Vishav Karma Refrigeration and Electric Work (BID ID -3384650)
M/S SINGHAL ENGINEERS (BID ID -3390813)
M/S MALHI CONSTRUCTIONS (BID ID -3391532)
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .