8646 REPAIRS MAINTENANCE OF INTERNAL ELCTRIFICATION INCLUDING ALL FITTINGS AND FIXTURES, FANS,GEYSERS, COOLING APPLIANCES AT INS KATTABOMMAN, RS(P) SESS PALAYAMKOTTAI UNDER GE TIRUNELVELI
2026_MES_785193_1
GE/TVL/8646/E8 of 2026-27
Open Tender
Civil Works
Item Rate
270 days
VIJAYANARAYANAM
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE Tirunelveli
₹77,000
Yes
19 Aug 2026
19 Aug 2026
11 Sept 2026
19 Aug 2026
9 Sept 2026
2 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Taking down carefully copper/aluminum point wiring (light,fan,socket etc.) complete including fittings such as switch, ceiling rose, light fittings, regulators etc. and making good to the disturbed surface of walls, floors etc. all complete as specified and directed. | 538 | Per point | - | - |
| 2 | Material & Labour for point wiring for one light/ bell/ fan controlled by one number one way switch complete with 1100 V grade FRLSH PVC insulated multistranded copper conductor cable conforming to IS : 694 of size 1.5 Sqmm two runs single core for phase and neutral drawn through and including PVC concealed conduit pipe of suitable size minimum 20mm dia medium grade ISI Marked complete with one run of 1100 V grade FRLSH PVC insulated multistranded copper conductor cable 1.5 Sq mm single core green colour for earth continuity conductor and connecting to common earth dolly including provision of MS sheet pressed sunken box not less than 1.12 mm thick concealed on wall, with 3 mm thick laminated sheet top cover ISI marked for fixing of switches/socket/regulator with screws complete including making good of disturbed surfaces of wall/ceiling/floor in same specification as per existing surrounding surface complete all as specified and directed.
Note : Proper colour code of wiring to be maintained. | 60 | Per point | - | - |
| 3 | All as per item No. 2 here -in -before but for One 3 pin 5 Amps Socket on same board complete all as specified and directed. | 15 | Per point | - | - |
| 4 | All as per item No. 2 above but for One 3 pin 05 Amps socket on independent board complete all as specified and directed. | 50 | Per point | - | - |
| 5 | All as per item No. 2 above but for 15 Amps independent socket with 2.5 sqmm copper conductor complete all as specified and directed. | 30 | Per point | - | - |
| 6 | All as per item No. 2 above but for one light/fan/bell, but in PVC casing caping complete all as specified and directed. | 80 | Per point | - | - |
| 7 | All as per item No. 2 above but for 5 Amps Socket on same board in PVC casing caping complete all as specified and directed. | 15 | Per point | - | - |
| 8 | All as per item No. 2 above but for 5 Amps Socket on independent board in PVC casing caping complete all as specified and directed. | 50 | Per point | - | - |
| 9 | All as per item No. 2 above but for 15 Amps independent socket with 2.5 sqmm copper conductor in PVC casing caping complete all as specified and directed. | 40 | Per point | - | - |
| 10 | Material & Labour for point wiring for one light/ bell/ fan controlled by one number one way switch for 5Amps SSC complete with 1100V grade FRLSH PVC insulated unsheathed multistranded copper conductor cable conforming to IS : 694 of size 1.5 Sqmm two runs single core for phase and neutral drawn through in and including PVC concealed conduit of suitable size (minimum 20mm dia medium grade ISI Marked) complete with one run of 1100V grade FRLSH PVC insulated multistranded copper conductor cable 1.5 Sq mm single core green colour for earth continuity conductor and connecting to common earth dolly including provision of modular type galvanized MS sheet pressed sunken box not less than 1.00 mm thick concealed on wall including fixing of modular frame and cover plate of suitable modules with fixing screws, for fixing of modular type switches / socket t/ Fan regulator etc. complete including making good of disturbed surfaces of wall/ceiling/floor in same specification as per existing surrounding surface complete all as specified and directed.
Note : Proper colour code of wiring to be maintained. | 80 | Per point | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.50 MB
8646TENDERDOCS.pdf
Tender Documents • 0.83 MB
BOQ_879830.xls
BOQ • 1.57 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].