Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.2 LAccepted-AOC | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹40.9 L+₹5.0 L (13.9%)Rejected-Finance | L2 | Rejected-Finance REJECTED BEING OTHER THAN L1 BIDDER | |
| 3 | L3₹41.8 L+₹5.9 L (16.4%)Rejected-Finance ADDITIONAL SECRETARIAT COMPOUND SHILLONG EAST KHASI HILLS MEGHALAYA 793001 | SHILLONG | EAST KHASI HILLS | MEGHALAYA | 793001 | L3 | Rejected-Finance REJECTED BEING OTHER THAN L1 BIDDER | |
| 4 | L4₹61.9 L+₹26.0 L (72.4%)Rejected-Finance | L4 | Rejected-Finance REJECTED BEING OTHER THAN L1 BIDDER |
Tender Value
₹43 L
EMD Value
₹86,000
Closing Date
3 Oct 2024, 6:00 pmClosed
GE SHILLONG
GE SHILLONG SHILLONG PIN 793002
REPAIR/MAINTENANCE OF AIR CONDITIONER, REFRIGERATION AND HEATING PLANTS AND REPAIR/MAINT OF D G SETS AND OTHER MISC SERVICES AT CANTT AREA UNDER GE SHILLONG
2024_MES_666535_2
GE/SHL/TOKEN-36 OF 2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE SHILLONG
ALL AS PER TENDER DOCUMENT
7 documents required · 7 mandatory
₹500
Yes
GE SHILLONG
₹86,000
Yes
8 Nov 2024
5 Sept 2024
5 Oct 2024
5 Sept 2024
3 Oct 2024
19 Sept 2024
Amount
M&L for Maintenance and servicing of standby DG Set complete including draining out of diesel from tank , cleaning the tank thoroughly and refilling the drained out diesel, draining out engine oil from the sump, cleaning the sump thoroughly and refilling the sump with new engine oil to required level, replacing the fuel filter, lubricating oil filter, checking & cleaning air cleaner, changing air cleaner elements, checking coolant level & topping up the same, draining the fuel filter & water separator, filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, replacement of the u/s brass connectors for batteries, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, including M & L for V Belts, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning of DG Set, checking of fuel, oil and water/ coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the DG Set with accessories as prescribed by the manufacturer and testing for satisfactory running of DG set for two hour at connected load and record shall be made in respect of RPM , oil pressure , oil temperature , coolant temperature, voltage , frequency , load current , battery charging , fuel consumption etc complete all as specified and directed. for DG Set of Capacities 10 to 50 KVA. Make of DG Set Kirloskar/Cummins/Ashok Layland /CG/Sudhir NOTE:- (a). Engine oil for refilling will be measured & paid separately. (b). Coolant for make up will be measured & paid separately (c). The Make of Fuel filter , Oil Filter , V belt & component will be as per manufacturer's recommendations and parts and lubricants shall be paid seperately under respective items at supply only rates here-in-after.
Supply only Gasket set.
Supply only Head gasket
Supply only Valve steam seal
Supply only Rear oil seal
Supply only Front oil seal
Supply only Hose pipe set
Supply only Hose clamp set
Supply only Flexible pipe set
Supply only Copper washer set.
Supply only Air filter set.
Supply only Diesel filter .
Supply only Oil filter set.
Supply only Fan belt.
Supply only Solonied switch.
Supply only Oil temperature gauge
Supply only Oil pressure gauge
Supply only Lube oil pump
Supply only Stop Solonied assy
Supply only High Pressure pipe
Supply only Door Lock
All as per Srl Item No.1 here-in-above but DG set of capacity 62.5 to 125 KVA. Make of DG Set Kirlosker/Cummins/Ashok Layland/CG/Sudhir
Supply only Gasket set.
Supply only Head gasket
Supply only Valve steam seal
Supply only Rear oil seal
Supply only Front oil seal
Supply only Hose pipe set
Supply only Hose clamp set
Supply only Flexible pipe set
Supply only Copper washer set.
Supply only Air filter set.
Supply only Diesel filter set.
Supply only Oil filter set.
Supply only Fan belt.
Supply only Solonied switch.
Supply only Oil temperature gauge
Supply only Oil pressure gauge
Supply only Lube oil pump
Supply only Stop Solonied assy
Supply only High Pressure pipe
Supply only Door Lock
All as per Srl Item No.1 here-in-above but DG set of capacity 180 to 200 KVA. Make of DG Set Kirlosker/Cummins/Ashok Layland/CG/Sudhir
Supply only Gasket set.
Supply only Head gasket
Supply only Valve steam seal
Supply only Rear oil seal
Supply only Front oil seal
Supply only Hose pipe set
Supply only Hose clamp set
Supply only Flexible pipe set
Supply only Copper washer set.
Supply only Air filter set.
Supply only Diesel filter set.
Supply only Oil filter set.
Supply only Fan belt.
Supply only Solonied switch.
Supply only Oil temperature gauge
Supply only Oil pressure gauge
Supply only Lube oil pump
Supply only Stop Solonied assy
Supply only High Pressure pipe
Supply only Door Lock
Repair/maintenance of existing control panel of DG set by replacing the connected items such as leads, copper wire, thimble , Analogue Ammeter, Analogue voltmeter, frequency meter etc. along with other minor parts required for carrying out maintenance complete all as directed. Note- Parts of control panel such as Ammeter, Voltmeter and frequency meter shall be measured and paid separately at supply only rates here-in-after.
Supply only Analogue Ammeter Class 1, 5 A, 3 phase.
Supply only Analogue Voltmeter Class 1, 3 Ph.
Supply only Frequancy meter single phase, Class 0.20.
Repair/ over hauling of self starter assembly of any type/make/ model including replacement of bearing bushing, washer, bendix pinion, carbon bush etc complete as required for proper functioning for the following capacities of DG sets complete all as directed. Note: (i) Make of DG Sets shall be as specified against item No 1 here-in-above. (ii) Repair works shall be carried out by authorised agent / dealer of DG Sets.
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 50 KVA
Disconnecting the Exhaust Pipe Line with mufler of DG set from Exhaust Manifold of the Engine and removing the Unserviceable Asbestos Rope from the Exhaust Pipe, Cleaning the Exhaust Pipe and cutting the mufler removing all Carbon Particles Inside including wrapping of existing asbestos rope complete all as directed for the following capacities of DG Sets:
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 50 KVA
Dismantling Radiator assembly from DG set Engine from inside and out side , Cleaning and Washing the Radiators & fins by Compressed Air with Chemical Water, removing all dust, etc. from the Radiator and Filling Coolant, re-assembling the same in Original Position with new gaskets, radiator connecting hoses and clamps complete all as directed by Engr-in-charge, for the following capacities DG Sets:- Note:- (i) Coolant shall be measured and paid seperatly under relevnt items of these schudule. (ii) Asbestos rope shall be measured and paid separately under relevant items of these schedule. (iii) Repair works shall be carried out by authorised agent / dealer of DG Sets. (iv) Make of DG Sets shall be as spesified against item No 1 here-in-before.
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 50 KVA
Disconnecting the fuel tank including Inlet/Outlet Connections of the following capacities of DG sets and cleaning the Tank properly and removing all dusts, mud, etc. and refixing the fuel tank and Inlet/Outlet Pipe connections in orginal position complete all as directed. Note: Repair/ maintenance & servicing shall be carried out through authorized representative of manufacturer of DG Sets.
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 50 KVA
Material and labour for Rewinding of starter armature complete for the following capacities of DG sets With super enamelled copper winding wire including taking out old unserviceable winding :- Note: (i) Make of DG Set shall be as specified against item No 1 here-in-before. (ii) Repair/ maintenance & servicing shall be carried out through authorized representative of manufacturer's of DG Sets.
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 50 KVA
Repair / over hauling of automatic/manual, Governor assembly of any make/type/model complete including calibration and replacement of spare parts as required to make the governor 100 % trouble free complete all as directed by Engr-in-Charge:- Note: (i) Make of DG Set shall be as specified against item No 1 here-in-before. (ii) Cost of spare parts shall deemed to be included in the rate quoted .
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 50 KVA
S&F battery 12 Volts 180 AH including charging etc for proper functioning complete including taking down damage/unserviceble Battery all as specified and directed. Make- Exide/Luminous/Amron/Okaya equivalent make
S&F battery 12 Volts 120 AH including charging etc for proper functioning complete including taking down damage/unserviceble Battery all as specified and directed. Make- Exide/Luminous/Amron/Okaya equivalent make
Repair/ over hauling, servicing of alternator for battery charger of 12 Volt Battery of any make / type, rewinding of armature and field coil including replacement of bearing / bushing etc. and make the alternator 100% serviceable complete all as directed.
S&F MCCB 4 pole 400 Amps, 36 KA, 415 Volts, with thermal magenetic release complete including taking down old unserviceable MCCB all as specified and directed.
S&F MCCB 250 Amps 4 pole, 25 KA, 415 Volts, adjustable thermal & fixed Magnetic setting including taking down old unserviceable MCCB all as specified and directed.
Repair/ servicing of alternator of any make/type/model including grinding/polishing of slip rings assembly cleaning and re-tensioning of carbon bush holder including replacement of carbon bush for the alternators of following DG Sets : Note: (i) Make of DG Set shall be as specified against item No 1 here-in-before. (ii) Cost of spare parts shall deemed to be included in the rate quoted by the bidder.
DG set 125 to 200 KVA
DG set 40 to 82.5 KVA
DG set 10 to 30 KVA
Taking out of defective automatic voltage regulator (AVR) of DG set (alternator side) and supply and fix New automatic voltage regulator (AVR) including necessary connection, testing and cable work etc. complete all as directed for the following capacities of DG Sets :-
DG set 160 to 200 KVA
DG set 30 to 140 KVA
Supply only Engine Oil (20 W 40) (Make- Servo/Castrol /Shell/Valvoline/Gulf/Motul).
Supply only Coolant. (Make- Servo/Castrol /Shell/Valvoline/Gulf/Motul).
Supply only Distilled water for Battery as per sample
Supply and Fix Asbestos rope of required size.
S&F in repairs Battery connection cable of length 1.2 Mtr with solid brass clamp lugs for "+" terminals at one side and copper lug on other side.
S&F in repairs Battery connection cable of length 1.2 Mtr with solid brass clamp lugs for "-" terminals at one side and copper lug on other side.
M&L Earthing with galvanized steel earth plate electrode of size 600 mm x 600 mm x 6.00 mm buried directly in ground connected to galvanized earth lead strip of size 32 mm x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel including 40mm dia medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe light grade 20mm dia, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC type C1 (1:3:6, using 20mm graded crushed stone aggregates) 50mm thick precast RCC type B1, (1:2:4, using 20mm graded crushed stone aggregates) pit cover reinforced with 8mm dia deformed bar and suitable handle made of 10mm dia round bar including galvanised strip of size 32mm x 6mm for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spoils to a distance n.exc 50m and necessary connection and testing complete all as shown in electrical plate No 3 of SSR Part-I, 2009 and all as specified and directed including taking down old unserviceable earth pit and accessories. Note : GI Strip upto 7.5m length shall be deemed to included in the cost of above item. Quantity of GI earth strip required over and above shall be measured under relevant item here-in-after.
S&F GI strip 32 x 6 mm as eath continuity conductor or main earthing lead buried in ground or drawn through pipes or fixed to wall or poles or any other situation for loop earthing etc including dismantling old unserviceable strip complete all as specified and directed.
Excavation In trenches not exceeding 1.5m wide and not exceeding 1.5m deep and getting out in soft/loose soil for laying/removing of UG cables complete all as specified and directed.
Returning, filling in, including, spreading, levelling, watering and wall ramming, in layers not exceeding 25Cm in soil obtained from excavation complete all as specified and directed.
Removal of surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above starting point complete all as specified and directed.
Supply and laying dry river sand filling for cable protection with a layer of 8cm deep before laying cable and 15cm covering above the top edge of cable after laying complete all as specified and as directed. (Note: Punned thickness shall be measured).
M&L for sub class 'B' bricks locally available best quality and laid dry, width wise across the line of cable in trenches for protection of underground cable complete all as specified and as directed.
S&F XLPE insulated, screened, PVC bedded, galvanized steel strip of wire armoured, electric power cables (heavy duty) 1100 Volts grade, with stranded aluminium conductor of size 150 Sqmm 3.5 core, including taking out old unserviceable cablecomplete all as specified and as directed.
S&F XLPE insulated, screened, PVC bedded, galvanized steel strip of wire armoured, electric power cables (heavy duty) 1100 Volts grade, with stranded aluminium conductor of size 120 Sqmm 3.5 core, including taking out old unserviceable cablecomplete all as specified and as directed.
S&F XLPE insulated, screened, PVC bedded, galvanized steel strip of wire armoured, electric power cables (heavy duty) 1100 Volts grade, with stranded aluminium conductor of size 95 Sqmm 3.5 core, including taking out old unserviceable cablecomplete all as specified and as directed.
S&F XLPE insulated, screened, PVC bedded, galvanized steel strip of wire armoured, electric power cables (heavy duty) 1100 Volts grade, with stranded aluminium conductor of size 70 Sqmm 3.5 core, including taking out old unserviceable cablecomplete all as specified and as directed.
S&F XLPE insulated, screened, PVC bedded, galvanized steel strip of wire armoured, electric power cables (heavy duty) 1100 Volts grade, with stranded aluminium conductor of size 50 Sqmm 3.5 core, including taking out old unserviceable cablecomplete all as specified and as directed.
S&F Changeover switch 400 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one complete all as specified and directed.
S&F Changeover switch 250 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one complete all as specified and directed.
S&F Changeover switch 160 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one complete all as specified and directed.
S&F Changeover switch 630 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one complete all as specified and directed.
S&F MCCB, 3 pole, 415 Volts,160 Amps, 36 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one complete all as specified and dreicted.
S&F MCCB, 3 pole, 415 Volts,125 Amps, 16 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one complete all as specified and dreicted.
S&F MCCB, 3 pole, 415 Volts,100 Amps, 16 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one complete all as specified and dreicted.
S&F MCCB, 3 pole, 415 Volts, 63 Amps, 16 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one complete all as specified and directed
M&L PCC 1:2:4 type B2 using 40 mm graded crushed stone aggregate as in floor, finished even and smooth without using extra cement including demolition of old concrete floor complete all as specified and as directed.
Supply only First aid Kit with all accessories including necessary medicines made of fibre sheet of size (LWH) 45cm x 30 cm x 15cm.
Supply and laying insulated Electrical matting class 1, proof voltage tested upto 10 KV, 2mm thick ness of size 1.00 mtr (wide) with one side fabric and other side plain finish as per IEC 61111 including taking out old unserviceable rubber matting. Make:- Raychem or equivalent as approved by Accepting officer.
Shifting of DG Set from one location to another location by removing of cable cannection, earthings and lifting up with the help of recory van and installing at new location complete with all T&Ps, Labours and making connection, earthing connection, testing after installation all as directed. Note- Damaged caused to DG Set, if any, during transit, will be make good by the contractor without any cost to the department.
S&F in repair of multi function meter for measuring line voltage,current frequency, power factor suitable for DG set of suitable capacity complete all as specified and directed.
M&L for Caliberation of FIP of 10 to 40 KVA DG Set with removal of plungers, delivery valve, O ring, diaphram springs and seal washers etc including caliberation of injector holders with renewal of nozzles complete all as Specified and directed. Make of DG Set: Kirlosker/Cummmins/Ashok Layland/CG/Sudhir
M&L for Caliberation of FIP of 45/62.5/63 KVA DG Set with removal of plungers, delivery valve, O ring, diaphram springs and seal washers etc including caliberation of injector holders with renewal of nozzles complete all as Specified and directed. Make of DG Set: Kirlosker/Cummmins/Ashok Layland/CG/Sudhir
M&L for Caliberation of FIP of 82.5/125 KVA DG Set with removal of plungers, delivery valve, O ring, diaphram springs and seal washers etc including caliberation of injector holders with renewal of nozzles complete all as Specified and directed. Make of DG Set: Kirlosker/Cummmins/Ashok Layland/CG/Sudhir
M&L for Caliberation of FIP of 180/200 KVA DG Set with removal of plungers, delivery valve, O ring, diaphram springs and seal washers etc including caliberation of injector holders with renewal of nozzles complete all as Specified and directed. Make of DG Set: Kirlosker/Cummmins/Ashok Layland/CG/Sudhir
GENERAL NOTES (APPLICABLE TO SL ITEM NOS. 54 to 113): The Quoted rates shall to be deemeed to include for the following :- (a) The work is required to be carried out for repair/maint of cooling appliances in the entire Mil Stn Shillong (HV, SE Falls and Cantt Area) , hence complaints of the user equipments (Refrigerators/DF/ACs/voltage stabilizers) will be handed over on daily basis (if received) for different units, locations and repairs to be carried out on the same day or next day or as directed by Engr-in-Charge. (b) The contractor shall depute adequate AC mechanic and helper (As per complaint) with all connected tools on daily basis (if required) with suitable vehicle & T&P arrangement for repairs and to attend the complaint in various units under AOR of GE Shillong and manage all spares included in this CA in advance or as directed by Engr-in-Charge. (c) A recovery of Rs 500/- shall be levied and recovered for non attending the complaint within 48 hrs.
S&F in repair sealed compressor rotary type of capacity 1.5TR suitable for window/split type air conditioner complete all as specified and directed. (Make:- Carrier / Voltas/ LG/ Bluestar/ Hitachi)
S&F in repair sealed compressor scroll type of capacity 2/1.5TR suitable for inverter type split type air conditioner complete all as specified and directed. (Make:- Carrier / Voltas/ LG/ Bluestar/ Hitachi)
S&F Relay, box type for 1.5/2.0 Ton capacity Split/Window type Ac as in repairs complete all as specified and directed. (Make: DANFOSS/RANUTAL/ORSIO/INDFOSS).
S&F Capacitor Running type, 45/55 mfd for window /Split type Ac 1.5/2.0 ton capacity as in repairs complete all as specified and directed. (Make: CIVCON/SARDA/UNIVERSAL/HAVELLS)
S&F Starting capacitor, 80-120 mfd for window/Split type air conditioner 1.5/2.0 ton capacity as in repairs complete all as specified and directed. (Make: CIVCON/ SARDA/ UNIVERSAL/ HAVELLS).
S&F Fan blade with blower motor for window/split type AC 1.5/2.0 ton capacity as in repairs complete all as specified and directed. (Make:LG/Voltas)
S&F Blower motor of suitable for 1.5/2.0 TR capacity Window/Split Type AC all as specified and directed as in repairs. (Make: NGEF/Kivon / Crompton Greaves / LG/Voltas/Carrier).
S&F Rotary type knob for Window type AC as in repairs complete all as specified and directed (Make:LG/Voltas/Carrier/Carrier)
S&F Roller assembly for Split type AC as in repairs complete all as specified and directed.
S&F Toggle switch for window/split type AC as in repairs complete all as specified and directed. (Make: KAYCEE/L&T/Havells)
S&F Flaring nut for Split Type AC of size 1/2"/1/4"/5/8" as in repairs complete all as specified and directed.
S&F Air filter suitable for 1.5/2.0 TR capacity Window/Split Type AC as in repairs complete all as specified and directed. (Make: LG/Voltas/Carrier)
S&F Over load protector suitable for 1.5/2.0 TR Window/Split Type AC as in repairs complete all as specified and directed. (Make: Siemns/ Crompton Greaves/Legrand/L&T).
Dismantling the outdoor and indoor unit of Split type air conditioner, 1.5 ton capacity after removing refrigerant pipe connection, electric wire connection including refixing in the same at new location/ existing position after following repairs and complete servicing of machine complete all as directed by Engr-in-Charge :- (a) Repairs of the suction and discharge tube and cooling coil and replacement of heat resistive thermocol, tube for gas & liquid line. (b) De-scaling the complete refrigeration system with carbon tetra chloride solution, replacement of defective capillary tube, strainer and dryer unit of required size assembling the system, leakage test of the system by applying approximate head and vacuum up to (-) 75 Cm column of mercury. (c) Recharging of gas with suitable refrigerant as required and testing the cooling effect satisfactorily on full load after re-installation of air condition complete all as directed. Note : Refrigerant Gas shall be measured and paid separately as 'Supply only' items.
Supply only refrigerant gas suitable for refrigerator, deep freezer,Window ,Split type Acs etc. complete including testing the cooling effect satisfactorily on full load all as specified and directed. Make: Moto: R22(AC),134A(Deep freezer), R12 (Refrigerator), R-410A (AC) & R-32
S&F Panel Circuit Board (PCB) for 1.5 /2.0 TR Window/Split type AC as in repairs complete specified and directed. (Make: LG/Samsung/Voltas)
S&F Remote circuit complete with remote device for 1.5/2.0 TR Window/Split type AC as in repairs complete all as specified and directed. (Make: LG/Samsung/Voltas)
S&F PVC insulated & sheathed copper conductor 1100 volts grade 3 core, 4 Sqmm ISI marked for ACs & Refrigerators including taking down old unserviceable copper conductor specified and directed.
M&L for Servicing of 1.5TR split/window type AC of make:- LG/ Voltas/ Carrier/ Amtrex after removing electric wire connection & cleaning of Cooling coil, condenrer coil, Filter, replacement of any unserviceable minor parts such as relay, capacitor , kobs etc. complete all as specified and directed. Note : Cost of minor spare parts shall deemed to be included in the rate quoted by the tenderer.
S&F Sheet metal enclosures with socket plug top & MCB single pole & neutral enclosure with a two pin & earth plug and socket complete with one single pole and neutral MCB -240 Volt- 20 Amps, 'C' series including taking down old unserviceable plug and socket.
M & L Sub main wiring with two runs of 6 Sqmm FR grade, (ISI mark) PVC insulated, multi stranded, unsheathed, copper conductor and one run of, PVC insulated multistranded FR, grade (ISI mark) unsheathed copper conductor of size 6.0 Sqmm as earth lead including PVC casing capping of suitable size including taking down old unservicable submain wiring complete all as specified and directed. Note: Two runs of 6 Sqmm, one run of earth wire of size 6.0 Sqmm and one run of PVC casing capping shall be measured as one unit.
S&F Condenser unit complete for 1.5/2.0 TR Window/Split type AC as in repairs complete all as specified and directed. (Make: LG/Voltas/Carrier)
S&F Evaporator unit complete for 1.5/2.0 TR Window/Split type AC as in repairs complete all as specified and directed. (Make: LG/Voltas/Carrier)
S&F Capillary tube and strainner with filter complete for 1.5/2.0 TR window/split type AC as in repairs.
M&L Cooling coil complete with aluminium deep freezer chamber for refrigerator of any capacity as in repairs. (Make: Voltas/Blue Star)
Dismantling of sealed compressor unit after removing all electrical connection and cutting of refrigerant pipe from refrigerators of 300/310/315/410 Ltrs capacity including de-scaling the refrigeration system with carbon tetra chloride solution, replacement of defective capillary tube, strainer and dryer filter of required size, re-assembling the system including recharging of suitable refrigerant as required, including testing of the complete system complete all as directed by Engr-in-Charge. Note for item Nos 79 to 79.02:- refrigerent gas shall be measured and paid separately under relevant items.
All as per item No 79 above but for refrigerator 165/180 ltrs capacity.
All as per item No 79 above but for deep freezer of capacity 320/220 ltrs.
S&F Relay for refrigerator/deep freezer of various capacities as in repairs complete all as specified and directed. (Make : Siemens/LG /Carrier/Bluestar).
S&F Sealed compressor for refrigerator of capacity 180 ltrs, including sealing of the compressor with welding as in repairs complete all as specified and directed. (Make: LG/ Voltas/ CARRIER)
S&F Sealed compressor for refrigerator / deep freezers of capacity 286/300/315/345 ltrs, including sealing of the compressor with welding as in repairs complete all as specified and directed. (Make: SRIRAM/ KIRLOSKAR / CARRIER).
S&F Thermostat switch suitable for refrigerator/deep freezer of any capacity as in repairs complete all as specified and directed. (Make: Blue Star/Voltas/Carrier)
S&F Cabinet lamp including lamp holder and push switch including connection with electric wires as in repairs complete all as specified and directed.
M&L Door rubber gasket complete for refrigerator up to 320 Ltrs capacity as in repairs.
M&L Defrost timer for refrigerator/deep freezer any capacity as in repairs complete all as specified and directed. (Make: Blue Star/Voltas/Godrej/Samsung)
M&L Bi-metal for refrigerator/deep freezer any capacity as in repairs all as specified and directed.
S&F Cooling coil with aluminium chamber for Freezer as in repairs complete of Refrigerator upto 320 Ltrs complete
S&F Defrost heater suitable for Refrigerator of any capacity as in repairs complete.
S&F Copper suction and discharge pipe icluding insulation suitable for AC 1.5/2.0 Ton of any dia as in repairs complete all as specified and directed.
S&F in repair of heating element of capacity 1.5/2 KW for heating system complete all as specified and directed.
S&F in repair of thermostat for heating system complete all as specified and directed.
S&F in repair of temperature gauge for heating system complete all as specified and directed.
S&F in repair of pre air filter of size 600x600mm for heating system complete all as specified and directed.
S&F in repair of pre air filter of size 300x600mm for heating system complete all as specified and directed.
S&F in repair of fine air filter of size 600x600mm for heating system complete all as specified and directed.
S&F in repair of fine air filter of size 300x600mm for heating system complete all as specified and directed.
S&F in repair of power contactor 3 pole 440 volts 32 Amps complete all as specified and directed. (Make :- L&T / Siemens / Legrand)
M&L Strip heater of capacity 3 KW for heating plant as in repairs complete all as specified and directed.
S&F Pan type heating element of 3 KW capacity for heating plant as in repairs complete all as specified and directed.
M&L PVC drain pipe 20/25mm bore, fixed on wall/roof/floor with necessary clamp/hook complete as in repair.
S&F in repair taking down transformer of voltage stabilizer 4/5 KVA and rewinding the same with super enamelled copper wire as per existing gauge and varnishing complete with 'E' class varnish, including and reassembling and fixing in position complete all as specified & directed.
S&F in repair, capacitor 10 MFD for fan motor of refrigerator complete all as specified & directed. (Make-Epcos/Bajaj/ Havells/CG)
S&F in repair, capacitor 15 MFD for fan motor of refrigerator complete all as specified & directed. (Make-Epcos/Bajaj/ Havells/CG)
S&F in repair blower fan motor of capacity 1/30 or 1/20 HP copper wound suitable for split type AC 1.5 TR, AC/DC complete including testing commissioning complete all as specified & directed. (Make- As per existing make and model)
S&F in repair, condensor fan motor for deep freezer of any make and capacity complete all as specified & directed. (Make- As per existing make and model)
S&F in repair, capillary tube suitable for any make & capacity deep freezer/refrigerator complete all as specified & directed. (Make- As per existing make and model)
S&F in repair, plug top 3 pin 5 amps, 230 volts (ISI marked) complete all as specified & directed. (Make C&S/ Anchor/Legrand or equivalent)
S&F in repair, plug top 3 pin 15 amps, 230 volts (ISI marked) complete all as specified & directed. (Make C&S/ Anchore/Legrand or equivalent)
S&F in repairs thermostat suitable for refrigerator 165 to 320 litres capacity complete all as specified & directed. (Make-Theeta/Racold/Tasspass)
S&F in repairs cooling coil suitable for split type AC of capacity 1.5/2 TR complete all as specified & directed. (Make- As per existing make and model)
S&F in repairs main PCB suitable to inverter split type AC 1.5/2 TR complete all as specified & directed (Make- As per existing make and model)
S&F 4 cylinder oxygen manifold with tailpipes & NRVs complete all as specified & directed. Make - NSP India Medical Services
Servicing of the fully automatic control panel for oxygen (of major manifild) complete all as specified & directed.
Servicing of the control panel for oxygen emergency system complete all as specified & directed.
Servicing of the oxygen outlets points complete all as specified & directed.
Servicing of oxygen flowmeter complete all as specified & directed.
S&F 12mm isolation valve on each downdrop connecting to oxygen gas outlets complete all as specified & directed.
S&F of oxygen flowmeter make - NSP India Medical Services complete all as specified & directed.
AMARDEEP KUMAR THAKUR (BID ID -3114763)
SUNITA DEVI (BID ID -3114653)
German Syiemlieh (BID ID -3115707)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .