| 3 | L3₹34.6 L+₹2.1 L (6.55%)Rejected-Finance OFFICE NO 101 MALAN PLAZA NEXT TO ESSAR PETROL PUMP NEAR GODAMBLE CORNER RAHATNI PIMPRI DP ROAD RAHATANI PUNE 411 017 | PUNE | PUNE | MAHARASHTRA | 411017 | L3 | Rejected-Finance Not lowest bidder |
Tender Value
₹44.6 L
EMD Value
₹89,200
Closing Date
19 Feb 2020, 6:00 pmClosed
GE CENTRAL KIRKEE
GE CENTRAL KIRKEE RANGE HILLS ROAD KIRKEE PUNE 411003
REPAIR REWIRING AND MAINT OF CERTAIN INTERNAL WIRING DISTRIBUTION BOARDS LED HIGH BAY LIGHTS AND CONNECTED REPAIR AT 512 ABWS CAFVD A PARK ARSENAL B PARK AND OTHER MISC BUILDING UNDER AGE EM II OF GE C KIRKEE
2019_MES_296826_2
8285/E8 OF 2019-2020
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
KIRKEE
AS PER NIT
7 documents required · 7 mandatory
₹500
Yes
GE CENTRAL KIRKEE
₹89,200
Yes
6 Mar 2020
8 Feb 2020
20 Feb 2020
8 Feb 2020
19 Feb 2020
8 Feb 2020
Amount
Taking down carefully existing unserviceable aluminium / copper point wiring of any description & in any position with and including existing steel conduit / PVC Conduit / Casing capping fixed on surface/wall/angle/guarder and including all fitting, accessories & fixtures such as switches, ceiling roses, pendants, regulators, sockets, etc including sunken boxes/junction boxes and making good the disturbed surface of walls, floors, ceiling etc to match with the existing surfaces complete all as specified and directed.
M&L for point wiring in non metallic white coloured PVC casing & capping of suitable size but not less than 20mm including all fittings such as elbow, bends, junction boxes, saddles, etc. on surface with and including ISI marked two runs of PVC insulated unsheathed multi stranded copper conductor cable (FRLSH) 1.5 sqmm nominal cross sectional area, 1100 volts grade and including one run of 1.5 sqmm (green colour) ISI marked PVC insulated unsheathed multi stranded (FRLSH) copper conductor cable as earth wire to be terminated in and incl PVC rectangular block of suitable size for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover for one light point or one fan point controlled by one switch including making good the disturbed wall and painting the same with matching to existing wall all as specified and directed by Engineer in charge.
All as per Srl item No 2 above but One bell/buzzer point controlled by one push button on the same board with other switches or independent with cables1.5 sq.mm. Size.
All as per Ser item No 2 above but point wiring for 5 pin socket outlet, 5 Amps on same board with other switches.
All as per Ser item No 2 above but point wiring for 5 pin socket outlet, 5 Amps on independent board.
All as per Ser item No 2 above but point wiring for one five pin socket outlet, 15 Amps & 5 Amp on independent board using 2.5 sqmm two run and one run 2.5 sqmm (nominal area) stranded copper conductor cable.
Material and labour for point wiring for one light point or one fan point controlled by one switch in and including stove enamelled steel conduit with and including all steel enamelled fittings such as elbow bends, junction boxes, supporting clamps for proper fixing arrangements made out from 25x3mm flat iron including nuts, bolts and bending to shape etc. of appropriate size but not less than 20mm on surface with two run of PVC insulated unsheathed multi stranded copper conductor cable (FRLSH) 1.5 Sqmm nominal cross sectional area 1100 volts grade and including one run of 1.5 sqmm (green colour) PVC insulated unsheathed multi stranded (FRLSH) copper conductor cable as earth wire incl. suitable size sunken type Galvanised pressed sheet steel 1.6 mm thick terminal box of suitable size for mounting switches, sockets etc. and wiring to be terminated in pressed steel sunken boxes with and including all accessories and making good the disturbed wall and painting the same with matching colour of the existing wall, all as specified and directed.
All as per Srl item No 7 above but point wiring for 5 pin socket outlet, 5 Amps on same board with other switches.
All as per Srl item No 7 above but point wiring for 5 pin socket outlet, 5 Amps on independent board.
All a s per Srl item No 7 above but point wiring for one five pin socket outlet, 15 Amps & 5 Amp (independent) with using 2.5 sqmm two run and one run 2.5 sqmm (nominal area) stranded copper conductor. Note for Item Nos 1 to 10: The contractor should make proper safety arrangements for working at various locations and at heights in industrial sheds. Misc items required for completion of job is deemed to be included in the rates quoted.
Supplying & fixing switch flush type, 5 Amps, single pole, one way , 230 volts AC circuit complete all as specified & directed.
Supplying & fixing switch flush type, 5 Amps, Bell push , flush type , 230 volts AC circuit complete all as specified & directed.
Supplying & fixing Socket outlet 3 pin, 5A, flush type, multipurpose, 230 volts AC circuit complete all as specified & directed.
Supplying & fixing switch flush type, 15 Amps, single pole, one way , 230 volts AC circuit complete all as specified & directed.
Supplying & fixing Socket outlet 2 in 1, 3 pin, 5 and 15 amp flush type , flush type, 230 volts AC circuit complete all as specified & directed.
Supplying & fixing Ding Dong call bell AC 230 Volts single pole to be fixed on surface complete all as specified & directed.
Supplying & fixing ceiling rose PVC/polycarbonate, isolated body, three terminals, complete all as specified & directed.
Supply and fixing Lamp Holder white PVC/ Polycarbonate type with back plate suitable for batten fitting with and including S&F LED retrofit white lamp 9 watt prewired 230 volts supply complete all as specified & directed.
Supply and fixing Stepped type electronic fan regulator flush type suitable for ceiling fans, prewired 230 volts AC 50Hz supply 100Watt complete all as specified & directed.
Supply, fixing, connecting and testing in replacement Industrial Earth Plug & socket with sheet metal enclosure electric driven single phase including S&F MCB 'C' series SP 20 Amps and supplied with neutral links complete all as specified and directed.
S&F in replacement of PVC insulated, FR PVC round sheathed three core flexible copper conductor cable of size 1.0 sqmm including connecting the same to the fan/equipment and to the existing ceiling rose all as specified and approved by Engr-in-Charge. Make - Havells/Polycab/Finolex.
Dismantling and Taking out old unserviceable copper/aluminium sub main wiring/Unarmoured cable (used as Sub main wiring) from any height of any Size and Core with all connecting accessories including conduit or casing capping and including making good to the disturbed wall and painting the same with matching paint as of existing wall all as specified and directed by Engineer in charge.
Material & Labour for Sub main wiring at any height with 2 single core PVC insulated, multi stranded copper conductor cable (FRLSH), unsheathed, 2.5 sqmm, 1100 volt grade drawn through and including New suitable size PVC non metallic conduit and including one single core PVC insulated multi stranded unsheathed copper conductor cable, 2.5 sqmm, ISI marked, FRLSH type in green colour as continuous earth wire including all accessories and fixing arrangements, supporting clamps, bends, sockets and connecting items etc. all as specified and directed. Note - (a). Two runs of 2.5 Sqmm wiring cable and one run of 2.5 sqmm earth continuity wire with steel conduit shall be measured as as one length.
Material and labour for Sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through and including New PVC non metallic conduit including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 4.00 sqmm, 1100 Volts grade, ISI marked, as earth continuity wire all as specified and directed by Engineer in charge. (Note:- (i) Two runs of cables & continuous earth wire in new PVC casing and capping / PVC non metallic conduit will be measured as one length of sub main wiring).
Material and labour for Sub main wiring at any height and surface with and including four single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 6.0 Sqmm, 1100 volts grade, drawn through and including New PVC non metallic conduit including connected accessories and two single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 6.0 sqmm, 1100 Volts grade, ISI marked, as earth continuity wire all as specified and directed by Engineer in charge. (Note:- (i) Four runs of cables & continuous earth wire in new PVC casing and capping / PVC non metallic conduit will be measured as one length of sub main wiring).
Material and labour for Sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through and including New metallic/ steel conduit including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 4.00 sqmm, 1100 Volts grade, ISI marked, as earth continuity wire all as specified and directed by Engineer in charge. (Note:- (i) Two runs of cables & continuous earth wire in new PVC casing and capping / PVC non metallic conduit will be measured as one length of sub main wiring).
Material and labour for Sub main wiring at any height and surface with and including four single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 6.0 Sqmm, 1100 volts grade, drawn through and including New metallic/steel conduit including connected accessories and two single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 6.0 sqmm, 1100 Volts grade, ISI marked, as earth continuity wire all as specified and directed by Engineer in charge. (Note:- (i) Four runs of cables & continuous earth wire in new PVC casing and capping / PVC non metallic conduit will be measured as one length of sub main wiring).
Material & Labour for Sub main wiring at any height with 2 single core PVC insulated, multi stranded copper conductor cable (FRLSH), unsheathed, 2.5 sqmm, 1100 volt grade conforming to IS drawn through and including New suitable size steel conduit and including one single core PVC insulated multi stranded unsheathed copper conductor cable, 2.5 sqmm,, FRLSH type green in colour as continuous earth wire including all accessories and fixing arrangements, supporting clamps, bends, sockets and connecting items etc. all as specified and directed. Note - (a). Two runs of cables & continuous earth wire in new steel metallic conduit will be measured as one length of sub main wiring).
Dismantling and drawing out old unserviceable Sub Main Aluminium/copper wiring from Existing Steel/PVC Conduit of any size and any type from any height with all connecting accessories (excluding conduit or casing capping) and making good the disturbed wall and painting the same with matching to existing wall all as specified and directed by Engineer in charge.
Material and labour Sub main wiring at any height including using two single core PVC insulated copper conductor cable (FRLSH) of size 1.5 sqmm 1100 volt grade conforming to IS drawn through existing Steel/ PVC conduit including 1.5 sqmm. PVC multi stranded copper conductor cable (FRLSH) green in colour for continuous earthing all as specified and directed. Note - (a). Two runs of 1.5 Sqmm cable and one run of earth continuity wire shall be measured as one length.
Material and labour Sub main wiring at any height including using 2 single core PVC insulated copper conductor cable (FRLSH) of size 2.5 sqmm 1100 volt grade drawn through existing Steel/ PVC conduit including 2.5 sqmm. PVC multi stranded copper conductor cable (FRLSH) in green colour for continuous earthing all as specified and directed. Note - (a). Two runs of 2.5 Sqmm cable and one run of earth continuity wire shall be measured as one length.
Material and Labour for Sub main wiring at any height with 2 single core PVC insulated copper conductor cable (FRLSH) of size 4 sqmm 1100 volt grade drawn through Existing Steel / PVC conduit including 4.0 sqmm PVC multi stranded copper conductor cable (FRLSH) in green colour for continuous earthing all as specified and directed. Note - (a). Two runs of 4 Sqmm and one run of earth continuity wire shall be measured as one length.
Material and Labour for Sub main wiring at any height with four single core PVC insulated copper conductor cable (FRLSH) of size 6 sqmm 1100 volt grade conforming to IS drawn through Existing Steel / PVC conduit including two single core 6.0 sqmm PVC multi stranded copper conductor cable (FRLSH) green in colour for continuous earthing all as specified and directed. Note - (a). Four runs of 6 Sqmm wiring cable and two runs of earth continuity wire shall be measured as one length.
Disconnecting and taking down old existing damaged metallic rigid steel conduit of any size and any type from any height with all fittings complete.
Supply & fixing hot galvanised rigid steel conduit 25 mm dia, light grade, at any height with and including of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks, screws, clips, plugs, clamps etc. for securing cables, battens, conduits etc. to walls, steel joists etc. complete to be fixed on wall/ceiling/MS angles all as directed by Engr-in-Charge. Make - Jindal/Kalinga/ BEC.
Supply & fixing hot galvanised rigid steel conduit 20 mm dia, light grade, at any height with and incld. of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks, screws, clips, plugs, clamps etc. for securing cables, battens, conduits etc. to walls, steel joists etc. complete to be fixed on wall/ceiling/MS angles all as directed by Engr-in-Charge. Make - Jindal/Kalinga/ BEC. NOTE for item NO 35 & 36 -(i) Stove enamelled black steel conduit only will be measured and paid under relevant items of this schedule. (ii) Quoted rate is deemed to be inclusive of conduit fittings and bell mouthed threaded sockets.complete all as specified & directed. (iii) Quoted rate is deemed to be inclusive any misc materials required for fixing new luminaries. Note for Item Nos 22 to 36: The contractor should make proper safety arrangements for working at various locations and at heights in industrial sheds. Misc items required for completion of job is deemed to be included in the rates quoted.
M & L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending colt or hot, drilling holes for bolts, at any height, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint for mounting Air Circulator / Exhaust Fan / Ceiling Fan for fixing arrangements complete.
Dismantling and Taking down unserviceable existing light fittings 1X 40 Watt / 2X 40 Watt/ 70 watt security lights of any size and capacity from any location/height after disconnecting of electrical connection complete including all connected accessories all as directed by Engr-in-Charge.
Supplying, fixing, connecting up to existing/new ceiling rose and testing industrial box type batten LED tube light fitting suitable for and including 1x18 Watt 4 feet white colour tube lamp with polycarbonate/Acrylic diffuser more than 85%efficiency of light with LED lamp efficiency as 100 Lum/W THD ≤15% with operating voltage range 100-300V, driver efficiency >85%, surge voltage withstand 2.5 KV , power factor ≥0.9 including connecting with 23/0.0076 copper conductor flexible twisted three core cable including all accessories for fixing the light fitting to steel trusses / false ceiling suspended by 2 nos. Ø19/20 mm rigid stove enamelled black steel conduit with bell mouth threaded sockets or with chains at a distance of 700mm complete all as specified & directed including dismantling of old fittings. Make Wipro/CG/Phillips/Bajaj
Supplying, fixing, connecting up to existing/new ceiling rose and testing industrial box type batten LED tube light fitting suitable for and including 2x18 Watt 4 feet white colour tube lamp with polycarbonate/Acrylic diffuser more than 85%efficiency of light with LED lamp efficiency as 100 Lum/W THD ≤15% with operating voltage range 100-300V, driver efficiency >85%, surge voltage withstand 2.5 KV , power factor ≥0.9 including connecting with 23/0.0076 copper conductor flexible twisted three core cable including all accessories for fixing the light fitting to steel trusses / false ceiling suspended by 2 nos. Ø19/20 mm rigid stove enamelled black steel conduit with bell mouth threaded sockets or with chains at a distance of 700mm complete all as specified & directed including dismantling of old fittings. Make Wipro/CG/Phillips/Bajaj
Supplying, fixing, connecting in at any height up to existing/new ceiling rose and testing LED luminaries made up with 20 W LED light source in integral module with polycarbonate/Acrylic diffuser more than 85% efficiency of light with LED lamp efficay as 100 Lum/W THD ≤15% with operating voltage range 100-300V, driver efficiency >85%, surge voltage withstand 2.5 KV , power factor ≥0.9, and connecting with 23/0.0076 copper conductor flexible twisted three/ two core cable fittings connection complete all as specified & directed all Make Bajaj /Havells/Wipro/CG/Phillips.
Supplying & fixing surface/recess mounting LED light fittings / luminaries Milky Way 2'X2' IP 20 Rating 36 watt suitable for surface mounting and false ceiling as per requirement with SMD LED Chip as per LM 80/IS16106 as light source and rated operating voltage of 140 to 280V, Total Harmonics Distortion ( ≤ 20% for upto 20W) ( ≤ 10% for above 20W), PF ≥0.90 complete with all accessories , connecting the same to ceiling rose with using copper conductor 23/0.0076 flexible twisted three/ two core cable including all accessories and fixing arrangements for fixing the light fitting to/ in ceiling /on roof etc. complete all as specified & directed, Make : Bajaj Phillips/CG/Havells.
Supplying & Fixing only LED Light Fitting 45 Watts lighting luminaires as security light to be fixed on buildings on external wall with connection from ceiling rose/ connector including copper conductor multi stranded three core cable 1 sqmm upto 2 meter length complete all as specified and directed by Engineer-in-Charge. MAKE C&S cat No LTESS45WLED/LS or equivalent in Bajaj / Havells NOTE for Item Nos 38 to 43 - The contractor should make proper safety arrangements for working at various locations and at heights in industrial sheds. Misc items required for completion of job is deemed to be included in the rates quoted.
Disconnecting and taking down old switch fuse type distribution Box with MCB/fuse grip TPN/SPN DB 2 Way to 12 Way old type DB including taking out all cable connections of any description and in any position and making good the disturbed surface with proper plastering of walls, to match with the existing surfaces including material complete all as specified and directed by Engineer in charge.
Supply, fixing, connecting & testing double door sheet metal TPN distribution board 6 way with 200 Amps rated aluminium bus bar, IP 43 class for using MCCB as incomer and SP/TP MCB as outgoing complete all as specified & directed. Make - Legrand cat No 6076 95 or equivalent in L&T/ABB/ Schneider.
Supply, fixing, connecting & testing double door sheet metal TPN distribution board 8 way with 200 Amps rated aluminium bus bar, IP 43 class for using MCCB as incomer and SP/TP MCB as outgoing complete all as specified & directed. Make - Legrand cat No 6079 14 or equivalent in L&T/ABB/ Schneider.
Supply, fixing, connecting & testing double door sheet metal TPN distribution board 12 way with 200 Amps rated aluminium bus bar, IP 43 class for using MCCB as incomer and SP/TP MCB as outgoing complete all as specified & directed. Make - Legrand cat No 6079 15 or equivalent in L&T/ABB/ Schneider.
Supply, fixing, connecting & testing double door sheet metal SPN distribution board 4 way with 100 Amps rated copper bus bar, IP 43, IK 09 class, inclusive of Neutral bar, Earth bar and Cable ties for Cable management complete all as specified & directed. Make - Legrand cat No 6077 20 or equivalent in L&T/ ABB/ Siemens.
Supply, fixing, connecting & testing double door sheet metal SPN distribution board 8 way with 100 Amps rated copper bus bar, IP 43, IK 09 class, inclusive of Neutral bar, Earth bar and Cable ties for Cable management complete all as specified & directed. Make - Legrand cat No 6077 21 or equivalent in L&T/ ABB/ Siemens.
Supply, fixing, connecting & testing double door sheet metal SPN distribution board 12 way with 100 Amps rated copper bus bar, IP 43, IK 09 class, inclusive of Neutral bar, Earth bar and Cable ties for Cable management complete all as specified & directed. Make - Legrand cat No 6077 22 or equivalent in L&T/ ABB/ Siemens NOTE for Item Nos. 45 to 50 :- Quoted rate is deemed to be inclusive of following - 1. suitable size metal flexible conduits and connected necessary accessories for terminating wires in to the distribution boards from conduits, 2. suitable size aluminium lugs to be crimped to incoming/outgoing cables.3. suitable size cable glands to be provided on incoming/outgoing cables. 4. any materials required such as anchor fasteners nuts, bolts, suitable size flat strip GI clamps etc. for fixing of DBs on the existing surface/frame.
Supplying & fixing in replacement MCCB 125 Amps, 4 pole, 25 kA breaking capacity at 415 Volt with thermal magnetic release (adjustment - 0.8 to 1 In) having Ics = 100% Icu complete with and inclusive of spreader terminals, glands complete all as specified and directed. Make - Legrand cat No 4200 56 or equivalent in ABB / L&T / Seimens.
Supplying & fixing in replacement MCCB 160 Amps, 4 pole, 25 kA breaking capacity at 415 Volt with thermal magnetic release (adjustment - 0.8 to 1 In) having Ics = 100% Icu complete with and inclusive of spreader terminals, glands complete all as specified and directed. Make - Legrand cat No 420057 or equivalent in ABB/L&T/ Seimens.
Supplying & fixing in replacement MCB 40 to 63 Amps, triple pole, 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, biconnect lower terminals, IP 20 protected terminals, sliding shutters complete all as specified and directed. Make - Legrand cat No 4086 59-61 or equivalent in ABB/L&T/ Seimens.
Supplying & fixing in replacement MCB 6 to 32 Amps, single pole and neutral, 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, biconnect lower terminals, IP 20 protected terminals, sliding shutters complete all as specified and directed. Make - Legrand cat No 4086-17 or equivalent in ABB/L&T/ Siemens.
Supplying & fixing in replacement MCB 6 to 32 Amps, single pole, 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, biconnect lower terminals, IP 20 protected terminals, sliding shutters complete all as specified and directed. Make - Legrand cat No 4085 87-95 or equivalent in ABB/L&T/ Seimens.
M&L for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground, earth pit not less than 2.25 meters deep below ground level with top edge of the plate not less than 1.5mtr below GL connected to and including 32x6 mm GI strip upto 7.5 m long by means of GI bolts, nuts, check nuts & washers and connected to earthing test point & earth dolly all as shown in electrical plate No 3 of SSR part I- (2009), earth lead protected with and including 40 mm bore GI pipe light grade and 20 mm bore medium grade watering pipe and testing on completion including excavation & earth work in any type of strata , PCC (1:3:6) type C-I chamber, precast slab 50mm thick in cement concrete (1:2:4) type B1 (reinforced with welded steel wire fabric of XPM, weight not less than 4 Kg /Sqm) with cast iron frame ,funnel with water pipe , wire mesh and lugs etc complete all as specified and directed by Engr-in-charge.
S&F earth continuity conductor or main earthing lead of size 32x6 mm GI strip fixed to wall drawn in conduit/pipe or any other indicated situation for loop earthing etc. incl removal of old as required all as specified and directed
S&F earth continuity conductor or main earthing lead of size 4.00 mm dia GI wire fixed to wall drawn in conduit/pipe or any other indicated situation for loop earthing etc. incl removal of old as required all as specified and directed
M&L control switch box for heavy duty Air circulator made from MS box ,8x 8x3 inch size fabricated from 2 mm thick ms sheet and painting with smoke gray colour over one coat of red oxide primer with 3 mm thick hylum sheet cover for fixing and including 01 No. dimmer controller, 450 W, 240 V, 50 Hz, pre wired, 01 No. 5&15 Amps socket, 01 No. 15 Amps piano switch and 01 No. 15 Amps plug top, all to be mounted on MS 'C' Channel/ angle iron with nut bolt etc . NOTE - (i) Quoted rate is deemed to be inclusive of fixing arrangements and connection of box and including dismantling of old unsv box. (ii) contractor should visit the site and study existing scheme. (iii) Any misc items required for completion of the same is deemed to be included in the rates quoted.
M&L for dismantling of existing panel/MS stand/rack including disconnecting of incoming and out going cables gland lugs/thimbles, etc carefully so that the same can be reconnected to new panel. and Supply, fix & testing LT panel-TTA (Totally type tested) factory made, single front,fix type,Floor mounted panel with aluminium bus bar of suitable size, panel fabricated with 2.0 mm CRCA sheet for load bearing members &1.6 mm thick sheet for non load bearing members . Panels shall be Suitable to accommodate the following incoming & outgoing switch gear , including accessories and making conections of incoming and outgoing cables with suitable cable glands, lugs, nuts and bolts , panel to be fixed on concrete base or on cable duct with and including necessary angle iron base frame of 50x50x6 mm duly painted and fixing material like fastener nut, bolt etc cable entry from back/bottom side as per site requirement complete all as specified and directed Make: Legrand/ABB/L&T
INCOMER : MCCB 4 Pole, 25 kA, 125 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420056 /L&T /ABB/
OUTGOINGS a) MCCB TPN, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In,with spreader links and insulating shields Make - Legrand, Cat No. - 420043/L&T /ABB/
b) MCCB TPN, 16 kA, 40 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420002 /L&T /ABB/
d) MCB four pole 6 to 32 Amps, 415 volts, 10 kA breaking capacity, 'C' curve Make Legrand Ct No 4086/99.- /L&T /ABB/
M&L for dismantling of existing panel/MS stand/rack including disconnecting of incoming and out going cables gland lugs/thimbles, etc carefully so that the same can be reconnected to new panel. and Supply, fix & testing LT panel-TTA (Totally type tested) factory made, single front,fix type,Floor mounted panel with aluminium bus bar of suitable size, panel fabricated with 2.0 mm CRCA sheet for load bearing members &1.6 mm thick sheet for non load bearing members . Panels shall be Suitable to accommodate the following incoming & outgoing switch gear , including accessories and making connections of incoming and outgoing cables with suitable cable glands, lugs, nuts and bolts , panel to be fixed on concrete base or on cable duct with and including necessary angle iron base frame of 50x50x6 mm duly painted and fixing material like fastener nut, bolt etc cable entry from back/bottom side as per site requirement complete all as specified and directed Make: Legrand/ABB/L&T
INCOMER : MCCB 4 Pole, 50 kA, 250 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420279/L&T /ABB
OUTGOINGS a) MCCB TPN, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In,with spreader links and insulating shields Make - Legrand, Cat No. - 420043/L&T /ABB
b) MCCB TPN,25 kA,100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420045/L&T /ABB
c) MCB TPN 32 AMPs "C" curve 10 KA Make Legrand Cat No 408699 /L&T /ABB
M&L for dismantling of existing panel/MS stand/rack including disconnecting of incoming and out going cables gland lugs/thimbles, etc carefully so that the same can be reconnected to new panel. and Supply, fix & testing LT panel-TTA (Totally type tested) factory made, single front,fix type,Floor mounted panel with aluminium bus bar of suitable size, panel fabricated with 2.0 mm CRCA sheet for load bearing members &1.6 mm thick sheet for non load bearing members . Panels shall be Suitable to accommodate the following incoming & outgoing switch gear , including accessories and making connections of incoming and outgoing cables with suitable cable glands, lugs, nuts and bolts , panel to be fixed on concrete base or on cable duct with and including necessary angle iron base frame of 50x50x6 mm duly painted and fixing material like fastener nut, bolt etc cable entry from back/bottom side as per site requirement complete all as specified and directed Make: Legrand/ABB/L&T
INCOMER : MCCB 4 Pole, 50 kA, 250 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420279 /L&T /ABB
OUTGOINGS a) MCCB TPN, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420043/L&T /ABB
b) MCCB TPN,25 kA,100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420045/L&T /ABB
c) MCB TPN 32 AMPs "C" curve 10 KA Make Legrand Cat No 408699 /L&T /ABB
M&L for dismantling of existing panel/MS stand/rack including disconnecting of incoming and out going cables gland lugs/thimbles, etc carefully so that the same can be reconnected to new panel. and Supply, fix & testing LT panel-TTA (Totally type tested) factory made, single front,fix type,Floor mounted panel with aluminium bus bar of suitable size, panel fabricated with 2.0 mm CRCA sheet for load bearing members &1.6 mm thick sheet for non load bearing members . Panels shall be Suitable to accommodate the following incoming & outgoing switch gear , including accessories and making connections of incoming and outgoing cables with suitable cable glands, lugs, nuts and bolts , panel to be fixed on concrete base or on cable duct with and including necessary angle iron base frame of 50x50x6 mm duly painted and fixing material like fastener nut, bolt etc cable entry from back/bottom side as per site requirement complete all as specified and directed Make: Legrand/ABB/L&T
INCOMER : MCCB 4 Pole, 50 kA,400 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 422021 /L&T /ABB/C&S
OUTGOINGS a) MCCB TPN, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420043 /L&T /ABB
b) MCCB TPN,25 kA,100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Make - Legrand, Cat No. - 420045 /L&T /ABB
c) MCB TPN 32 AMPs "C" curve 10 KA Make Legrand Cat No 408699 /L&T /ABB
M&L for dismantling of existing panel/MS stand/rack including disconnecting of incoming and out going cables gland lugs/thimbles, etc carefully so that the same can be reconnected to new panel. and Supply, fix & testing LT panel-TTA (Totally type tested) factory made, single front,fix type,Floor mounted panel with aluminium bus bar of suitable size, panel fabricated with 2.0 mm CRCA sheet for load bearing members &1.6 mm thick sheet for non load bearing members . Panels shall be Suitable to accommodate the following incoming & outgoing switch gear , including accessories and making connections of incoming and outgoing cables with suitable cable glands, lugs, nuts and bolts , panel to be fixed on concrete base or on cable duct with and including necessary angle iron base frame of 50x50x6 mm duly painted and fixing material like fastener nut,bolt etc cable entry from back/bottom side as per site requirement complete all as specified and directed Make: Legrand/ABB/L&T
INCOMER : MCCB 4 Pole, 50 kA, 250 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In,with spreader links and insulating shields Make - Legrand, Cat No. - 420279 /L&T /ABB
OUTGOINGS a) MCCB TPN, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420043/L&T /ABB
b) MCCB TPN,25 kA,100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420045/L&T /ABB
c) MCB TPN 32 AMPs "C" curve 10 KA . Make Legrand Cat No 408699 /L&T /ABB
Supply and laying and fixing on wall /laid in floor/duct/drawn through conduit XLPE insulated PVC bedded armoured heavy duty electric cable 1100 Volt grade with aluminium conductor of size 4 x 10 Sq mm all as specified and directed . Make Policab/ Gloster/ Finolex/ Havells
All as per item No 65 above but cable size 4x16 sqmm
All as per item No 65 above but cable size 4x25 sqmm
All as per item No 65 above but cable size 3.5x35 sqmm
All as per item No 65 above but cable size 3.5x50sqmm
All as per item No 65 above but cable size 3.5x70sqmm
All as per item No 65 above but cable size 3.5x120 sqmm
Removing of old ICTP main switch after disconnecting the incoming and out going cables and supply and fix MCCB thermal magnetic release 4 Pole 25 KA 63 Amps Make Legrand Cat No 420053 /L&T /ABB with one way metal inclosure Cat No 607944 /L&T /ABB and making connections of cables with suitable size nut bolt lugs and glands etc including making good the disturbed suface of wall including material complete all as specified and directed.
Removing of old ICTP main switch after disconnecting the incoming and out going cables and supply and fix MCCB thermal magnetic release 4 Pole 25 KA 100 Amps Make Legrand Cat No 420055 /L&T /ABB with one way metal enclosure Cat No 607944 /L&T /ABB and making connections of cables with suitable size nutbolt lugs and glands etc including making good the disturbed surface of wall including material complete all as specified and directed.
Removing of old ICTP main switch after disconnecting the incoming and out going cables and supply and fix Industrial plug and socket board confirming to IEC 61439-3, IK 08 TP32 Amps including plug top and MCB "C" curve 10 KA 32 Amps Make Legrand Cat No 5078 18 & 408658 /L&T /ABB including making good the disturbed surface of wall with and including all fixing material complete all as specified and directed.
Removing of old ICTP main switch after disconnecting the incoming and out going cables and supply and fix one way metal enclosure confirming to IEC 61439-3, IK 08 Cat No 5078 62 /L&T/ C&S and MCB "C" curve TPN 10 KA 32Amps Make Legrand Cat No 4086 80 /L&T/ABB including making good the disturbed surface of wall including material complete all as specified and directed.
Supply, fixing, connecting & testing sheet metal enclosures for TPN DBs (DPX 160 type of Legrand or equivalent) confirming to IP43 IK09 Protections suitable for using MCCB 160 Amps as incomer and MCB as outgoing 6 Way complete all as specified & directed, conforming to IS Make Legrand : cat No 6076 95 or equivalent in Schneider/L&T/ABB Note : MCCB , MCBSPN and MCBSPs will be measured and paid separately under relevant item of this schedule.
Supply only aluminium tube terminal ( Lug/thimble) heavy duty suitable for XLPE conductor 16 sqmm size make Dowells / Comet
Supply only aluminium tube terminal ( Lug/thimble) heavy duty suitable for XLPE conductor 25 sqmm size make Dowells / Comet
Supply only aluminium tube terminal ( Lug/thimble) heavy duty suitable for XLPE conductor 35 sqmm size make Dowells / Comet
Supply only aluminium tube terminal ( Lug/thimble) heavy duty suitable for XLPE conductor 50 sqmm size make Dowells / Comet
Supply only aluminium tube terminal ( Lug/thimble) heavy duty suitable for XLPE conductor 70 sqmm size make Dowells / Comet
Supply only aluminium tube terminal ( Lug/thimble) heavy duty suitable for XLPE conductor 95 sqmm size make Dowells / Comet
Supply only aluminium tube terminal ( Lug/thimble) heavy duty suitable for XLPE conductor 120sqmm size make Dowells / Comet
Supply only aluminium tube terminal ( Lug/thimble) heavy duty suitable for XLPE conductor 150 sqmm size make Dowells / Comet
Om Construction
M/S. Niksun Electro-Infra Private Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .