| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.8 LAccepted-AOC | L1 | Accepted-AOC Bidder quoted L1 rates | |
| 2 | L2₹45.9 L+₹2.3 L (5.38%)Rejected-AOC 131 SANGAM NAGAR OPP NATIONAL SCHOOL SANGHVI PUNE 411027 | PUNE | MAHARASHTRA | 411027 | L2 | Rejected-AOC Bidder not quoted L1 rates | |
| 3 | L3₹46.0 L+₹2.5 L (5.72%)Rejected-AOC | L3 | Rejected-AOC Bidder not quoted L1 rates | |
| 4 | L4₹51.3 L+₹7.7 L (17.8%)Rejected-AOC PLOT NO 8 PREMA APARTMENT VEDANTNAGAR CHHATRAPATI SAMBHAJINAGAR 431 007 M S | CHHATRAPATI SAMBHAJINAGAR | CHHATRAPATI SAMBHAJINAGAR | MAHARASHTRA | 431007 | L4 | Rejected-AOC Bidder not quoted L1 rates | |
| 5 | L5₹56.7 L+₹13.2 L (30.2%)Rejected-AOC 24 25 MANGAL ARCADE TELCO ROAD OPP HOTEL DOUBLE TREE MOHAN NAGAR CHINCHWAD PUNE 411019 | PUNE | MAHARASHTRA | 411019 | L5 | Rejected-AOC Bidder not quoted L1 rates |
Tender Value
₹44 L
EMD Value
₹88,000
Closing Date
25 Nov 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE SOUTH PUNE
NO 1 GENERAL BHAGAT MARG PUNE 411040
8301 REPAIRS TO LT DISTRIBUTION SYSTEM, REPLACMENT OF CABLE, MAINTENANCE OF PANELS, EXT ELECTRICAL SYSTEMS, PROTECTIVE SYSTEM AND MISC WORK IN AREA No. II AND OTHER AREA UNDER GE SOUTH PUNE
2021_MES_484536_1
8301 GE SOUTH PUNE
Open Tender
Civil Works
Item Rate
273 days
GE SOUTH PUNE
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE SOUTH PUNE
₹88,000
Yes
17 Jan 2022
28 Oct 2021
27 Nov 2021
28 Oct 2021
25 Nov 2021
13 Nov 2021
60 days
Amount
Design, supply, install, test and commissioning of free standing floor mounted, dust and vermin proof of suitable size for outdoor installation factory made LT Panel both front and rear side double door system, fabricated with 3.15mm thick CRCA sheet for load bearing members and 2 mm thick for doors and covers and shall be painted witrh epoxy powder paint by means of electro static gun after rigorous pre treatment comprising of cold phosphating process on all internal and external surfaces after due preparation of surfaces. The panel shall consists of 600Amps rating TPN bus bars of high conductivity aluminium alloy and shall be provided with colour coded heat shrinkable sleeves, with 600 mm depth of the panel. The panel shall be modular/cubical type with bus chamber cable ally and provided with separate fully compartments for each switch including instrumentation such as Ampere Meter, Volt meter, Phase indicating lamp with double stud hinged door, front and rear openable with locking arrangement and suitable for 1100 Volts grade, 3 phase 415 Volts, 50 cycles, AC Supply and to with stand short circuit fault level of not less than 10 KA and degree of protection shall be IP 54 .
Item No. 1 Contd... The panel shall be fixed with angle iron frame made of angles of size 50x50x6mm, embedded 200 mm below ground level in PCC 1:2:4, Type B1 using 20 mm grade stone aggregate, 600mm above ground level and comprising the following including taking out of old panels etc, removing of cables and connecting to new panels with all required material such as glands, lugs etc. (Note - Rate of all incoming and outgoing MCCBs with connected materials are included in this item. Old unserviceable LT Panel shall be dismantled and rate quoted shall be deemed to include in quoted rates.)
Item No. 1 Contd... INCOMING :- (a) MCCB TPN 400 Amps capacity rup cap 25 KA at 415 volt 50 Hz AC fixed thermal magnetic release type and earth leakage protection ICS =100% ICU with rotary handle - 01 No incoming OUTGOING :- (a) MCCB TPN 250 Amps capacity rup cap 25 KA at 415 volt 50 Hz AC fixed thermal magnetic release typewith rotary handle - 02 Nos Out going (b) MCCB TP 63 Amps capacity rup cap 16 KA at 415 volt 50 Hz AC fixed thermal magnetic release type with rotary handle - 02 Nos Out going (c) On load Change over switch 400 Amps TPN 415 volt 50 Hz with rotary handle 01 No (d) LT Danger notice plate -01 No (e) Panel Control wiring complete with suitable size copper conductor cable and suitable size gland for LT cables
Design, supply,install, test and comissioning of free standing floor mounted, dust and vermin proof of suitable size for out door installation factory made LT Panel both front and rear side double door system, fabricated with 3mm thick CRCA sheet for load bearing members and 2mm thick for doors and covers and shall be painted witrh epoxy powder paint by means of electro static gun after rigorous pre treatment comprising of cold phosphating process on all internal and external surfaces after due preparation of surfaces. The panel shall consist of 600Amps rating TPN bus bars of high conductivity aluminium alloy and shall be provided with colour coded heat shrinkable sleeves, with 600 mm depth of the panel. The panel shall be modular/cubical trype with bus chamber cable allyand provided with separate fully compartments for each switch including instrumentation such as Ampere Meter, Volt meter, Phase indicating lamp with double stud hinged door , front and rear openable with locking arrangement and suitable for 1100 Volts grade, 3 phase 415 Volts, 50 cycles, AC Supply and to with stand short circuit fault level of not less than 10 KA and degree of protection shall be IP-54.
Item No. 2 Contd... The panel shall be fixed with angle iron frame made of angles of size 50x50x6 mm , embedded 200 mm below ground level in PCC 1:2:4, Type B1 using 20 mm grade stone aggregate, 600mm above ground level and comprising the following including taking out of old panels etc, removing of cables and connecting to new panels with all required material such as cable, glands, lugs etc (Note - Rate of all incoming and outgoing MCCBs with connected materials are included in this item. Old unserviceable LT Panel shall be dismantled and rate quoted shall be deemed to include in quoted rates.)
Item No. 2 Contd... INCOMING :- (a) MCCB TPN 400 Amps capacity rup cap 25 KA at 415 volt 50 Hz AC fixed thermal magnetic release type and earth leakage protection ICS =100% ICU with rotary handle - 01 No incoming OUTGOING :- (a) MCCB TPN 200 Amps capacity rup cap 25 KA at 415 volt 50 Hz AC fixed thermal magnetic release typewith rotary handle - 01 Nos Out going (b) MCCB TP 125 Amps capacity rup cap 16 KA at 415 volt 50 Hz AC fixed thermal magnetic release type with rotary handle - 02 Nos Out going (c) MCCB TP 100 Amps capacity rup cap 16 KA at 415 volt 50 Hz AC fixed thermal magnetic release type with rotary handle - 02 Nos Out going (d) LT Danger notice plate -01 No (e) Panel Control wiring complete with suitable size copper conductor cable and suitable size gland for LT cables
Material and Labour for Cutting of branches of tree of various length to keep a clear distance of 3 mtr from LT/HT/ overhead line/ Transformer/ four pole/ two pole structure and depositioning the cut branches upto a distance of 50 mtr away from the LT/HT/ overhead line/ Transformer/ four pole/two pole structure complete all as spd and directed. (Note :- Each span between pole to pole shall be measured as one job)
Attending complaints of HT / LT fault, No light, short circuit fault, light fittings, DBs, Switch boards, Panel boards (Internal & External) require to be make it functional by replacing fuse, small piece of wire etc by providing one electrician and one helper in the complete area of residential area round the clock for and including Sundays and Holidays complete in working hours as decided by the MES and maintaining proper complaint register and upkeeping complaint slips duly signed by JE E/M and checked by Engineer in charge all as specified and directed (Note :- 1. Rate of Fuse wire, copper cable, copper thimbles, glands, earthing wire are deemed to be considered in this item 2. Minimum One electrician to be present daily during the contract period, if found absent Rs-1600 will be deducted daily)
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables etc. and getting out in the following type of strata complete all as specified and as directed :-
Soft/Loose soil
Hard/ Dense soil
Soft/disintegrated Rock
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed.
Removal of excavated material [soil] to a distance not Exc 50m and depositing where directed at a level not exc 1.5m above the starting point where directed complete all as specified and as directed.
M&L for laying reinforced concrete pipes, class NP2 of dia 100 mm, 2 nos half round (for bottom and top) and before laying exacaved area shall be leveling complete all as specified and as directed.
M & L for Earthing complete (Generator, Transformer, lightning arrestor and feeder pillar box) with galvanised steel earth plate electrode '60cm × 60cm × 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel earth strip protected by provision of GI 'medium grade' pipe 40mm bore including provision of concrete pit in PCC (1:2:4) type B1 (using 20mm graded stone aggregate) with 40mm thick cover in RCC (1:2:4) type B-1 reinforced with XPM (weight not less than 4 kg/sqm) and frame made out in MS angle iron of size 25x25x3mm with lugs 02 Nos and with MS handle made in 6mm dia round bar made to shape,
Item No. 09 Contd... including GI 'medium grade' 20mm bore pipe for watering, perforated at bottom 1.75m long placed on top edge of earth plate including provision of mixture of charcoal dust & common salt packed upto minimum 150mm all around the earth plate, test point made out of ohosphorus bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil returning filling in and removal of surplus soil to a distance not exceeding 50mtr all as shown in electrical plate No. 3 of SSR Part I 2009 connected to earthing test point all as specified or indicated 'including testing on completion. (NOTE :- GI strip and GI pipe 40mm bore medium grade for encasing GI strip upto 7.50m length per earthing shall be deemed to be included in the unit rate.)
M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc as required for 32x6mm galvanized iron strip, complete all as specified and directed.
Supply and fix in repair single phase preventer suitable for operation on 415 volt 50 HZ AC supply complete all as specified and as directed. (Make- L&T/Minilec)
Supply, laying, testing and commissionnig of UG LT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, crimpimg type cable lugs in LT panel/MCCB in bldg etc to suit the cable laid in trenches/fixed to poles/drawn through pipes of size 240 Sqmm 3.5 core complete all as specified and as directed.
All as per Sl. Item No. 14.00 above but 185 sq mm 3.5 core complete all as specified and as directed.
All as per Sl. item No. 14.00 above but 150 sq mm 3.5 core complete all as specified and as directed.
All as per Sl. item No. 14.00 above but 120 sq mm 3.5 core complete all as specified and as directed.
All as per Sl. item No. 14.00 above but 95 sq mm 3.5 core complete all as specified and as directed.
All as per Sl. item No. 14.00 above but 70 sqmm 3.5 core complete all as specified and as directed.
All as per Sl. item No. 14.00 above but 50 sqmm 3.5 core complete all as specified and as directed.
All as per Sl. item No. 14.00 above but 35 sqmm 3.5 core complete all as specified and as directed.
All as per Sl. item No. 14.00 above but 25 sqmm 3.5 core complete all as specified and as directed.
All as per Sl. item No. 14.00 above but 16 sqmm 4 core complete all as specified and as directed.
All as per Sl. item No. 14.00 above but 6 sqmm 2 core complete all as specified and as directed.
Material and Labour for bringing Cable testing van (Fault Finder) for detecting the location of fault in the LT /HT UG cable of any size complete all as specified and as directed
M&L in replacement for heat shrinkable Straight through jointing kit for LT 1.1 KV XLPE cables 185 to 240 Sqmm 3.5 core including all accessories required complete all as specified and as directed.
M&L in replacement for heat shrinkable Straight through jointing kit for LT 1.1 KV XLPE cables 70 to 150 Sqmm 3.5 core including all accessories required complete all as specified and as directed.
M&L in replacement for heat shrinkable Straight through jointing kit for LT 1.1 KV XLPE cables 25 to 50 Sqmm 3.5 core including all accessories required complete all as specified and as directed.
M&L in replacement for heat shrinkable Straight through jointing kit for LT 1.1 KV XLPE cables 6 to 16 Sqmm 2/4 core including all accessories required complete all as specified and as directed.
M&L in replacement of outdoor end termination joint cable jointing kit out door heat shrink type suitable for 11 kv HT cable 95 sq mm 3 core with jointing material including all accessories required complete all as specified and as directed.
M&L in replacement of outdoor end termination joint cable jointing kit out door heat shrink type suitable for 22 kv HT cable 95 to 120 sq mm 3 core with jointing material including all accessories required. [Make for Sl. Item No. 26 to 31 :- Denson/M Seal/Siemens.]
Supply and Fix in replacement of MCCB 63 Amps to 100 Amps,16 KA,3 Pole,415V complete all as specified and directed.
Supply and Fix in replacement of MCCB 63 Amps to 100 Amps,16 KA,4 Pole,415V complete all as specified and directed.
Supply and Fix in replacement of MCCB 125 Amps, 16 KA, 3 Pole, 415V complete all as specified and directed.
Supply and Fix in replacement of MCCB 125 Amps, 16 KA, 4 Pole, 415V complete all as specified and directed.
Supply and Fix in replacement of MCCB 200 Amps, 25 KA, 3 Pole, 415V complete all as specified and directed.
Supply and Fix in replacement of MCCB 200 Amps, 25 KA, 4 Pole, 415V complete all as specified and directed.
Supply and Fix in replacement of MCCB 250 Amps, 25 KA,3 Pole,415Vcomplete all as specified and directed by Engr-in-Charge.Make - Legrand /L&T/ABB
Supply and Fix in replacement of MCCB 250 Amps, 25 KA, 4 Pole, 415V complete all as specified and directed.
Supply and Fix in replacement of MCCB 400 Amps, 25 KA, 3 Pole, 415V complete all as specified and directed.
Supply and Fix in replacement of MCCB 400 Amps, 25 KA, 4 Pole ,415V complete all as specified and directed.
Supply and fix in repair Power Contactors 4 pole- Type MCX 13 AC-1 80 Amps confirm to IS / IEC 60947-4-1 & IEC 60947-4-1 CAT NO- CS97015 complete all as directed (Make: L&T/Havells/HPL)
Supply and replace on load change over switch disconnector in Sheet metal enclosure 200Amps 415 Volt 4Pole all as specified and directed. (Make -L&T/ Havells /Legrand)
S&F in repair Capacitor duty Contactors sutable for 5 KVAR capacitor complete all as specified and directed. (Make- L&T CAT NO- CS96127 or equivalent in Siemens / Schneider)
S&F in repair Capacitor duty Contactors sutable for 10 KVAR capacitor complete all as specified and directed.
S&F in repair Capacitor duty Contactors sutable for 20 KVAR capacitor complete all as specified and directed.
S&F in repair Capacitor duty Contactors sutable for 25 KVAR capacitor complete all as specified and directed.
S&F in repair Capacitor bank of 5 KVAR capacity suitable for existing capacitor panel complete all as specified and directed.
S&F in repair Capacitor bank of 10 KVAR capacity suitable for existing capacitor panel complete all as specified and directed.
S&F in repair Capacitor bank of 20 KVAR capacity suitable for existing capacitor panel complete all as specified and directed.
S&F in repair Capacitor bank of 25 KVAR capacity suitable for existing capacitor panel complete all as specified and directed. (Make for Sl. Item No. 45 to 51 above : L&T or equivalent in Siemens/Schneider)
Supply only 11 KV grade EN- 13319-2000 Rubber insulating seamless rubber Hand safety gloves Item Part No- JG of Jyot manufacturer and equivalent make complete all as specified and directed.
Supply and replace door for out door LT pannel made out of CRCA sheet 3.15 mm thick bend on side of match the existing door duly powder coated and with new hinges three to suit any size /shape of pannel complete all as specified and as directed.
S&F in repair post top lantern pure polyster UV resistant powder coated die cast aluminium housing with PMMA opal diffuser for uniform illumination type 45 W high power LEDs at light source and symetrical light distribution conforming to CAT Part No LP02-501-XXX-57-XX of WIPRO or of equivalent in Bajaj/Wipro/Philips/HPL specified here-in-after.
S&F in repair driver suitable for LED POST TOP light fitting of 20 to 30 wattage as per the existing make of the fitting and testing lights complete all as specified and as directed.
M&L for plain cement concrete 1:2:4 type B1 using 20mm graded stone aggregate etc including necessary form work complete all as specified and directed.
M & L for earthing with galvanised steel earth plate electrode 600 x 600 x 6.0 mm buried directly in ground earth pit not less than 2.25 m deep below normal ground level, with top edge of the plate vertically to a depth of not less than 1.5 m below ground level connected to and incl GI wire 4 mm dia and GI pipe 15 mm dia light grade for protection to the extent of 7.5 m as earthing lead by means of GI bolts and nuts etc connecting to equipment with provn of charcoal and salt etc all as per electrical plate No 3 of SSR Pt-I incl RCC cover, watering arrangement with GI pipe 20 mm dia and MS funnel, concrete pit incl excavation and earth work in any type of soil and testing on completion etc complete all as specified and directed.
Supply and fix earth continuity conductor or main earthing GI lead fixed to wall or pole on floor of size 4mm dia steel wire complete all as specified and as directed.
S&F LED Fantasy Bollard LB14 of 11/10 Watt IP 65 protection,corrosion resistance better optics for uniform distribution all as specified and directed conforming to WIPRO cat part No. LB14-131-XXX-65-05 or equivalent in Crompton/Bjajaj/ HPL complete all as specified and as directed.
S&F in repair Timer distribution boards of 32A 3pole/230V- with Analog Time Switch (with battery back up) of 3 mod DIN Daily 3P Module, 24 hours program, programmable every 15 min, backup of 100 hrs, current capacity 16A, with 1 change over (1 CO). conforming to Make- Indo Asian Timelite distribution boards conforming to Cat no-TL032ABO or equivalent in HPL/Havells including connecting with street light and testing complete all as directed
Supply, install, test and comissioning of 100 kvar automatic power factor control panel out door installation factory made both front and rear side double door system, fabricated with 3.15 mm thick CRCA sheet for load bearing members and 2mm thick for doors and covers and shall be painted witrh epoxy powder paint by means of electro static gun after gigorous pre treatment comprising of cold phosphating process on all internal and external surfaces after due preparation of surfaces. The panel shall consist of 300Amps rating TPN bus bars of high conductivity aluminium alloy and shall be provided with colour coded heat shrinkable sleeves, with more depth for accomodating Capacitor bank 08 Nos inside of the panel.
Item No. 61.00 Contd.... The panel shall be modular/cubical trype with bus chamber cable allyand provided with separate fully compartments for each switch including instrumentation such as Ampere Meter, Volt meter, Phase indicating lamp with double stud hinged door, front and rear openable with locking arrangement and suitable for 1100 Volts grade, 3 phase 415 Volts, 50 cycles, AC Supply and to with stand short circuit fault level of not less than 10 KA and degree of protection shall be IP 54. The panel shall be fixed with angle iron frame made of angles of size 50x50x6 mm, embedded 200 mm below ground level in PCC 1:2:4, Type B1 using 20 mm grade stone aggregate, 600mm above ground level and comprising the following including taking out of old panels etc, removing of cables and connecting to new panels with all required material such as glands, lugs etc (Note : Old unserviceable LT Panel shall be dismantled and rate quoted shall be deemed to include in quoted rates.)
Supply, install, test and comissioning of free standing floor mounted, dust and vermin proof suitable size for out door installation factory made both front and rear side double door system panel, fabricated with 3.15 mm thick CRCA sheet for load bearing members and 2 mm thick for doors and covers and shall be painted witrh epoxy powder paint by means of electro static gun after rigorous pre treatment comprising of cold phosphating process on all internal and external surfaces after due preparation of surfaces. The panel shall consist of 600Amps rating TPN bus bars of high conductivity aluminium alloy and shall be provided with colour coded heat shrinkable sleeves,with 600 mm depth of the panel.
Item No. 62.00 Contd.... The panel shall be modular/cubical trype with bus chamber cable ally and provided with separate fully compartments for each switch including instrumentation such as Ampere Meter, Volt meter, Phase indicating lamp with double stud hinged door , front and rear openable with locking arrangement and suitable for 1100 Volts grade, 3 phase 415 Volts, 50 cycles , AC Supply and to with stand short circuit fault level of not less than 10 KA and degree of protection shall be IP 54 . The panel shall be fixed with angle iron frame made of angles of size 50x50x6mm, embedded 200mm below ground level in PCC 1:2:4, Type B1 using 20 mm grade stone aggregate, 600 mm above ground level and comprising the following including taking out of old panels etc, removing of cables and connecting to new panels with all required material such as glands, lugs etc (Note : Old unserviceable LT Panel shall be dismantled and rate quoted shall be deemed to include in quoted rates.)
Item No. 62.00 Contd.... INCOMING :- (a) MCCB 4 pole 400 Amps capacity rup cap 25 KA at 415 volt 50 Hz AC fixed thermal magnetic release type and earth leakage protection ICS =100% ICU with rotary handle - 01 No incoming OUTGOING :- (a) MCCB 4 pole 200 Amps capacity rup cap 25 KA at 415 volt 50 Hz AC fixed thermal magnetic release typewith rotary handle - 01 Nos Out going (b) MCCB 3 pole100 Amps capacity rup cap 16 KA at 415 volt 50 Hz AC fixed thermal magnetic release type with rotary handle - 02 Nos Out going (c) MCCB 3 pole 63 Amps capacity rup cap 16 KA at 415 volt 50 Hz AC fixed thermal magnetic release type with rotary handle - 02 Nos Out going (d) LT Danger notice plate -01 No (e) Panel Control wiring complete with suitable size copper conductor cable and suitable size gland for LT cables
Supply and laying 40mm bore light grade GI pipe fixed to walls / poles or laid in trenches, road crossing etc, for protection of under ground cable including sealing ends with hessian cloth impregnated with bituminous compound in ground and with suitable clamps, bolt/nuts etc for fixing on walls, poles etc. including taking down / taking out old unserviceable pipes complete all as specified and directed.
All as per Sl. item No. 63.00 above but 50 mm bore complete all as specified and as directed.
All as Sl. item No. 63.00 above but 80mm bore complete all as specified and as directed.
Leo Enterprises
SHRI SWAPNAYOG ENTERPRISES
ASHWAMEDH ENGINEERS
metro electrical services
RAJKUMAR KISHANCHAND JASWANI
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .