EX. ENGINEER JAL SHAKTI PHE MECH DIVISION SGR
OFFICE OF THE EX. ENGINEER JALSHAKTI MECH SGR
Emergent Electrical and allied works to be carried out at WSS Tangnar Stage-Ist and 2nd.
2023_PHE_212135_1
PHE/MECH/e-NIT-10 of 05/2023
Open Tender
Electrical and Maintenance Works
Item Rate
25 days
Tangnar
As Per NIT
2 documents required · 2 mandatory
₹200
Yes
EX. ENGINEER JAL SHAKTI PHE MECH DIVISION SGR
₹7,000
Yes
24 May 2023
15 May 2023
23 May 2023
15 May 2023
22 May 2023
15 May 2023
Amount
TANGNAAR STAGE 1st
Repairs to existing (33/0.44 kV) 630 KVA HT transformers installed at Stage 1stby way of: - i) Dismantling/removing of upper Top lid cover of HT transformer along with disconnectingof all LV connection leads, thimbling etc for replacement of damaged LVbushing assembly after Providing and fitting of New Brass terminalAnti fog bushing assembly [03 No’s] completewith porcelain insulators, Neoprene rubber bushing, Brass bush rods of Dia more than 25 mm and length of 300mm approx. & allied gaskets etc as per existing sample using highly skilled manpower, tools& tackles keeping all precautions for the safety of the transformer into consideration. Re-assembling the HT transformers by way of fitting the top lid with all allied accessories. ii) Providing& filling of new Silica gel breatherhaving ½ kg of silica inside along with providing and fitting of New Gasket set to main Top cover/lid of above transformers as per existing sample. iii) Topping up of the HT transformer with HT Transformer Oilof Apar/TRUE Oil make of about 170 litres [Approx.]having Break Down Voltage/breaking capacity of 33KVand Conforming to IS: 335/2018. iv) Providing & Fitting of 400 mm2 Aluminium long barrel lugs [08 no’s] preferably of DOWELS make to be fitted at cable end terminals as a replacement against damaged/ worn-out ones with proper insulation/tapping at end joints. The Job includes crimping of thimbles after replacement of worn-out ones using Hydraulic crimping tool skilled labour and allied tools and tackles. The job includes connecting the 33 & 0.44 KV terminals and earthing to the said transformers and successful testing it on no and then on full load at site.
Repairs to existing (33/0.44 kV) 250 KVA HT transformers installed at Stage 1st by way of: - i) Dismantling/removing of upper Top lid cover of HT transformer along with disconnecting of all LV connection leads, thimbling etc for replacement of damaged LV bushing assembly after Providing and fitting of New Brass terminal bushing assembly [02 No’s] complete with porcelain insulators & allied gaskets etc as per existing sample using highly skilled manpower, tools & tackles keeping all precautions for the safety of the transformer into consideration. Re-assembling the HT transformers by way of fitting the top lid with all allied accessories. ii) Providing & filling of New Gasket set to main Top cover/lid of above transformers as per existing sample. iii) Topping up of the HT transformer with HT Transformer Oil of about 70 litres [Approx.] having Break Down Voltage/breaking capacity of 33KV and Conforming to IS: 335/2018.
Repairs to FASD motor starter for unit-2 by way of replacement of Main ML10 contactor point setafter disconnecting the starter from the system and then extracting the damaged/worn out contact point set. The contact point set shall be of L & T make. After fitting, the contact points starter is to be tested on full load. The job is inclusive of minor repairs to auxiliary wiring to the starter along with servicing of other existing ML10 contactor assembly by way of cleaning and decarbonising the contactor using the tools and tackles, skilled labour for execution of the job at site.
Replacement of damaged 4 pole D-sineMCCB at main LT panel inside sub-station yard at Stage 1st by way of providing and fitting of New 400 ampere, 415 /440 V, 4-pole, 50/60 Hz MCCB having breaking capacity of 50 ka with spiders in placeand shall conform to IS/IEC 60947-2 & EN 60947-2 standards. The MCCB to be of L&T make [DN3-400N].
TANGNAAR STAGE 2nd
Providing and Fitting of below Specified Motor Protection relay to 800A outgoing sub-panel for pumping unit-2as a replacement against damaged one by way of disconnecting both AC &DC power supply to the sub panel and then extraction of damaged motor protection relay from the outgoing panel after dismantling all control and Tripping circuit cable terminals from the relay. The job includes programming of the relay as per required parametersof HT motor installed at site with initial relay testing of above relayby relay testing equipment. The relay shall be interlocked with 11 KV VCB and Over Current &Earth fault relay already installed at the Sub- Panel per the rating and capacity of HT motor installed. The relay shall be tested on full load for all the protections and tripping’s like Thermal overload, Phase over current, Earth fault rotor block, loss of load etc. All tools and tackles and a Qualified Electrical Engineer well versed with the relay testing and programming is to be arranged by the firm. Test Certificate from Manufacturer for above relayis mandatory. Specifications of Relay required are as: - Brand: Schneider Current: 1/5 A Relay Type: Motor Protection Relay Mounting Type: Panel Ampere Sensitivity Setting: 1/5 A Voltage Type: AC/DC Voltage (V): 110 V Number Of Poles: 4 Pole Power Source: Electric Quantity: 01
Providing and fitting of below specified Single Phase 11Kv Cast Resin Current transformer as a replacement against damaged onesfor 800A out-going sub-panel of unit-2by way of extraction of damaged CTs installed at outgoing sub-Panelfrom bus bar arrangement to be dismantled from outgoing Panel with all lead and lifts involved. Specifications of CT areas; Model: MCTE 11011-0000/Equivalent Ratio: 100-200/1-1 A Frequency : 50 Hz Insulation class : E Burden: 15 VA/15 VA Standard: IS 2705 The entire job is to be executed by utilizing the services of an expert to be hired by firm having expertise in automation and cabling in HT electric supply and LT electronics. The job further includes replacement of 2.5mm Sq single coreCopper cables in four lengths [20 meters per CT]with proper ferrolling for proper identification etc from CT chamber to control /tripping relay/arrangement inside the Panel. The job has to be carried out with extreme caution as it has to be carried out in HT electric supply arrangement without halting the overall operation of the scheme.
Providing and fitting of below specified 16 channel Temperature Scanner as a replacement against damaged onesfor 800A out-going sub-panel of unit-2nd and 3rd by way of extraction of damaged Temperature scanners installed at outgoing sub-Panelwith all lead and lifts involved. The job further includes connection of control cabling with proper ferrolling for proper identification of parameters of temperature of windings of HT motor and both bearings etc. The entire job is to be executed by utilizing the services of an expert to be arranged by firm having expertise in automation and cabling and has to be carried out with extreme caution as it has to be carried out in HT electric supply arrangement without halting the overall operation of the scheme Specifications of Temperature scanners areas; Brand : Masibus/Equivalent No of Channel: 16 Channel Applicable Standards: DIN (ITS - 9 0) for Thermocouple and RTD Sampling Period Per Unit: 50 ms for TC and Linear Input and 100 ms for RTD Burnout Current: 0.4 uA Measurement Current: 250 uA Input Impedance: 1 Mohm for RTD/Voltage inputs,250ohms for current Input Allowable Wiring Resistance for RTD: Maximum 15 ohms/wire (Conductor resistance between three wires should be equal).
M/S SARIM ELECTRICAL SOLUTIONS
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .