Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.5 LAccepted-AOC 72 USMAN ENCAVE SECTOR O ALIGANJ LUCKNOW 226004 UP | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226004 | L1 | Accepted-AOC BEING L1 BIDDER | |
| 2 | L2₹12.4 L+₹3.4 L (38.3%)Rejected-Finance | L2 | Rejected-Finance NOT BEING LOWEST | |
| 3 | L3₹12.7 L+₹3.8 L (42.2%)Rejected-Finance | L3 | Rejected-Finance NOT BEING LOWEST | |
| 4 | L4₹13.6 L+₹4.6 L (51.3%)Rejected-Finance WARD NO 4 NEAR MASZID BHATTAGAON DISTT JHANSI 284001 UTTAR PRADESH | JHANSI | UTTAR PRADESH | 284001 | L4 | Rejected-Finance NOT BEING LOWEST | |
| 5 | L5₹15.8 L+₹6.9 L (76.5%)Rejected-Finance | L5 | Rejected-Finance NOT BEING LOWEST |
Tender Value
₹19.4 L
EMD Value
₹39,000
Closing Date
1 Jan 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) BKT
GE (AF) BKT LUCKNOW
SPECIAL REPAIR FOR RENEWAL OF ALUMINIUM WIRING AND CONNECTED WORK AT AF STN BKT
2023_MES_630969_1
8739/BKT/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) BKT
7 documents required · 7 mandatory
₹500
GE (AF) BKT
₹39,000
19 Mar 2024
4 Dec 2023
3 Jan 2024
4 Dec 2023
1 Jan 2024
18 Dec 2023
Amount
Taking down copper/aluminium point wiring for (light, fan, socket or power) complete including unserviceable fittings such as switches, ceiling rose, holders, sockets,light fittings etc. and making good the disturbed surfaces on wall/floor etc complete all as specified and directed. Note- (i) Dismantled serviceable light fitting shoud be kept in safe custody for reuse. (ii) Refixing of serviceable fitting shall be paid seperately under relevant items of this schedule
Refixing of serviceable light fittings upto 22 watt obtained form item no 1 including connecting up with 3 core flexible cable copper conductor of suitable size from ceiling rose complete all as specified. (Note : Rate of copper conductor cable shall deemed to be included in the quoted unit rate)
Taking down ols and unserviceable sub main wiring any size/type /core including earth wire complete with batten conduit etc complete all as soecified and directed.
Taking down old unserviceable sheet metal enclousure ,switch fuse unit,distribution board any type/way/capacity including fuses MCBs ,insulator RCCBs etc copmlete after removing all connection and making good the disturbed surface complete all as specified and directed..
M & L for point wiring with two single core PVC insulated & PVC unsheathed FRLS-H multistranded copper conductor cable of size 1.5 sqmm 1100 volt grade drawn into and including non metallic rigid PVC concelled conduit medium grade 25 mm dia with all accessories mounting all the surface of wall/ceiling/roof/etc with suitable size of module metal flush boxes and including modular front cover plate & back plate for mounting modular type switches /socket/fan/ regulator etc including provision of one single core PVC insulated and unsheathed multi stranded copper cable of size 1.5 sqmm 1100 volt grade as earth continuty conductor connected to common earth dolly switch board complete for following- One light/fan point controlled by one switch SP 5 Amps, 240 V
Ditto all as per item No 5 above but for one bell/buzzer point controlled by bell push
All as per the item no 5 here-in-before but for 2.5 sqmm conductor for 5 pin 15 Amps switch socket outlet.
All as per item No 5 above but for one light point controlled by two 2 way switches.
One 3 pin 5 amps switch socket outlet point on independent board
One 3 pin 5 amps socket point on same board
S&F switch modular type 1 module single pole, one way 5 Amps complete all as specified and directed.
S&F switch modular 15 Amps modular type 1 module complete all as specified and directed
S&F socket outlet 2 in 1, 3 pin, 5 Amps modular type 2 module complete all as specified and directed
S&F socket outlet 15 Amps 5 pin modular type 2 module complete all as specified and directed
S&F Bell push module type with two module complete all as specified and directed
S&F 5 Amps 2 way module with one module complete all as specified and directed
M&L for ceiling rose, PVC/polycarbonate, isolated body complete all as specified and directed
S&F stepped type electronic fan regulator modular type 1 module complete all as specified and directed
S&F bell, ding dong type AC, 230 Volt, single pole complete all as specified and directed
S&F Submain wiring with two single core PVC insulated FRLS multistrand copper conductor cable of size 04 Sq mm drawn into and including non metallic medium duty rigid concealed PVC conduit not less than 25 mm size ISI marked with all fittings / accessories and 04 Sq mm FRLS-H multistrand copper conductor cable as continuous earth wire complete all as specified and directed. (Note :- For submain wiring: Two run of single core cable and one run of earth wire will be measured as one length and conduit and its accessories are deemed to be included in the unit rate quoted for this items)
S&F Submain wiring with two single core PVC insulated FRLS multistrand copper conductor cable of size 10Sq mm drawn into and including non metallic heavy duty rigid concealed PVC conduit not less than 25 mm size ISI marked with all fittings / accessories and 10Sq mm FRLS-H multistrand copper conductor cable as continuous earth wire complete all as specified and directed. (Note :- For submain wiring: Two run of single core cable and one run of earth wire will be measured as one length and conduit and its accessories are deemed to be included in the unit rate quoted for this items.)
S&F Sheet metal enclosure 4 way TPN double door distribution board 415 volt complete all as specified and directed
S&F Sheet metal enclosure 12 way double door distribution board when MCB to be used SPN 240 volt sheet complete all as specified and directed
S&F MCB TPN 63-100 Amps 415 volt rupturing cap 10 ka "C" series complete all as specified and directed.
S&F MCB SPN 40 to 63 Amps 240 volt,50 hz,10 KA breaking capacity :C" curved type complete all as specified and directed.
S&F MCB single pole, 6 to 32 Amps, 240 Volts 50 HZ, 10 KA breaking capacity complete all as specified and directed.
S & F socket outlet 5 pin 20 Amps modular type 2 module with suitable size module metal flux boxes and including modular front cover plate and back plate for mounting modular type switch & socket with one single pole switch 15 Amps (1 module) including electrical connection all as specified and directed.
S & F batten holder backlite with 1x9 watt LED bulb includig all fixing accessories and making connection with copper conductor complete all as specified and directed.
S & F brass made bracket single light fitting with 115 mm dia Round base , brass arm length 57 mm provided with 78 mm lengthx76 mm bredth gallery inside 2 pin brass holder ,frosted glass shade 170 mm finish black nickel and gold plated with 1x7/1x9 watt LED bulb all as specified and directed.
S & F LED light fittings 1x18/20 watt ,220 volt AC decorative box type with driver holder including 18 watt LED tube light connecting up with 3 core flexible cable copper conductor of suitable size from ceiling rose complete.
S&F for Sleek LED mirror light 10 watt rating with diffuser 2ft long twisted flexible copper wire (approx 0.5 mtr long) complete all as specified and directed.
S & F new generation energy saving & enivornmental freindly long life LED street light made up to pressure dia cast housing with toughened glass and individual high power LEDs with secondary optics ,IP 66 protection and impact resistance of IK 07 and electronic driver of 45 watt 5700 K complete with security light bracket (complete with two set of suitable clamp ,nut and bolt) made out of 40 mm medium grade GI pipe bend to shape and with fixing arrangements duly welded (length of pipe should not be less than 1.2 mtrs) and making conection with using 2.5 sqmm PVC insulated multistranded copper conductor two single core cable complete all as specified and directed.
M & LEarthing complete with galvanised steel earth plate electrode size 60cm x 60cmx6 mm thick burried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 5 of MES Schedule Part-I connected to distribution board on completion with and including 15 mm bore light grade G.I. protection pipe (upto 7.5 M beyond outer edge of earth pit) and pit chamber with PCC (1:3:6) type C-1 using 20mm graded stone aggregate including 40mm thick cover of RCC (1:2:4) type B-1 using 20mm graded stone aggregate, reinforced with 6 mm dia M.S bars 3 Nos both ways with lifting hook made out of 6 mm dia bar, watering arrangement with funnel and wire mesh and 20 mm bore light grade G.I. watering pipe, common salt and charcoal filling, necessary excavation and earth work, complete all as specified and directed
H C CONSTRUCTION
M/S BABA ENTERPRISES
M/s JS Constructions
Shree Kanth Technologies
Industrial Traders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .