Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.9 LAccepted-AOC | ₹20.9 L Quoted ₹22.9 L | L1 | Accepted-AOC Lowest amount quoated |
| 2 | L2₹23.6 L+₹73,746.20 (3.22%)Rejected-Finance | ₹23.6 L+₹73,746.20 (3.22%) | L2 | Rejected-Finance Higher amount quoted |
| 3 | L3₹25.0 L+₹2.1 L (9.17%)Rejected-Finance | ₹25.0 L+₹2.1 L (9.17%) | L3 | Rejected-Finance Higher amount quoted |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not enlisted in required Catogary |
| 5 | Rejected-Technical A 14 USHA SADAN NEAR POST OFFICE COLABA MUMBAI 05 | MUMBAI | MUMBAI | MAHARASHTRA | 400005 | - | - | Rejected-Technical Not enlisted in required Catogary |
Tender Value
Refer Docs
EMD Value
₹47,560
Closing Date
15 Jul 2021, 6:00 pmClosed
CWE (A) Jaisalmer
CWE (A) Jaisalmer
REPAIR AND MAINT OF 33 KV SUB STN, HT OH LINE/UG CABLE, TRANSFORMER AND ALLIED WORKS IN AREA UNDER AGE (I) POKARAN
2021_MES_447076_1
83918
Open Tender
Electrical and Maintenance Works
Works
180 days
Pokaran
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
GE (A) Jaisalmer
₹47,560
Yes
30 Sept 2021
31 May 2021
16 Jul 2021
31 May 2021
15 Jul 2021
14 Jun 2021
Amount
Material and Labour for disconnecting defective transformer 33 KV/11 KV of capacity 3150 KVA on foundation and repairs at sub stn location or transportation for repair to workshop/ factory, dismantling the transformer for repair and reassembling the same after repairs checking with phase to phase, phase to neutral with body & neutral earthing for proper result and connecting all connection properly with checking of oil level, silica gel , air release plug , gate valve, drain valve, bushing terminal, tapping changer etc and renewal of unserviceable parts, denting, welding, etc and spray painting with two coats of synthetic enamelled paint (grey paint) including preparation of surface, marking of MES No.with white paint of suitable size and transportation from workshop/ factory to site and re-installed on platform commissioning and testing of transformer upto entire satisfaction of Engineer-in-charge. Note :- Spare parts/transformer oil/ rewinding will be measured and paid separately and supply & fixing only
M&L for taking out unserviceable complete coil on limb and HT/LT winding of transformer 13 KV/11 KV capacity 3150 KVA with suitable size/ existing gauge supper enamelled copper winding wire insulated with necessary insulating material complete all as specified & directed by Engineer-in-charge.
M&L for renewal of unserviceable HT bushes insulators of transformer 3150 KVA capacity including brass bush rod/spindle with nuts & wahers complete all as specified & directed by Engineer-in-charge.
Disconnecting transformer from load of any make,any size and any capacity, draining out transformer oil and regular filtration at location in position at site (on pole / platform) filtration upto required dielectric strength 45-50 KV with the help and drying plant by mechanical machines of suitable capacity to achive including testing of dielectric strength all directed by Engineer - in - charge
Supply and topping up / refilling of transformer oil of dielectric strength 50 KV minimum for transformer complete all as specified & directed by Engineer-in-charge.
S&F inreplacement of over current & earth fault relay complete accessories all as specified and directed by Engr-in-charge, Make - Avana Npa 422, ABB, CG
S&F indicator lamp red/green complete all as specified and as directed by Engr-in-charge.
M&L for checking, servicing of HT 11 KV 630 Amps, 20KA indoor type both sides externsible 5 way SF6 gas insulated, floor mounted with copper bus bar HT panel consisting of 01 No incoming VCB and 03 Nos outgoing VCB and 01 No air insulated bus PT panel coupled with RMU through bolted connection and sleeved busbars covered with insulating bolts. All live part , bus bars replacement of required part complete system commencing by technician if necessary requirement with following parts :-
S&F in replacement of resin cast ring core protection CT 50/1 Amp
S&F in replacement of 11 KV PT fuse complete all as specified
Dismantling concrete poles/struts, any size
Supply & errect in position Prestressed concrete pole, 11.0 metres long, 152mm x 152mm at top and 152mm x 260mm at bottom class 9 all as specifid and directed by Engr-in charge
S&F in replacement of pin type porcelain vitreous white brown or green insulator including one galvanised mild steel spindle two galvanised iron washers and one galvanised iron nut , 33000 volts grade complete all as specified & directed by Engineer- in -charge.
S & F in replacement of disc type insulator porcelain vitreous 145mm high and 255mm dia ball and socket type white brown or green single disc insulator including three-in series assembly for tension with tension clamps conductors working pressure 33000 volts grade complete all as specified & directed by Engineer-in charge.
Dismantling of ACSR conductors from existing pole and removing from site all as directed by Engr -in Cahrge.
M&L of aluminium conductor steel reinforced (ACSR) on pole, stringing properly on insulators and binding with aluminium binding wire, jumpers etc complete for any size ( Mink of size 3 of 6/1X3.66 mm , Dog ,Ferret ,Weasel ,Squirel of conductor. Note : - Measurement & Payment shall be made by measuring horizontal distance between centre of two adjaacent pole and adding 3% extra for sag , joints and jumper etc .
Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use with in 50m
M&L cross arm , bracing support MS clamps etc including necessary fabrication, bolts, nuts, washers etc and painting with one coat of red oxide and two coats of aluminium paints all as directed complete.
Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair/replacemnt of broken/worn out components and insulators etc.
Supply and fix in replacement ,installation commissioning & testing isolator gang operated (air break switch) outdoor type triple pole single break suitable for horizontal mounting revolving type consisting hot dipped galvinised channel having 2 Nos 33 KV post type insulator in stack and 03 such stack per phase copper or copper alloy high pressure heavily tinned and double contacts plated MS arcing horn complete with 40mm galvanised medium grade pipe as operating rod of suitable length operated handle with locking arrangements at both on & off position coupling connection etc suitable for 33 KV of rating 400 Amp capacity as per IS-1818 and rated short time current 25 KA for 3 seconds complete all as specified & directed by EIC.
S&F in replacement of Lightning arresters (4 Nos 22/24 KV post insulator per phase, for all 3 phases) (station type) out door line discharge class 3 nominal discharge current 10 KA and high current withstand 100 KA assembly suitable for 36 KV including all clamps, nuts and bolts, washers etc complete all as specified & directed by Engr-in-charge transmission class, discharge capacity 65 kilo amp ® suitable for 33000 volt.
M&L in replacement of Danger notice plate of 1.6mm thick mild steel sheet, viterous enamelled white, with letters, figures and conventional skull and bones in single red color and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size.
M&L for making pedastal 30 cm above GL in PCC 1:3:6 type C-1 using 20mm grade stone aggregate all around PCC / STEEL tubular poles.
M & L for trimming of trees/ branches minimum 3 mtrs. Either sides coming under / touching HT over head line and throughing at a distance out side cantt area all as directed
M&L for earthing with GI plate electrode 600 x 600 x 6 mm thick burried directly and preferably vertically in ground (earth pit not less than 2.25 m deep below the ground level) with top edge of the plate not less than 1.5 m below ground level connected to GI earthing strip 32 x 6 mm by means of nuts/bolts/washer check nuts and other end connected to earht test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh charcoal or coke and common salt in alternate layer of 15 cm (compacted thickness) all round the earth electrode, concrete pit PCC (1:3:6) type C-1 (with 20mm graded aggregate). 50 mm thick precast RCC (1:2:4) cover slable (re-inforced with 8mm dia TMT bar @ 15 cm both ways and suitable handle made of 10mm dia ) including necessary earth work in excavation, returning filling, and removal of surplus earth upto a distance exceeding 50 mtr etc. all as shown in electric plate No 3 of SSR part-I complete all as specified and directed by Engr-in- Charge.
M& L for GI earthing with GI plate electrode 600x600x6mm thick burried directly and preferably vertically in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below ground level connected to GI earthing lead of 4 mm dia GI steel wire all as shown in plate No 4 of SSR part (2009) to earthing test point including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete pit PCC (1:3:6) type C-1 (with 20mm graded aggregate). 50 mm thick precast RCC (1:2:4) cover slable (re-inforced with 8mm dia TMT bar @ 15 cm both ways and suitable handle made of 10mm dia ) including necessary earth work in excavation, returning filling, and removal of surplus earth upto a distance exceeding 50 mtr etc. all as shown in electric plate No 2 of SSR part-2 complete all as specified and directed by the Engr-in- Charge.
M & L for painting of PCC HT poles in Zebra pattern 30 cm wide, with synthentic enamelled paint in black and Red colour up to 1.2 metre height from pedestal, including writing in 80 mm wide letters/ numberss in both side of pole MES,HT and pole no all as directed by engr in charge.
M&L for painting of steel structure, GOD structural, cross arms, bracings, supports, clamps and back plates (all metalic parts) on PCC /Steel Tubular pole complete, with two coats of aluminium paint incl preparation of old painted steel surfaces incl painting of pole coping with black paint all as directed at site.
Dismantiling of broken stay assembly from various lacation any size and stay rod complete all as specified and directed at site. Note : Rates includes demolation of concrete and making good.
M&L fo stay assembly complete comprising of MS galvanised stay plate 30cm x 30 cm x 6mm , MS galvanised stay rod 20 mm dia with nut,215 cm long , MS galvanised stay bow 40 cm long with 02 Nos galvanised thimbles with and including all fittings as shown in electrical plate No 1 of SSR Part-I (loop type insulator, stay clamps, excavation and concrete measured separately).
S&F in repair, galvanised stay strand 7/3.15 laid for stay of poles complete .
M & L for re-stretching ACSR conductor on HT pole having (3) conductors with earthing GI wire or guardning wire etc complete in any type OH line including jumpers using new conductor & binding wire complete all as specified and as directed by Engr-in-charge.
M & L for Surface dressing n.exc 15 Cm deep in soft/ loose soil
M & L for Graded coarse aggregate 40 mm including spreading, levelling at various location pole structure, transformer area etc complete all as directed by Engr-in- Charge
Supply and replacement ACSR conductor duly insulated with HT heat shrink sleeve tubes for Jumper/incoming/dropout/GOD complete all as specified and as directed by Engr-in-charge.
M & L /overhauling /maintenance of HT 33 KV & 11 KV GOD horizontal/vertical type in position at locations by greasing all moving parts, cleaning contacts, making operating handle functional and tightening all connections incoming/ outgoing all as directed.
Supply and fix inr eplacement of HT 33 KV dropout insulators set (Set of three) in position at location
Excavation in trenches in soft /loose soil not exceeding 1.5 mtr wide for and 1.5 mtr depth for laying of cables and foundation etc.all as specifiedand getting out including trimming sides and forming bottom surface all as specified and directed at site.
Excavation in trenches in hard/ dense soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide for laying of cables, RCC poles/stays and struts etc and getting out including trimming sides and forming bottom surface all as specified and directed at site.
Excavation in trenches in soft /loose soil not exceeding 1.5 mtr wide and exceeding 1.5 mtr depth for pole foundation etc and getting out including trimming sides and forming bottom surface all as specified and directed at site.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm each soil
Removing excavated surplus soil obtained from excavation to a distance not exceeding 50 mtr and deposting where directed at a level not exceeding 1.5m above the starting point all as specified and directed.
M&L for sand cushioning to under ground cable using tibba sand and gently punning to cushioning to cable complete all as directed by Engineer-in-Charge.
Supply & laying 40 to 50mm thick roughly hammer dressed jodhpur stone patti cable cover 25 cm to 30 cm wide and n. exc 60cm long each laid dry abutting with each other with maximum gap between adjacent slabs n.exc 10mm complete all as specified & directed by Engineer-in-charge.
M&L for PCC 1:3:6 type C-1 using 20mm grade stone aggregate for pole road/ stay assy incl necessary form work & finishing concrete surface even & smooth without using extra cement all as specified & directed by engr-in-charge
M&L for PCC 1:4:8 type D-2 using 40mm grade stone aggregate in foundation of pole/road all as specified & directed by engr-in-charge
M&L for PCC 1:3:6 type C-2 using 40mm grade stone aggregate in foundation of stay all as specified & directed by engr-in-charge
Supply and laying & testing cable XLPE insulated screened PVC bedded galvanised steel strip or wire, armoured electric power cable (heavy duty) with stranded aluminium conductor 33000 volts earthed grade of cross sectioal area 300 Sq mm 3 core.
M&L cable jointing kit for 33 KV ( Earthed) grade cable for out door termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 Sqmm
Supply and fix in replacement of Galvanised steel water tubing 100 mm bore, light grade with all fittings (such as bends, elbows, tees, short plugs and unions etc.) and laid in trenches for protection of cable at road crossing etc.
Supply and fix in replacement of Galvanised steel water tubing 80 mm bore, light grade with all fittings (such as bends, elbows, tees, short plugs and unions etc.) and laid in trenches for protection of cable at road crossing etc.
M&L in repair galvanised steel wire 4mm dia as earth conductor run along the over head line duly binded with metallic cross arms and armour of cable at the end pole cpomplete .
Supply and lay rubber mat 2.0mtr long 1.0 m width and 19 mm thick complete all as specified
star electricals
SHOBHIT BUILDERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .