Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.1 LAccepted-AOC P O BEGAMPUR CHANDITALA JOYKRISHNAPUR HOOGHLY WEST BENGAL PIN 712306 | CHANDITALA | HOOGHLY | WEST BENGAL | 712306 | L1 | Accepted-AOC lowest bidder | |
| 2 | L2₹2.4 L+₹24,000 (11.2%)Rejected-Finance | L2 | Rejected-Finance Higher bidder | |
| 3 | L3₹2.4 L+₹28,560 (13.3%)Rejected-Finance JHETA JAMBANI PASCHIM MEDINIPUR | MIDNAPORE | PASCHIM MEDINIPUR | WEST BENGAL | 721260 | L3 | Rejected-Finance Higher bidder | |
| 4 | L4₹2.5 L+₹32,400 (15.1%)Rejected-Finance B 16 280 KALYANI KALYANI NEAR KALYANI MUNICIPALITY NADIA WEST BENGAL 741235 | NADIA | WEST BENGAL | 741235 | L4 | Rejected-Finance Higher bidder | |
| 5 | L5₹4.7 L+₹2.5 L (117.3%)Rejected-Finance F IA 24 4210 CO JAYKRISHNAPUR P O BEGAMPUR DIST HOOGHLY | BEGAMPUR | HOOGHLY | WEST BENGAL | L5 | Rejected-Finance Higher bidder |
| Sl No | Description | Qty | Unit | REFRICON L4 | SNOWLINE ENGINEERS L7 | SUPER COOLING AGENCY L6 | M.S. COOLING & ENGINEERING CO. L1 | MIR ENTERPRISE L3 | SYSTEMS CONTROL L2 | P. M. COOLING AND ENGINEERING CO L5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Comprehensive upkeepment of 8 x 5 Tr. Capacity Mortuary cooler plant, for 3 nos of 10 body and 1 no. Decomposed mortuary chamberas per terms & conditions. (New Morgue)(8 nos x 12 months=96) | 96 | Set | 2,200 ₹2,11,200 | 4,350 ₹4,17,600 | 4,250 ₹4,08,000 | 1,800 ₹1,72,800 Lowest | 2,260 ₹2,16,960 | 2,100 ₹2,01,600 | 4,150 ₹3,98,400 |
| 2.00 | Comprehensive upkeepment of 2 x 1.5 Tr. Capacity,2 nos 6 Body Mortuary cooler plant as per terms & conditions. (Old Morgue)(2 nos x 12 months=24) | 24 | Set | 1,500 ₹36,000 | 3,300 ₹79,200 | 3,250 ₹78,000 | 1,750 ₹42,000 | 1,100 ₹26,400 Lowest | 1,550 ₹37,200 | 2,850 ₹68,400 |
| 3.00SCOPE OF WORK FOR MAINTENANCE :- 1. CHECKING :- To check and service of the Mortuary cooler plant fortnightly covering the following works:- a)Checking the Mortuary cooler plant performance, gas leak and oil return and also refrigerant system. b)Checking the motors, starters, temparature controller with alarm system and other electrical equipments connected with the plant. c)Lubrication of bearings of compressor motor and blower fan etc. d)Checking and rectification the operation of control panel and safety cut-outs. e)Cleaning and discaling of the condenser once in a month as per direction of EIC. f)Cleaning of cooling coil once in a month as per direction of EIC. 2.REPAIRING OR REPLACEMENT :- a) Repairing the Mortuary cooler plant or repairing of parts thereof as and when necessary including cooling coil and temparature controller with alarm system. b) Thorough overhauling of the Mortuary cooler plant except compressor once in a year as directed. c)Pouring of refrigerant gas as and when required. d)Painting of the Mortuary cooler plant once in a year with approved paint as per direction of EIC. | ||||||||||
| 4.00TERMS & CONDITIONS FOR MAINTENANCE 1. Maintanance & servicing of Mortuary cooler plant includes control panel, motors, compressors, condensers, blower fans etc. and electrical installation after main incoming source. 2. The contract covers preventive servicing twice in a month. 3.This comprehensive contract covers preventive & corrective maintenance of AC plant / spare parts as required so as to keep the AC Plant well operative / functioning round the clock as desired from performance and safety point of view. 4.Service Challan should be submitted to the AE concerned duly countersigned by the Junior Engineer-in-Charge of work. Room temperature at the time of servicing must be mentioned in the service Challan. Room temperature should be 38ºF ± 2ºF. 5.The Log Book should be maintained and signed by the contractor or his authorized representative after completion of each phase of maintenance work under countersigned of the Junior Engineer concerned. In case of fault if so arises during maintenance work that should also be got signed by the contractor or his authorized representative noting the date & time of fault under countersignature of the Junior Engineer concerned. Date of repair of the same should also be signed by the Junior Engineer concerned with proper remarks. 6. Log Book will have to be maintained by the Supervisor of the entrusted Agency in which Grill temperature of the plant AC and details of servicing will have to be noted down everyday and duly countersigned by the JE and AE. 7. In case any fault / breakdown it should be intimated to the Junior Engineer/Assistant Engineer at earliest. 8. Service challan certifying satisfactory performance of the machines should be submitted to the concerned JE periodically after overhauling and that has to be countersigned by the AE and to be submitted alongwith the bill. Grill temperature for the AC machines have to be maintained within 40ºF ± 2ºF keeping proper entries in the service challan. 9. Any fault should be set right within 48 (fortyeight) hours. 10. A certificate of Assistant Engineer concern giving satisfactorily performance to machine should be obtained before payment. | ||||||||||
| 5.0011.This contract covers repair and replacement of spare parts & accessories including blower motor, sheet metal body and repairing of condenser coil & copper tubes, Capacitors, relay, thermostat, air filters etc. as necessary and these spare parts / accessories should be available at site in the custody of the entrusted agency. 12.Any inconvenience caused so far as performance of AC plant is concerned due to negligence in the part of the agency, if detected, will be liable to penalty. Quantum of penalty would be decided by EIC depending on the gravity of situation. 13. While taking up / starting the comprehensive maintenance of Mortuary cold storage units, the agency will have to start maintaining this plants as per above terms and conditions irrespective of the condition of the A.C.plant and no extra charges will be paid for repairing / replacement work. 14.The agency will have to provide self explanatory laminated photo identity cards and proper dresses with company’s logo for all the maintenance staff for need of Hospital Security reasons. 15.The behavior of mtc staff of the entrusted agency should be polite in nature and may be withdrawn from site in case of any adverse is reported. However, in normal cases, frequent changes of mtc staff will not be allowed without prior official intimation to the AE / JE. 16. No extra charges ( Duties/ Cess/ Taxes etc ) will be paid except the rate quoted by the agency as per unit per month basis for maintaining the above described terms & conditions 17. In case of any accident/ incident and or physical illness of the staff of entrusted agency while on duty, no claim will be entertained by this Department (P.W.D.) and all responsibilities thereof should be shoudered by the agency only. Minimum wages as per existing Labor Act should be paid to the staff. 18. Bill should be submitted bimonthly / quarterly as per direction of the EIC, keeping at least one spare log book at site and payment will be made on production of bill supported by documentary evidence. 19. The philosophy of "Public Interest" would be the MOTTO of this all inclusive comprehensive maintenance, any deviation may be viewed otherwise. 20. The concerned Executive Engineer reserves the right to terminate the contract against two months notice for performance not observed satisfactory as well as for any other administrative reason. | ||||||||||
Tender Value
Refer Docs
EMD Value
₹9,940
Closing Date
14 Sept 2022, 1:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer Paschim Med. Elecl. Div. PWDte
Office of the Executive Engineer, Paschim Medinipur Electrical Division, P.W.Dte. Paschim Medinipur.
Comprehensive Up keepment of 8X5 ton capacity Mortuary Cooler plant for 3 nos. of 10 body and 1 no. Decomposed mortuary chamber and 2nos 6 body at Midnapore Medical College , Paschim Medinipur.(01..10.2022-30.09.2023)
2022_WBPWD_401214_1
WBPWD/EE/PMED/NIQ-27/e-Q /2022-2023
Open Tender
ELECTRICAL WORKS ORG
Item Rate
365 days
Medinipur, Paschim Medinipur
Please refer Tender documents.
3 documents required · 3 mandatory
₹9,940
Executive Engineer Paschim Med. Elecl. Div. PWDte.
30 Oct 2026
2 Sept 2022
16 Sept 2022
2 Sept 2022
14 Sept 2022
7 Sept 2022
6 Sept 2022
Amount
Comprehensive upkeepment of 8 x 5 Tr. Capacity Mortuary cooler plant, for 3 nos of 10 body and 1 no. Decomposed mortuary chamberas per terms & conditions. (New Morgue)(8 nos x 12 months=96)
Comprehensive upkeepment of 2 x 1.5 Tr. Capacity,2 nos 6 Body Mortuary cooler plant as per terms & conditions. (Old Morgue)(2 nos x 12 months=24)
SCOPE OF WORK FOR MAINTENANCE :- 1. CHECKING :- To check and service of the Mortuary cooler plant fortnightly covering the following works:- a)Checking the Mortuary cooler plant performance, gas leak and oil return and also refrigerant system. b)Checking the motors, starters, temparature controller with alarm system and other electrical equipments connected with the plant. c)Lubrication of bearings of compressor motor and blower fan etc. d)Checking and rectification the operation of control panel and safety cut-outs. e)Cleaning and discaling of the condenser once in a month as per direction of EIC. f)Cleaning of cooling coil once in a month as per direction of EIC. 2.REPAIRING OR REPLACEMENT :- a) Repairing the Mortuary cooler plant or repairing of parts thereof as and when necessary including cooling coil and temparature controller with alarm system. b) Thorough overhauling of the Mortuary cooler plant except compressor once in a year as directed. c)Pouring of refrigerant gas as and when required. d)Painting of the Mortuary cooler plant once in a year with approved paint as per direction of EIC.
TERMS & CONDITIONS FOR MAINTENANCE 1. Maintanance & servicing of Mortuary cooler plant includes control panel, motors, compressors, condensers, blower fans etc. and electrical installation after main incoming source. 2. The contract covers preventive servicing twice in a month. 3.This comprehensive contract covers preventive & corrective maintenance of AC plant / spare parts as required so as to keep the AC Plant well operative / functioning round the clock as desired from performance and safety point of view. 4.Service Challan should be submitted to the AE concerned duly countersigned by the Junior Engineer-in-Charge of work. Room temperature at the time of servicing must be mentioned in the service Challan. Room temperature should be 38ºF ± 2ºF. 5.The Log Book should be maintained and signed by the contractor or his authorized representative after completion of each phase of maintenance work under countersigned of the Junior Engineer concerned. In case of fault if so arises during maintenance work that should also be got signed by the contractor or his authorized representative noting the date & time of fault under countersignature of the Junior Engineer concerned. Date of repair of the same should also be signed by the Junior Engineer concerned with proper remarks. 6. Log Book will have to be maintained by the Supervisor of the entrusted Agency in which Grill temperature of the plant AC and details of servicing will have to be noted down everyday and duly countersigned by the JE and AE. 7. In case any fault / breakdown it should be intimated to the Junior Engineer/Assistant Engineer at earliest. 8. Service challan certifying satisfactory performance of the machines should be submitted to the concerned JE periodically after overhauling and that has to be countersigned by the AE and to be submitted alongwith the bill. Grill temperature for the AC machines have to be maintained within 40ºF ± 2ºF keeping proper entries in the service challan. 9. Any fault should be set right within 48 (fortyeight) hours. 10. A certificate of Assistant Engineer concern giving satisfactorily performance to machine should be obtained before payment.
11.This contract covers repair and replacement of spare parts & accessories including blower motor, sheet metal body and repairing of condenser coil & copper tubes, Capacitors, relay, thermostat, air filters etc. as necessary and these spare parts / accessories should be available at site in the custody of the entrusted agency. 12.Any inconvenience caused so far as performance of AC plant is concerned due to negligence in the part of the agency, if detected, will be liable to penalty. Quantum of penalty would be decided by EIC depending on the gravity of situation. 13. While taking up / starting the comprehensive maintenance of Mortuary cold storage units, the agency will have to start maintaining this plants as per above terms and conditions irrespective of the condition of the A.C.plant and no extra charges will be paid for repairing / replacement work. 14.The agency will have to provide self explanatory laminated photo identity cards and proper dresses with company’s logo for all the maintenance staff for need of Hospital Security reasons. 15.The behavior of mtc staff of the entrusted agency should be polite in nature and may be withdrawn from site in case of any adverse is reported. However, in normal cases, frequent changes of mtc staff will not be allowed without prior official intimation to the AE / JE. 16. No extra charges ( Duties/ Cess/ Taxes etc ) will be paid except the rate quoted by the agency as per unit per month basis for maintaining the above described terms & conditions 17. In case of any accident/ incident and or physical illness of the staff of entrusted agency while on duty, no claim will be entertained by this Department (P.W.D.) and all responsibilities thereof should be shoudered by the agency only. Minimum wages as per existing Labor Act should be paid to the staff. 18. Bill should be submitted bimonthly / quarterly as per direction of the EIC, keeping at least one spare log book at site and payment will be made on production of bill supported by documentary evidence. 19. The philosophy of "Public Interest" would be the MOTTO of this all inclusive comprehensive maintenance, any deviation may be viewed otherwise. 20. The concerned Executive Engineer reserves the right to terminate the contract against two months notice for performance not observed satisfactory as well as for any other administrative reason.
SYSTEMS CONTROL
MIR ENTERPRISE
REFRICON
P. M. COOLING AND ENGINEERING CO
SUPER COOLING AGENCY
SNOWLINE ENGINEERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .