Loading…
Loading…
Tender Value
₹43.5 L
EMD Value
₹87,500
Closing Date
7 Sept 2026, 6:00 pm
GARRISON ENGINEER JORHAT
GARRISON ENGINEER JORHAT
SPECIAL REPAIR TO LT CABLE AND OTHER MISC WORKS UNDER JORHAT MIL STN
2026_MES_784912_1
8346/GE/E8
Open Tender
Civil Works
Item Rate
180 days
GE JORHAT
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GARRISON ENGINEER JORHAT
₹87,500
Yes
18 Aug 2026
18 Aug 2026
8 Sept 2026
18 Aug 2026
7 Sept 2026
1 Sept 2026
18 Aug 2026 - 25 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply , install, testing and commissioning as in replacement of cubical housing cabinet type CPRI approved Confirming to IP55 LT panel board outdoor type of size 0.80m x 0.80m x 0.40m, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 3.15 mm thick CRCA MS Sheet and built upon suitable size MS angle iron frame work, having front and rear hinged doors, lifting lugs (2 Nos), earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts, spring and washers. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment and apply spray paint with two coat of synethetic enamel paint over a coat of red oxide primer. The panel should be suitable for 415 volts, 50Hz, 3 phase 4 wire system and internal connection should be provided with aluminium strips of suitable size and necessary foundation work and comprising following:-
System Voltage-415V, 3-Ph, 4 wire, 50 HZ
Aluminium BUSBAR rating -200 Amps, cable entry (incomming and outgoing ) form bottom with cable gland
Incomming : 63 Amps MCCB FP, 16 KA, 415 Volts, 50 Hz-01 No
Outgoing -
(a) MCB 4 pole 40 Amps 10 kA Ac 50 Hz - 01 Nos
(b) Fully Automatic Star Delta Starter-01 No
(c) Motor Protection Relay - 01 No
(d) Digital Multifunction Meter - 01 No
(e) LED indicating lamps -03 Nos
(f) Spare Compartment - 01 No | 4 | Each job | - | - |
| 2 | Labour only for boring of hole under roads with mechanical arrangement upto 50 mm dia without disturbing the top surface of the road for passing the cable across the road complete all as specified and as directed. | 82 | RM | - | - |
| 3 | Supply and laying GI tubing 40mm bore light grade with fittings laid in trenches or for road crossing for protection of LT underground cables including taking up old unserviceable pipe complete all as specified and as directed. | 115 | RM | - | - |
| 4 | Supply and laying GI tubing 80mm bore light grade with fittings laid in trenches or for road crossing for protection of LT underground cables including taking up old unserviceable pipe complete all as specified and as directed. | 90 | RM | - | - |
| 5 | Material and labour for HDPE pipe of pressure rating 10 kgf/cm² and dia 75 mm for passing of cable through PCC foundation from trench to distribution board with necessary clamp nuts and bolts complete all as specified and as directed. | 65 | RM | - | - |
| 6 | Material and labour for HDPE pipe of pressure rating 10 kgf/cm² and dia 100 mm for passing of cable through PCC foundation from trench to distribution board with necessary clamp nuts and bolts complete all as specified and as directed. | 35 | RM | - | - |
| 7 | Supply and laying under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 16 Sqmm 4 core laid in trenches as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc. and replaement of old unserviceable cable complete all as specified and as directed. | 650 | RM | - | - |
| 8 | Supply and laying under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 25 Sqmm 4 core laid in trenches as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc. and replaement of old unserviceable cable complete all as specified and as directed. | 550 | RM | - | - |
| 9 | Supply and laying under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 35 Sqmm 3.5 core laid in trenches as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc. and replaement of old unserviceable cable complete all as specified and as directed. | 795 | RM | - | - |
| 10 | Supply and laying under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 50 Sqmm 3.5 core laid in trenches as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc. and replaement of old unserviceable cable complete all as specified and as directed. | 495 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.68 MB
1_CONTENT_TO_NOTE_8346.pdf
Tender Documents • 0.67 MB
2_General_Condition_8346.pdf
Tender Documents • 0.78 MB
3_Spl_Con_8346.pdf
Tender Documents • 0.37 MB
4_PS_8346.pdf
Tender Documents • 1.61 MB
BOQ_879523.xls
BOQ • 0.43 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].