| 1 | L1₹3.8 CrAccepted-AOC 54 AKASH DEEP COLONY CHAKRATA ROAD DEHRADUN UK 248001 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | ₹3.8 Cr | L1 | Accepted-AOC Being the lowest tenderer (L1) and reasonable tender. |
| 2 | L2₹4.5 Cr+₹75.2 L (19.8%)Rejected-Finance NOT SPECIFIED | ₹4.5 Cr+₹75.2 L (19.8%) | L2 | Rejected-Finance Not being the lowest |
| 3 | L3₹4.9 Cr+₹1.1 Cr (28.9%)Rejected-Finance | ₹4.9 Cr+₹1.1 Cr (28.9%) | L3 | Rejected-Finance Not being the lowest |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not enlisted in required category i.e b(ii) |
Tender Value
₹4 Cr
EMD Value
₹4.8 L
Closing Date
28 Aug 2020, 6:00 pmClosed
CHIEF ENGINEER NAVY MUMBAI
CHEIF ENGINEER NAVY MUMBAI, 26, ASSAYEE BUILDING, COLABA, MUMBAI-400005
PROVISION OF EXTERNAL SERVICES FOR INFRASTRUCTURE FOR BASING OF P-8I AIRCRAFT INCLUDING ALLIED FACILITIES AT INS HANSA
2020_MES_319333_3
87812-A/E8
Open Tender
Civil Works
Lump-sum
180 days
VASCO
As per tender documents
9 documents required · 9 mandatory
₹2,000
Yes
GE (NW) Vasco
₹4.8 L
Yes
5 Oct 2020
21 Jul 2020
31 Aug 2020
21 Jul 2020
28 Aug 2020
13 Aug 2020
22 Jul 2020 - 29 Jul 2020
Amount
SCH 'A' PART-I "BUILDINGS & STRUCTURES" Total of Sch-'A' Part-I B/F to BOQ(Schedule ‘A’) Serial Page No. 25
SCH 'A' PART- II "SITE CLEARANCE, EXCAVATION & EARTH WORK. Total of Sch "A" Part-II B/F to BOQ at Sl page No 26
SCH 'A' PART-III "EXTERNAL WATER SUPPLY" Total of Sch "A" Part-III B/F to BOQ at Sl page No 27
SCH 'A' PART-IV "EXTERNAL ELECTRIFICATION" Total of Sch "A" Part-IV B/F to BOQ (Schedule 'A') on Serial Page No 30
SCH 'A' PART- V" MISCELLANEOUS ITEMS"
"EXTERNAL ELECTRIC SUPPLY"
Supply, install, test and commissioning of step down POWER transformer outdoor type complete with standard accessories/fittings suitable for primary voltage HT 33KV, 3 phase and secondary voltage 11KV, 3 phase system ONAN type with copper Strip wound and Off load tap changing to vary secondary voltage ± 7.5% in step by step continuous rating of capacity 1600 KVA all as per IS-2026 with necessary PCC plinth foundation of suitable size and equipped with the following:- (Note: Considering furture expansion of 01 in Number new hanger) MAKE : BHEL/ ABB/ SCHNEIDER/ANDREW YULE
(a) Lifting lug for transformer and tank. (b) Earthing terminal rating and diagram plate. (c ) Air release device. (d) Oil filling inlet pipe with plug. (e) Drain outlet pipe with brass gate valve. (f) Conservator tank with oil level indicator (g) Silica jel breather (j) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335. (k) Type of connection Delta (l) Type of cooling: Oil and Natural Air. (m) Vector group:DYN 11. (n) Temperature rise over an ambient of 50 °C maximum. (o) Cable end box on both side for HT cables of suitable size. (p) Provision of thermometer with pocket. (q) Provision of oil and winding temperature gauge. (r) Buchholz relay with alarm trip contacts (s) explosion vent double diaphram
Supply,Installation,Testing and commissioning OUTDOOR TYPE Current Transformer, 33 KV, 60/30/5 A, 15 VA, 2 CORE , CORE -01 FOR METERING AND CORE -II FOR PROTECTION CLASS 5P20 AND KNEE POINT VOLTAGE MORE THAN 90VOLT AND COMPLETED system mounted on steel structure complete all as specified and directed.
Supply,Installation,Testing and commissioning OUTDOOR TYPE potential Transformer, (33000/110)/ volts single pole self cooled having 200 va burden suitable for metering /protection equipment installed including necessary steel structure , padestals all as specified and directed
Supply,Installation,Testing and commissioning of remote control panel for 33 kv outdoor VCB type tested indoor type made out of 2 mm thick CRCA sheet duly powder coated internally and externally complete with all interconnecting with CT, PT ,VCB by suitable size of copper control cable and comprising with the following accessiories:
Supply, install, testing and commisioning of Distribution transformer mounted on massonry platform stepdown , 11KV 0.433KV , Three Phase complying with IS: 1180/IEC-76(Part-1) 2014 with latest ammanmendts , Indoor type double opper wound suitable for 50 Hz system of capacity 1000 KVA, oil immersed naturally cooled delta connected on HT side and Star connected on LT side ,Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5 % in steP of 2.5 %. Losses should be confined to the limits specified as follows: :maximum allowable losses at full load (100 % ) & Half Load ( 50 % )shall not be exceeded 0.98 % & 0.70 % Respectivly as per GRlHA RATING, Percentage Impedance: 5%. Losses and Impedance are subjected to tolerance as specified in IS 1180. The transformers should be supplied with first filling of oil confirming to IS 335 .The transformer should have both side cable end box with neutral brought out complete all as directed by Engineer - in -Charge, and installation of transformer shall be carried out as per IS-10028 and comprising with the following standerd fittings/Technical specifications. Make BHEL/ABB/ Schneider/ Andrew Yule
(a) Lifting lug for transformer and tank.
(b) Earthing terminal rating and diagram plate.
(c ) Air release device.
(d) Oil filling inlet pipe with plug.
(e) Drain outlet pipe with brass gate valve.
(f) Conservator tank with oil level indicator
(g) Silica jel breather
(j) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335.
(k) Type of connection Delta/Star
(l) Type of cooling: Oil and Natural Air.
(m) Vector group:DYN 11.
(n) Temperature rise over an ambient of 50 °C maximum.
(o) Cable end box on both side for HT/LT cables of suitable size.
(p) Provision of thermometer with pocket.
(q) Provision of oil and winding temperature gauge.
(r) Buchholz relay with alarm trip contacts
(s) Explosion vent double diaphram
Supply, Installation, test and Commissioning CPRI approved factory fabricated, indoor type, LT Pannel Board made out of 2 mm thick CRCA Sheet with dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Test-ing after Installation including complete all as specified and comprising of the following :–Make of MCCB/MCB -LEGRAND/L&T/HEGGER/SCHNEIDER (location - near transformer)
INCOMING:-
OUTGOINGS:-
(d) MCCB 400 A 35 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no-CM98401OOROOG /Legrand cat no-4220 60/schneider cat no-LV540309 -3 NO (O/G) For Hanger-1 , 2, & Spare
(e) MCCB 40 A 25 KA,3 POLE ,thermal magnetic relese, Ics=100% Icu L&T cat no- SL98648OOOO /Legrand cat no-4200 82/schneider cat no-LV510316 - 1 no
(f) One cabinet space for fixing elecronic energy trivactor meter,suitable for 3 phase 4 wire CT operated ,temper proof,operated on 240v AC ,three phase, 5 amps to 10 amps, base mounting meter, backlit LCD display with user friendly legend, accuracy class-0.5, MD recording, revenue protection ( in case of wrong electric connection),capability to disply & communicate ( in case of absence of main supply), with optical port,deficiency metering with either phase/netral current, IP 51 protection, as per IS13779,, L&T model no- ER300P & Cat no-WR300BC5200 of L&T or equivalant of secure - 01 Nos each.
(g) Copper TPN bus bar 2000 Amps - 01 Set
(k) LED TYPE indicator lamp 1 set (set of three for R,Y,B)
Supply, Installation, test and Commissioning CPRI approved factory fabricated, indoor type, LT Pannel Board made out of 2 mm thick CRCA Sheet with dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 wire system , bus bar chamber with copper bus bar of 1200 amp rating for 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeve as per colour code , supported on epoxy insulators – 01 set incl necessary copper bus bar of suitable size for ACB / MCCBs / MCBs / changeover switch inter connections suitable for 440 volts 3 phase 4 wire system including danger plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Test-ing after Installation including complete all as specified and comprising of the following :–Make of MCCB/MCB -LEGRAND/L&T/HEGGER/SCHNEIDER
INCOMING:-
OUTGOINGS:-
(a) MCCB 400 A 35 KA ,3 POLE ,thermal magnetic relese, Ics=100% Icu & L&T c /Legrand /schneider - 1 no
(b) MCCB 250 A 35 KA, 3 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no-CM92009OOP1OG /Legrand cat no-420239/schneider cat no-LV525333 -02 No. (Adm bldg & Tech bldg)
(c) MCCB 100 A 25 KA, 3 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- SL98652OOOO/ LEGRAND CAT NO-420085 / ABB/schneider cat no-LV510317 -03(For Fire Fighting Pump , Lighting load Hanger-1 & Hanger 2)
(d) MCCB 40 A 25 KA,3 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- SL98648OOOO /Legrand cat no-4200 82/schneider cat no-LV510316 - 03 (Pump House , street light & Spare)
(g) LED TYPE indicator lamp 1 set (set of three for R,Y,B)
(h) Astronomical, Multifunctional digital time swithces cat no 004767 of legrand or equivalent of L & T cat no- T2 DD T7/MDS/GIC - 1 no
(j ) Power contactor ML-3 , 3 pole rating not less than 40 A with 230 coil make L&T/SEIMENS - 1 no.
(k ) MCB SP 6 amps-1 no.
M&L XLPE insulated screned PVC beded galvanised steel strip or wire armoured earthed electric power cable (heavy duty) with aluminium couductor 33/33 KV grade suitable for earthed system cross sectional area 120 sqmm 3 core H.T.U.G cable laid in tranches/through GI pipe/fixed along with pole complete all as specified & directed Note -Excavation and earth work shell be measured and paid for separately under relevant item of schedule.(b) High voltage test to be conducted at site with suitable voltage after laying of HT cable & reading to be recorded jointly & test report to be submitted in triplicate. The cost of the same is deemed to be included in unit rate of subject item.
Supply and fix Cable jointing kit for 33 KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm.
S& .PVC insulated armoured and pvc sheated heavy duty electric cable with COPPER conductor 1100 volt grade laid in tranches passing through pipes /ducts including testing complete of 8 CORE, 2.5 SQMM cross sectional area and size note- rate is inclusive of cable gland & cable lugs
Supply and fix cable route indicator made of round CI disc embossed LT Cable, of size 16cm dia 6mm thick duly revited with angle of size 50x50x4mm and 60cm long including PCC 1:2:4 B1 using 20mm aggregate 15cm x 15cm x 15cm for grouting the same complete all as specified.
Supply and fix cable route indicator made of round CI disc embossed HT Cable, of size 16cm dia 6mm thick duly revited with angle of size 50x50x4mm and 60cm long including PCC 1:2:4 B2 using 20mm aggregate 15cm x 15cm x 15cm for grouting the same complete all as specified.
Supply and erect RCC pole, 11m long, 180mm x 160mm at top and 300mm x 160mm at bottom, conforming to IS-785:1964.
Supply and fixed RCC pole, 9m long, 100mm x 130mm at top and 150mm x 230mm at bottom, conforming to IS-785:1964.
Material and Labour for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure
Supply and fix LED street light fitting 60 Watts complete with bracket made out of 40mm dia GI light grade tubing not less than 1.5mtr long bent to shape 120 deg including pole clamps (2no), clamp for fixing GI conduit pipe bracket made out of 50x6mm flat and nut bolts and 15mm GI LG for controle cable from top of SMC box to bottam of light fitting bracket, washers etc all as directed
Supply & fix PVC junction box IP 65 Protection of Size 200 mm x 250 mm x 115 mm complete with 1 Nos of MCB SP 2.5 Amps & 4 way industrial connector including Clamp made out of MS flat 30X5 mm, connection from junction box to street light fitting with three single core PVC insulated , PVC sheathed wire 2.5 Sqmm copper & PVC Conduit 20 mm dia. Make of Box- SPELS BERG/RITTAL/HENSEL CAT NO K8350
Supply and fix electric rubber hand gloves 11 KV
Supply and fix electric rubber hand gloves 33 KV
Material and Labour for Elecronic energy trivactor meter,suitable for 3 phase 4 wire CT operated ,temper proof,operated on 240v AC ,three phase, 5 amps to 10 amps, base mounting meter, backlit LCD display with user friendly legend, accuracy class-0.5, MD recording, revenue protection ( in case of wrong electric connection),capability to disply & communicate ( in case of absence of main supply), with optical port,deficiency metering with either phase/netral current, IP 51 protection, as per IS13779,, L&T model no- ER300P & Cat no-WR300BC5200 of L&T or equivalant of secure - 01 No each.
Material and Labour for Switch air break gang operated triple pole mechanically operated mounted on insulator and steel frame out door type suitable for vertical installation single brake provided with locking arrangement, consisting of MS channel ,HT post type insulator ,copper alloy high pressure assembly ,operating rod of 25 mm dia GI pipe medium grade confirming to IS-1818 of 1972 ,suitable for 33000 volt ,200 Amps all as specified.
M & L for drop out fuse assembly for 33 KV, 3 Phase of 200 Amp capacity each pole, consisting of galvanized steel base paper fuse carrying brackets, mounting channel, separating rod complete all as specified including labour for taking down old unserviceable DO unit all as directed by Engr-in-Charge.
Supply and fix pin insulator HT 33KV 10 KA station class with all connecting accessories complete, all as directed.
Supply and fix disc insulator HT 33KV 10 KA station class with all connecting accessories complete, all as directed.
Supply and fix LT bus duct air insulated type made out of 3mm thick CRCA sheet flanged type of suitable cross section with copper bus bars three phase and half neutral of 2000A capacity duly supported on DMC /FRP insulators including provision of suitable supports from ground for outdoor portion of bus duct with canopy &from roof for indoor portion of bus duct, painting the bus duct with two coats of synthetic enamelled paint over a coat of red oxide primer and connection with flexible laminated copper strips of same capacity at both transformer and LT panel complete all as directed and specified Makes : L&T
Supply, Installation, Testing and Commissioning of PLC based Outdoor type Remote Monitoring Control Panel suitable for Remote Monitoring of 1 no. 33 KV VCB, 01 nos. 11 KV VCB and 01 nos. HT transformers (33/11 KV), and 01 no. distribution transformer consisiting of (i) PLC with power supply and Rs 485 communication port (02 nos. - minimum),suitable DI/DO & AI expansion adaptors, (ii)HMI - 7" (min) Touch screen with USB port etc., (iii)SMPS of 5 A rating (iv) The PLC shall support Modbus / canbus / profibus communication protocol (v) Suitable Surge Protection device (vi) suitable no. of interposing relays 12/24 V D.C. coil rating and 2 A contact rating and (vi) 1 KVA UPS with Sealed Maintenance free Batteries for powering the panel for a minimum of 30 minutes,GPRS based communication with SCADA . Note: Scope of work includes integrating with the existing Integrated Smart Station Platform. The work of integration has to be carried out by representative of the Original implentor of the Smart Station Platform
Supply, Installation, Testing and Commissioning of PLC based Outdoor type Remote Monitoring Control Panel suitable for Remote Monitoring of 01 no 11 KV VCBs, 02 nos distribution transformer and 02 nos. LT panel consisting of (i) 15 nos. Energy meter Modules, (ii) Connectors, (iii) PLC with power supply and Rs 485 communication port (02 nos. - minimum), suitable DI/DO & AI expansion adaptors, (iv)HMI - 7" (min) Touch screen with USB port etc., (v)SMPS of 5 A rating (vi) The PLC shall support Modbus / canbus / profibus communication protocol (vi) Suitable Surge Protection device(viii) suitable no. of interposing relays 12/24 V D.C. coil rating and 2 A contact rating and (ix) 1 KVA UPS with Sealed Maintenance free Batteries for powering the panel for a minimum of 30 minutes GPRS based communication with SCADA. Note: Scope of work includes integrating with the existing Integrated Smart Station Platform. The work of integration has to be carried out by representative of the Original implentor of the Smart Station Platform. Make Techsol/ Nirmiti/ BCH/ Eldon/ Rittal
Supply, Installation, Testing and commissioning of 5 A Current Transformers of suitable for the existing Load on the feeder pillar
Supply, Installation, Testing and commissioning of 2 wire temperature sensor with thermocouple suitable for mounting on existing transformer. Technical Specifications: Input 24VDC, Output 4-20mA. Make : Honeywell/ Yog Electro Process/ Schnider as approved.
Supply, Installation, Testing and commissioning of Oil Level Sensor and Transmitter switch with suitable mounting bracket for existing transformer. Technical specifications: Input 24VDC, Output 4-20mA/RS485, Permissible Load: 600 Ohms @24VDC, enclosure: Weather Proof, Material of construction: Aluminum Make : Techtrol/ Yog Electro Process/ Trumen as approved.
Supply and Fixing of 4* 1.5 sq mm PVC sheathed and PVC insulated Cu flexible unarmoured Cable
Supply and Fixing of 6* 2.5 sq mm PVC sheathed and PVC insulated Cu flexible unarmoured Cable
Supply, install ,testing and commissioning SF6 insulated compact Outdoor type R.M.U. rated voltage 11 KV,rated current 630 A, short circuit breaking current 16 KA and making capacity 40 KA ,fully arc proof metal enclosed, free standing, floor mounting, flush fronted type consists of manually operated non draw out type SF6 module-2 Nos load break switches (Incomers) and 1 No. Vaccum circuit breaker (outgoing) with integrated relays and related CTs as specified below, cable switch module and an interlocking mechanism with the earthing switch all as specified and directed. Degree of protection shall be per manufacturer specifications.
(s) LED indicating lamps i) Auto trip ii)Spring charge iii)Fault alarm iv)Trip circuit healthy v)Trip circuit unhealthy vi)Breaker ON vii) Breaker OFF (t) Complete control panel wiring with copper wire of size not less than 1.5 sqmm (u) Civil works required for foundation as per manual of manufacturer
Supply, Install,testing and commissioning of battery bank OF 110 volt DC ( 55 nos + 2 nos Spare Lead acid VRLA MAINTANANCE FREE battery of 2 volts 100 AH) INCL necessary internal connection, wooden/steel racks suitable for kept at powerhouse incl Automatic Floatt cum boost ( 20AMPS) Battery charging equipment SCR controlled suitable for 30Volts 100 AH VRLA batteries with the following features/accessiories. input power supply 230 volt, 1 phase, 50 HZ, out put Voltage( Float/Boost Mode) 34 Volts, Output Current: 20 Amps (MAX) , at Float mode: 10 Amps DC continious plus Trickle charging Current, At boost mode: 15 Amps at Battery Terminal Mode of Operation /Terminal Charging : Automatic/Manual Control configaration: 1-Phase full wave half control thyristorised bridge fed through 1-phase transformer and controlled by constant potential controller unit with load limiting feature. Protection against (1) battery under/over voltage(i) Battery over charge/overload, (ii) Short circuit(iv) Surge suppressor(v) AC/DC CURRENT PROTECTION. (VI)fuse fail, (vii) earth fault protection. LED indications For: i) AC Input, ii) Float Charging, ii) Boost Charging, iv) charge Complete, v) Battery short, vii) reverse Polarity.
Supply & Fix Battery chargers of sufficient capacity to suit battery sets of 110V, 120 AH Capacity. The battery chargers suitable for 110V-120AH battery sets shall be operative from single phase, 50 Hz, 230 Volts AC supply. The battery charger shall be operative on Thyristor based Silicon Controlled Rectifier (SCR) both for float & boost section.
Supply and install 15 mtr Highmast system with its accessories. Mast shaft shall be in two sections hot deep galvanized and suitable for wind velocity of 50m/s. it shall include also accessories for highmast including head frame, steel wire rope 6mm dia (7/19 construction) trailing cable, double drum winch, galvanised lantern carriage arrangement suitable for 8 NOS (150 WATT LED LIGHT FITTING) luminaries symmetrically and lightning finial. The mast shall have an integral power tool installed inside the base compartment for its operation. (i) Supply of foundation bolts manufctured from special steel alongwith nuts, washers ,anchor plates & templates. (ii) supply of integral flood luminaries 150 Watt LED fittings complete with LED DRIVER. Make Philips/WIPRO/HAVELLS/CROMTEN/BAJAJ (iii) S&F control panel housing 32A TPN MCB (incomer, single dial timer contactor circuit for the automatic control of luminaries, outgoing terminals and control circuit for the power tool motor) and Aviation twin dome fitting. (iV) Aviation Obstructing lighting is vital for safety of every passenger on broad an aircraft as well as tall structures, towers and airp building of type : 919515810001 XGP 400 1 XLED-K2/RD 240V of Make Philips/ Equivalent fron Bajaj Foundation & Errection Part (1) Design and casting of suitable RCC foundation for 15m HM considering SBC of soil as 1OT/Sq.mt (ii) Errection of the highmast with the help of suitable equipments and wiring of luminaries with all wiring materials and labour. (ii) Erection of the above panel on suitable foundation including all materials and labour. (iv) Gl pipe earthing with long pipe The connections to be made with GI strip 32X6MM.- 02 set
Supply,Installation,Testing and commissionbing OUTDOOR `33KV, 400 Amps , 750 MVA, 25 KA for 3 Sec HT Vaccum Circuit Breaker for PROTECTION OF TRANSFORMER confirming to the IEC 62271-200,IAC-AFLR-25KA for 3 Sec PM KLSC -2B comprising of the following equipment :-
(a) Circuit breaker shall be mounted on a STEEL STRUCTURE MAKE: ANDREWYULE/AREVA/SIEMENS/ABB
(b) Motorised Spring charged Mechanism
(c)Separate eartyhing truck shall be provided for bus earthing and cable earthing.
(e)Panel Must Have additional features
(i) Continous rated closing/tripping coils (ii) Sprimg Charging Handle (iii) Fully internal Arc tested for 25 KVA for 3 Sec (iv) Manual closing /tripping of the CB with compartment door closed (v) Short time rating for 3 seconds as per IEC 62271-(vi) Mechanical endurance test-M2
Supply,Installation,Testing and commissioning `11 KV indoor, 630 Amps, 25 KA for 3 Sec HT Vaccum Circuit Breaker for Incommer confirming to the IEC 62271-200,IAC-AFLR-25KA for 3 Sec PM KLSC -2B comprising of the following equipment :-
(a) 630 Amps continous Bus Bar material shall be of high condiuctiveity electrolytic copper only.All Bus bars shall be insulated with heat shrinkable PVC sleeves and joints shall be covered with bitumen compound followed by HT tape. Phase identification shall be made at the end by coloured tape. Bus bars shall be mounted on integral seal off bushings all inter connection shall be of electrolytic grade copper only with joints silver plated.
(b) Circuit breaker shall be mounted on a with drawable truck which shall roll out horizontally from service position to isolated position with ease and .MAKE: ANDREWYULE/AREVA/SIEMENS/ABB
(c) Motorised Spring charged Mechanism
(d) Separate eartyhing truck shall be provided for bus earthing and cable earthing.
(e)Cast Resin Current Transformer, 11 KV, 50/25/5 A, 15 VA, CI 5P 10, CIO 5 Core II PS Class-03 Nos
(f)Cast Resin Three phase Potentail Transformer 11 KV/ 3/110V/ 3, 200VA, CI 1.0 – 03 Nos with desired capacity PT Fuses.
(h)Multifunction meter, Digital type (Displaying A,V,PF,Hz,KVA,KW,KVAR,KWh,KVARh etc) Class 0.5 with RS 485 port for commuinication of Modbus protocol Make : : L&T, Conzerve.
(j)SCADA compatible NUMERICAL NON-DIRECTIONAL IDMT four pole 3 O/C + 1 E/F WITH iNSTANTENEOUS OVER CURRENT AND EARTH FAULT PROTECTION Feeder Protection Relay -01 NOS . Make: ASHIDA Model No: ADR241A/equivalent in ABB /areva/ Siemens.
(k)High Speed Master Trip Relay – 1 No . Make ASHIDA Model No : AVAJH 33/ equivalent in ABB or Siemens.
(l)Trip Circuit Supervision Relay (VAX) – 1 No Make ASHIDA Model No : ATSR31A/ equivalent in ABB or Siemens.
(m)Air Insulated rear end Bottom Entry Cable Box suitable for termination of XLPE Cables.
(n) Panel Must Have additional features
(i) Continous rated closing/tripping coils (ii) Sprimg Charging Handle(iii) Fully internal Arc tested for 25 KVA for 3 Sec(iv) Manual closing /tripping of the CB with compartment door closed(v) Short time rating for 3 seconds as per IEC 62271-100(vi) Mechanical endurance test-M2
Breaker shall be provided with following features
(i) Auxillaty Switch 6 NO + 1 NC Contacts mounted on the draw out portion of the switchgear(ii) Position Cell Switch with 3 NO + 1 NC Contact on each for test position and Service Position.
Digital independent Volt meter and ammeter of suitable ratings- 01 each
Provision of necessary PCC foundation / masonry foundation of suitable size as recommonded by OEM
note: (i)Inbuild Power pack 110 v dc to be provided with panel at lkeast for 30 minuite Back Up.(ii) Auxiliary Supply Voltage for the Relay/Close/Trip coil 110 Volt DC.
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, indoor type 2 mm thick, APFC capacitor bank Panel Board of size as recommended by manufactrer 200 KVAR with 8 steps ( 50 + 25 + 25 + 25 + 25 + 25 + 12.5 + 12.5) WITH MD-XL CAPACITOR AND MCCB AS INCOMER Automatic Power Factor Correction panel , made out of 2 mm thick CRCA Sheet Dust and Vermin Proof, single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System,The enclosure shall be pre-treated as per 11 tanks process and finished with powder coating of shade RAL 7032. , including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified .The panel shall be factory fabricated comprosing of following. Make of pannel L&T/ SCHNEIDER/ABB
INCOMER
MCCB 630 A 35 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM94104OOT1OG /Legrand cat no-025540/schneider cat no-LV540310- 1 no (Thermal Magnetic Release)
ROM+SPDR - 1 no
Auxiliary 1 c/o +TAC 1 c/o- 1 no
OUTGOING CAPACITOR FEEDERS : -
50KVAr Capacitor feeder comprising of:- ( 1No. )
160A, BUSSMANN FUSE type 160EET - 3 nos
Thyristor switching module 50kVAR, 440V,TSM,LTTSM- 1
7% Detuned Aluminium Reactor 50KVAr 440V,LTAL,CAT NO-0750B2 -1
Ultra heavy duty capacior LTXL , BOX type oil Filled Capacitor bank 30 kVAr,sutable for 480V ,LTXL - 2 nos
Push Button ON/OFF -2 nos
Indicating lamps 2 nos
Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage, MX-0 type -1
6A DP MCB ,C-CURVE-1
25 KVAr Capacitor feeder comprising of:- ( 5 Nos. )
80A, BUSSMANN FUSE 80ET,-15 nos
Thyristor switching module 25kVAR, 440V , TSM,LTTSM-5 nos
7% Detuned Aluminium Reactor 25KVAr 440V
Ultra heavy duty capacior LTXL , BOX type oil Filled Capacitor bank 30 kVAr,sutable for 480V , LTXL - 5 NOS
Push Button ON/OFF -10nos
Indicating lamps 10 NOS
Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 5
6A DP MCB , C CURVE 5 NOS
12.5 KVAr Capacitor feeder comprising of:- ( 2 Nos. )
40A, BUSSMANN FUSE- 6 NOS
Thyristor switching module 25kVAR, 440V,TSM,LTTSM - 2 NOS
7% Detuned Aluminium Reactor 12.5KVAr 440V LTAL,CAT NO-0712B2- 2 NOS
Ultra heavy duty capacior LTXL , BOX type oil Filled Capacitor bank 15 kVAr,sutable for 480V
Push Button ON/OFF -4nos
Indicating lamps 4 NOS
Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 2
6A DP MCB , C CURVE 2 NOS
Incomer Metering
APFC relay 8 stage {BLR CM – 06T MB } -1 NO [230/ 110 V, 1/5A, 50 Hz] [Transistor output + Single CT sensing + RS 485 MODBUS]
Digital Voltmeter (3Ph, Class 1) -1 NO
Digital Ameter (3Ph, Class 1, 5A) -1 NO
Metering CT --/5A, Class-1- 3 NOS
SMPS 5A, Input 230V AC Output 24V DC -1 NO
ON Delay Timer 0-10 Sec.,Coil 24V DC -1 NO
Auxiliary Contactor {4NO} with 24V DC}-3 NOS
Indicating Lamp(R,Y,B)-3 NOS
6A SP MCB-3 NOS
6A DP MCB -01 no 6A FP MCB -1 NO
"EXTERNAL WATER SUPPLY"
Supply install test and commissiong of centrifugal pump set , electric driven complete with all accessories suitable for pumping water 180 LPM discharge at 50 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as , necessary connection from starter to motor terminal using proper size of copper cable including CI foot valve 50mm dia pressure gauge in delivery pipe ,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head rservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standared code of colour including MS base plate complete complete all as specified and directed.Note : Suction and delivery pipes shall be measured and paid under appropriate items
Supply install test and commissiong of centrifugal pump set ,electric driven complete with all accessories suitable for pumping water 180 LPM discharge at 150 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as necessary connection from starter to motor terminal using proper size of copper cable including CI foot valve 50mm dia pressure gauge in delivery pipe ,,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head rservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standared code of colour including MS base plate complete complete all as specified and directed.Note : Suction and delivery pipes shall be measured and paid under appropriate items
Supply and fix gunmetal non return valve of size 50 mm PN-1.6 dia ISI MARKED of MAKE Kirloskar/Upadhyay/L&T
Supply and fix CI foot valve, flanged end and drilled of size 50 mm dia ISI MARKED of MAKE Kirloskar/Upadhyay/L&T
Supply and fix CI 'Y ' Strainer screwed end or flanged type conforming to IS, size 50 mm dia.
Supply and fix Cast Iron Air Valves with single air Outlets, conforming to IS 14845 for Cast Iron Water supply mains of size 80 mm dia.
Construction of brick masonry valve chamber of size 900x 900x1200 mm (internal dia) suitable for 150 mm dia sluice valve with necessary earth work excavation plain cement concrete 1:4:8 using 40 mm graded stone aggregate 75 mm thick in cement mortar 1:6 15 mm thick plastering 1:6 inter nally including flooring and externally rep to 15 mm below ground level plain cement concrete 1:4:8 type B1 using 20 mm graded stone aggregate in coping MS sheet cover made out of 3 mm thick MS sheet flat iron frame and bracing with locking arrangement applying two coat of synthetic enamel paint including dismantling removing the existing damage chamber completely removal of debris to a distance not exce eding 50 mtr distance depositing where as directed by Engr in charge
Supply and laying Ductile iron pipes with spigot and socket ends centrifugally cast, Class K-9, in any length laid in trenches of size 80 mm dia Incuding rubbur Tytan joint Make : Electro steel/ Jindal/ Tata as approved
Supply and laying Ductile iron pipes with spigot and socket ends centrifugally cast, Class K-9, in any length laid in trenches of size 100 mm dia Incuding rubbur Tytan joint Make : Electro steel/ Jindal/ Tata as approved
Supply and laid spigot/flanged/ socketed DI fittings. Such as bends (any type radius and angle), tapers, tees, collars & tail piece socket/flanged/spigot etc of size 80mm to 300mm dia. Make : Electro steel/ Jindal/ Tata as approved
Supply install test and commission LT Panel board, TPN 415 Volts, 50 Hz, 100 Amps capacity, indoor cubical type floor mounted factory made double door dust and vermin froof fabricated out of CRCA sheet not less than 2.00 mm thick fixed on angle iron frame made out of 40x40x5 mm with cable chamber for individual feeders for incomming and outgoing connections, one set of indicator lamp RYB with switch and fuse, multifunction intelligent panel meter etc and with the followings (Main Pump panel):-
Supply install test and commission LT Panel board, TPN 415 Volts, 50 Hz, 100 Amps capacity, indoor cubical type floor mounted factory made double door dust and vermin froof fabricated out of CRCA sheet not less than 2.00 mm thick fixed on angle iron frame made out of 40x40x5 mm with cable chamber for individual feeders for incomming and outgoing connections, one set of indicator lamp RYB with switch and fuse, multifunction intelligent panel meter etc and with the followings (Fresh water pump)
Supply, Installation Testing & Commissioning of Indoor type Programmable Logic Controller based Pump and Valve Automation, Protection and communication Panel suitable for control and/or monitoring of 02 Nos. Centrifugal pumps, 14 Nos. motorized valves, 02 nos. priming valves, 02 nos. air release solenoid valves, 01 Nos Ultrasonic level sensor and 02 Nos Pressure transmitters.The panel should be of suitable size fabricated from 2.0 mm thick CRCA sheet and properly powder coated with angle iron supports not less than 40x40x5mm. .The Panel should comprise the following items: (a) Water Level Sensing & Display (b) Pump On/Off (c) Auto priming (d) Operation of Motor Actuated Butterfly Valves (e) Automatic Toggling of Pumps (f) Auto Change Over In Case of Pump Failure (g) Single Phasing Prevention (h) Manual mode operation (all connected sub system including all valves( in pump houses and connected buildings overhead
xi) Redundant GPRS modem based communication module comprising of one Main and One standby Modem with suitable antenna, modem controller and 02 nos. data eabled SIM cards (01 no. per modem) using two different service providers . The module shall be programmed to automatically toggle between the service providers based on the actual signal strength. switch to the stand by modem in case the main modem fails cost of communicationfrom the date of completion. The quoted cost shall deem to include the cost of communication for 12 months from the date of completion. Make of Control Panel: Any make with proven track record of having supplied a minimum of 50 (total) PLC based Panels with dual SIM card based GPRS communication in at least 03 nos. infrastructure automation projects during the last 3 years. Contractor shall produce documentary evidence in the form of completion certificate along with copy of Schedule / BOQ or certificate from an officer of rank not less than executive Engineer confirming the above condition. Note: Scope of work includes integrating with the existing Integrated Smart Station Platform. The work of integration has to be carried out by representative of the Original implentor of the Smart Station Platform
Supply, Installing,Testing and Commissioning of Ultrasonic Level Transmitter Range : 0-5 metres Accuracy : 0.5 % minimum Supply Voltage : 24V dc Output : 4-20 mA Ultrasonic Frequency:75 kHz burst, rep. rate 96 ms Delay at Power-up: 1.5 seconds Temperature Effect: Uncompensated: 0.2% of distance/°C &Compensated: 0.02% of distance/°C Delay at Power-up: 1.5 seconds Resolution: 1.0 mm Output Response Time: 100 ms to 2300 ms Minimum Window Size: 20 mm Environmental Rating: Leakproof design is rated IEC IP67; NEMA 6P Operating Conditions: Temperature: –20 °C to 70 °C (–4 °F to 158 °F) Maximum relative humidity: 100% Indicators Green Power On LED: Indicates power is ON Red Signal LED: Indicates target is within sensing range, and the condition of the received signal Teach/Output indicator (bicolor Amber/Red): Amber – Target is within taught limits; Flashing Amber – Target is outside taught window limits; Red – Sensor is in TEACH mode Makes: Endress+Hauser / Banner / Krohne Marshal / Siemens
Supply, Installation Testing & Commissioning of motor actuated ball valve suitable for 25mm GI pipe for priming of pump including all necessary GI fittings with following specifications: Size: 25 mm Pressure rating: 10 kg / sq. cm. Make: AVCON/ ROTEX/ ASCO/JOHNSON CONTROL/ RITETORK
Supply, Installation Testing & Commissioning of direct acting type release solenoid valve for air release during priming; with follwing specifications : Size: 10 mm Pressure rating: 10 kg / sq. cm. Type: Normally closed Make: AVCON/ ROTEX/ ASCO/JOHNSON CONTROL/ RITETORK
Supply, Installation Testing & Commissioning of pressure Transmitter with following specification including necessary power pack for supply of DC : Power supply: 10-36 V DC Process connection: G ½ “ Enclosure: whether proof IP 65 Process temperature: -30 to 120 celcius Accuracy: 0.25 % Make: Danfoss / Siemens / E & H
Supply, Installation Testing & Commissioning of Motor Actuated Butterfly Valve consisiting of Quarter turn single phase Actuator and Wafer type butterfly valve of size 80 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure. Specifications & Features Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Operating Angle: 90 degrees Disc Material: CI with nylon coating Limit Switches : 02 Nos.For open and close status In built Serial / USB communication Port In built data logger with memory In built SD Card Space Heater n built blue tooth transceiver with capability of pairing with any android based smart phone to download logged data. Mounting :Direct on valve Make: EMTORK / HASEL HOFENER / RITETORK / HONEYWELL / SIEMENS
Supply, Installation Testing & Commissioning of Motor Actuated Butterfly Valve consisiting of Quarter turn single phase Actuator and Wafer type butterfly valve of size 100 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure. Specifications & Features Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Operating Angle: 90 degrees Disc Material: CI with nylon coating Limit Switches : 02 Nos.For open and close status In built Serial / USB communication Port In built data logger with memory In built SD Card Space Heater n built blue tooth transceiver with capability of pairing with any android based smart phone to download logged data. Mounting :Direct on valve Make: EMTORK / HASEL HOFENER / RITETORK / HONEYWELL / SIEMENS
Earthing complete with Copper earth plate electrode 600mm x600 mm x 3mm thick buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to copper earth strip 32x6 mm by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm bronze flat including earthing pit , charcoal-250 kg, common salt-250 kg,& Magnesium sulphate -100 kg, Earthing lead 32x6 mm up to 7.5m, 20mm dia medium grade GI watering pipe ,PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover Including Earth work & GI protection pipe 40 mm dia upto 7.5 m long complete all as shown in electrical plate No-5 of SSR-2014 (part-I) NOTE-: COPPER earth strip shall be measured and paid for separately under relevant item of schedule .[ External Electrification]
Supply and fix copper earth strip 32mmx 6mm for earthing from earth plate to equipment complete fixed on porcelain insulator every 1 mtr interval all as specified and directed.
Earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth wire 4.00mmdia by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit , charcoal common salt ,Earthing lead 4.00mm dia up to 7.5m, 20mm dia medium grade GI watering pipe ,G.I. protection pipe 15 mm dia up to 7.5m long,,PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover including earth work complete all as shown in electrical plate No-5 of SSR-2014 (part-I)
Earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth strip 32 x 6mm GI by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit , charcoal common salt,Earthing lead 32x6 up to 7.5m, 20mm dia medium grade GI watering pipe ,PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover including Earth work & GI protection pipe 40 mm dia upto 7.5 m long complete all as shown in electrical plate No-5 of SSR-2014 (part-I) NOTE-: GI earth strip shell be measured and paid for separately under relevant item of schedule .
Suppy & Fixing 2 x 1.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, Copper cable multistranded. (Make: POLYCAB/FINOLEX/RR CABLE)
Suppy & Fixing 4 x 1.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, Copper cable multistranded. (Make: POLYCAB/FINOLEX/RR CABLE)
Suppy & Fixing 6 x 1.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, Copper cable multistranded. (Make: POLYCAB/FINOLEX/RR CABLE)
Supply and fix CI foot valve, flanged end and drilled of size 100 mm dia ISI MARKED
Supply and fix CI 'Y ' Strainer screwed end or flanged type conforming to IS, size 100 mm dia.
Supply and fix CI non return valve (ISI MARKED) of size 80 mm PN-1.6 dia. MAKE: Kirloskar/Upadhyay/L&T
United Sales Corporation
B D Raizada Projects Pvt Ltd
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .