Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹1.8 L
EMD Value
₹2,000
Closing Date
27 Mar 2020, 12:00 pmClosed
SE ETC-II,MORADABAD
220 KV S/S CAMPUS MAJHOLA MORADABAD
WORK OF SAFE CARRIAGE OF MATERIAL AND M AND R WORK OF 145 KV CIRCUIT BREAKER AT 132 KV S/S BIJNOR UNDER ETD BIJNOR
2020_UPTCL_442801_1
E-T-58/ETC-II/M/2020
Open Tender
Electrical Works
Fixed-rate
45 days
BIJNOR
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
EE ETD AMROHA ,SBI CURRENT ACCOUNT NO. 30723557626
₹2,000
25 Apr 2020
4 Mar 2020
27 Mar 2020
4 Mar 2020
27 Mar 2020
4 Mar 2020
Amount
WORK OF SAFE CARRIAGE OF MATERIAL AND M&R WORK OF 145 KV CIRCUIT BREAKER AT 132 KV S/S BIJNOR UNDER ETD BIJNOR.
Loading & unloading of 145 KV Circuit breaker (3 pole & breaker mechanism) by private crane/hydra at both sub stations and safe carriage of above material by private truck/vehicle from 132 KV S/S Kanth Road Moradabad to 132 KV S/S Bijnor. Approx. Distance 95 KM .
Attending SF-6 gas leakage from 03 No. Poles of 145 KV SF-6 CGL make circuit breaker of 40 MVA T/F-I at 132 KV S/S Bijnor as well as from 03 No. Poles brought from 132 KV S/S Kanth Road, Moradabad Detect pole leakage by SF-6 gas leakage detector, extract SF-6 gas from pole units with the help of SF-6 gas extraction plant & store it into empty SF-6 gas cylinder, dismantling pole units, pole panel & opening the pole joint & fixed contact chamber from the pole, cleaning of fixed & moving contacts, polishing the contacts & applying micro carbon grease on contacts surface, replace poles O rings, attending the air leakage from control valve, apply vacuum on poles by help of vacuum pump upto specified value & keep it for 8 to 10 Hrs. & check no loss of vacuum. Checking of NRV & drain valve for SF-6 gas leakage with the help of soap seeds. Replacement of NRV & drain valve if required. Checking of air switch, i.e. governor switches. Checking of gas density switch including it's adjustment. De rusting, lubrication of horizontal rod assembly & it's various linkages including all men, materials, consumable items and T&P.
Complete overhauling of mechanism assembly and checking/recording of 01 Nos. 145 KV SF-6 CGL make circuit breaker of 40 MVA T/F-I at 132 KV S/S Bijnor a Overhauling of drive mechanism along with replacement of overhauling kit of 'O' rings, gaskets and K slot rings. b Overhauling of magnetic valve along with replacement of overhauling kit of 'O' rings, gaskets and K slot rings. c Overhauling of control block along with replacement of overhauling kit of 'O' rings, gaskets and K slot rings. d Filling air upto specified value and check no air leakage. e Satisfactory close/trip operation of the breaker both by local and remote.
M/S AJAY KUMAR POWER CONSTRUCTION
M/S SATKAR TRADERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .