Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.0 LAccepted-AOC NEAR BDA COLONY JATNI DIST KHORDHA PIN 752050 | JATNI | KHORDHA | ODISHA | 752050 | L1 | Accepted-AOC Being L1 and fulfilled the required conditions of NIT | |
| 2 | L2₹5.9 L+₹97,434 (19.6%)Rejected-AOC 32 EQUIPMENT SALES AND SERVICES PRIVATE LIMITED 32 MADHUSUDAN NAGAR UNIT 4 BHUBANESWAR MADHUSUDAN NAGAR | L2 | Rejected-AOC Being not L1 tenderer |
Tender Value
₹5.8 L
EMD Value
₹11,528
Closing Date
17 Feb 2020, 3:00 pmClosed
Executive Engineer (E), BSNL, Bhubaeswar
Room no-317, 3rd Floor Door Sanchar Bhawan Unit IX Bhubaneswar
SITC of Addressable Fire Alarm system
2020_BSNL_42376_1
SITC of Addressable Fire Alarm system at ORERA BBS
Open Tender
Electrical Works
Works
15 days
Toshali Bhawan Bhubaneswar
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹11,528
Yes
21 Sept 2020
7 Feb 2020
18 Feb 2020
7 Feb 2020
17 Feb 2020
7 Feb 2020
7 Feb 2020 - 12 Feb 2020
Amount
Addressable analog 2 loop Control panel: Supply, installation, testing and commissioning of Micro processor based UL listed, addressable analog type, 2 wires, 2 Loop fire alarm/detection control panel, able to give location of all fire/fault conditions of addressable units via the address codes and must be able to automatically switch ON /OFF the respective control module when ever any alarm is triggered. It should consist of rectifier, Loop cards, 160 character L C D display unit to indicate Fire/Fault Signal with address and analog output, RS 485 communication for Network/Repeater, provision of maintenance alert, programmable detector sensitivity, automatic device type verification, USB 2.0 interface for PC connectivity, SLC loop max. length 3000mtrs, device wise configuration facility, suitable for operation on 120 to 220V, 50 Hz AC supply along with Battery backup 24 V DC with built in charger etc. complete as required. The panel should be made with CRCA sheet, powder coated and IP 30 degree of protection with LED indications for all faults and alarms etc. and should have a built in power supply and battery charger along with maintenance free 2 x12 volt, 7 AH, SMF batteries capable of running for a minimum of 4.5 hours with battery charger and conforming to BS:5839 Standards and Duly Approved by UL/FM/LPCB/VDS as per specifications complete in all respect as reqd.
Addressable Multi criteria Detector: Supply Installation Testing and Commissioning of Addressable analogue, UL Listed multi criteria Detectors of with round junction boxes for fixing of detectors & screws etc. on real ceiling/false ceiling/below false flooring connection, testing and commissioning etc. as per requirement and detailed specification. a) On Real Ceiling / On False Ceiling / On false Flooring
Addressable control modules: Supply Installation Testing and Commissioning of UL Listed Addressable control module complete with junction box etc. for control options for Hooters & for other control options like PA evacuation, Access Doors opening, the package Air Conditioners trip etc. in case of emergency, as required.
Manual Call Point: Supply Installation Testing and Commissioning of UL Listed addressable type Manual call points, break glass type made out of CRCA sheet with hammer and chain etc. as per specifications.
Electronic Hooter : Supply Installation Testing and Commissioning of UL listed Addressable type Electronic Hooter, dual tone sounder and optical strobe type with suitable CRCA housing & wiring circuits etc. as required.
Response Indicator: Supply Installation Testing and Commissioning of Response indicator having twin LEDs for mounting on false ceiling / wall at the entries of the cabin for indicating the operation of detectors in the above false ceiling / below false flooring detectors etc. as required.
Fault Isolator Module: Supply Installation Testing and Commissioning of UL Listed Fault isolation module to electrically isolate different sections of detector loops (for every 20 detectors / devices) as per detailed specifications.etc. as required.
Supply and laying of 2 core X1.5sqmm FRLS copper conductor armoured cable on surface/recess for looping the fire alarm devices & providing power supply to sounder cum strobes etc. as required. (ISI)
Supplying and making indoor end termination with brass compression gland and copper lugs for following size of PVC insulated and sheathed/XLPE copper conductor cable of 1.1 KV grade as required. a) 2 core, 1.5 Sq. mm (15mm)
Supplying and drawing of following sizes FRLS PVC insulated copper conductor single core cable in the existing surface/recessed steel conduit as required. a) 2X1.5sqmm
EQUIPMENT SALES AND SERVICES PRIVATE LIMITED
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .