Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹82.3 LAdmitted-Finance G II 3 ELDECO ESTATE ONE G T ROAD SECTOR 6 PANIPAT PANIPAT HARYANA 132103 | PANIPAT | HARYANA | 132103 | ₹82.3 L | L1 | Admitted-Finance |
| 2 | L2₹1.4 Cr+₹55.2 L (67.1%)Admitted-Finance | ₹1.4 Cr+₹55.2 L (67.1%) | L2 | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical 348 MADAN PUR KHADAR NEW DELHI 44 | CENTRAL | DELHI | 110002 | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| Sl No | Description | Qty | Unit | Mani Infracon Pvt. Ltd. L2 | M/s Surender & Co. L1 |
|---|---|---|---|---|---|
| 1.00Laying and Jointing PVC Pipe. Heading | |||||
| 1.01 | Supply, erection, testing and commissioning of Common Effluent Treatment plant based on attached growth aerobic moving bed bio reactor technology for the following:
Daily Avg. Sewage : 100 m3/day
PH : 7.0 - 8.0
BOD 5 : 300 mg/l
S. Solids : 250 mg/l
COD : 450 mg/l
Coliform : 10^6 - 10^7 counts / 100 ml
Effluent discharge standard after treatment:
Conforming to requirement approved standards
PH : 7.0 - 8.0
BOD 5 : Less than 20 mg/l
S. solids : Less than 20 mg/l
COD : Less than 100 mg/l
Outlet Coliform : < 1000 counts / 100 ml (at CCT outlet)
Common Effluent treatment plant shall include supply erection, testing & commissioning of the following items:
Manual Bar screen for 90 m3/day at the inlet of receiving sump for Sewage.
600 x 600 mm | 2 | Each | 1,50,000 ₹3,00,000 | 12,612 ₹25,224 Lowest |
| 1.02 | Manual Bar screen for 10 m3/day at the inlet of receiving sump for Effluent. 500 x 600 mm | 2 | Each | 3,267 ₹6,534 Lowest | 12,512 ₹25,024 |
| 1.03 | Raw Sewage / Effluent pumps: Non clog Submersible pumps complete with valves, suction and delivery header and priming tank of an approved make of suitable capacity capable of handling minimum 32mm size solids for untreated effluent with fan cooled induction motor with class 'B' insulation, mounted on a common structural base plate, suitable vibration eliminated pads of approved design for pump foundation, motor to be suitable for 400/440 volts, 3 phase, 50 cycles AC supply with rpm, to suit the corresponding pumps.
(a) Capacity 1.5 m3/hr at 10m head (For Effluent lifting from Collection Tank) | 2 | Each | 50,000 ₹1,00,000 | 19,286 ₹38,572 Lowest |
| 1.03 | Raw Sewage / Effluent pumps: Non clog Submersible pumps complete with valves, suction and delivery header and priming tank of an approved make of suitable capacity capable of handling minimum 32mm size solids for untreated effluent with fan cooled induction motor with class 'B' insulation, mounted on a common structural base plate, suitable vibration eliminated pads of approved design for pump foundation, motor to be suitable for 400/440 volts, 3 phase, 50 cycles AC supply with rpm, to suit the corresponding pumps.
(b) Capacity 4.5 m3/hr at 10m head (For sewage lifting from Equalization Tank) | 2 | Each | 1,00,000 ₹2,00,000 | 20,022 ₹40,044 Lowest |
| 1.04 | Sludge pumps: Centrifugal type, non clog self priming pumps complete with valves, suction and delivery header and priming tank of an approved make of suitable capacity capable of handling minimum 7 mm size solids for untreated effluent with fan cooled induction motor with class 'B' insulation, mounted on a common structural base plate, suitable vibration eliminated pads of approved design for pump foundation, motor to be suitable for 400/440 volts, 3 phase, 50 cycles AC supply with rpm, to suit the corresponding pumps
Capacity 4 m3/hr at 10m head (For transfer of sludge) | 2 | Each | 1,00,000 ₹2,00,000 | 19,343 ₹38,686 Lowest |
| 1.05 | Air Blowers: Twin lobe positive displacement type, rotary air blowers of suitable type with V-belt drive, belt guard, base plate, inlet filter-silencer, flexible connectors, check valve, relief valve, pressure gauge and piping.
Capacity- 130 m3/hr @ 5000 MMWG 2 Nos. (1w+1s), | 2 | Each | 5,000 ₹10,000 Lowest | 1,35,744 ₹2,71,488 |
| 1.06 | Non- Clogging, freely moving PP media for MBBR reactors | 5.5 | Meter cube | 10,000 ₹55,000 Lowest | 20,361 ₹1,11,985.5 |
| 1.07 | Air Grids (1 set): The FAB tanks equipped with non clog Air Grids for 800m3/day sewage flow to supply sufficient air for the treatment process and maintain adequate circulation velocity to prevent solids from settling.
No. of Diffusers : As required
Non submerged air piping : MS
Submerged Air Piping : Flexible braided pipe | 1 | Each | 8,999 ₹8,999 Lowest | 80,930 ₹80,930 |
| 1.08 | Media for tube settler as per design requirement | 2.5 | Meter cube | 9,000 ₹22,500 Lowest | 22,876 ₹57,190 |
Tender Value
Refer Docs
EMD Value
₹1.8 L
Closing Date
8 Apr 2021, 3:00 pmClosed
Ex. Engineer
Office of the Executive Engineer (Pr.)-I/Central Zone Shiv Mandir Marg, Jal Vihar, New Delhi-110003
Construction of 100 bedded Poornima Sethi Multi Specialty Hospital Kalkaji in W.No. 90-S, Central Zone SH Construction of Effluent Treatment Plant and Sewerage Treatment Plant
2021_SDMC_74764_1
EE (Pr.)-I/CNZ/TC/2020-21/16_01
Open Tender
Civil Works
Percentage
180 days
Work
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
₹1.8 L
Yes
12 Apr 2021
1 Apr 2021
9 Apr 2021
1 Apr 2021
8 Apr 2021
1 Apr 2021
Amount
Laying and Jointing PVC Pipe. Heading
Supply, erection, testing and commissioning of Common Effluent Treatment plant based on attached growth aerobic moving bed bio reactor technology for the following: Daily Avg. Sewage : 100 m3/day PH : 7.0 - 8.0 BOD 5 : 300 mg/l S. Solids : 250 mg/l COD : 450 mg/l Coliform : 10^6 - 10^7 counts / 100 ml Effluent discharge standard after treatment: Conforming to requirement approved standards PH : 7.0 - 8.0 BOD 5 : Less than 20 mg/l S. solids : Less than 20 mg/l COD : Less than 100 mg/l Outlet Coliform : < 1000 counts / 100 ml (at CCT outlet) Common Effluent treatment plant shall include supply erection, testing & commissioning of the following items: Manual Bar screen for 90 m3/day at the inlet of receiving sump for Sewage. 600 x 600 mm
Manual Bar screen for 10 m3/day at the inlet of receiving sump for Effluent. 500 x 600 mm
Raw Sewage / Effluent pumps: Non clog Submersible pumps complete with valves, suction and delivery header and priming tank of an approved make of suitable capacity capable of handling minimum 32mm size solids for untreated effluent with fan cooled induction motor with class 'B' insulation, mounted on a common structural base plate, suitable vibration eliminated pads of approved design for pump foundation, motor to be suitable for 400/440 volts, 3 phase, 50 cycles AC supply with rpm, to suit the corresponding pumps. (a) Capacity 1.5 m3/hr at 10m head (For Effluent lifting from Collection Tank)
Raw Sewage / Effluent pumps: Non clog Submersible pumps complete with valves, suction and delivery header and priming tank of an approved make of suitable capacity capable of handling minimum 32mm size solids for untreated effluent with fan cooled induction motor with class 'B' insulation, mounted on a common structural base plate, suitable vibration eliminated pads of approved design for pump foundation, motor to be suitable for 400/440 volts, 3 phase, 50 cycles AC supply with rpm, to suit the corresponding pumps. (b) Capacity 4.5 m3/hr at 10m head (For sewage lifting from Equalization Tank)
Sludge pumps: Centrifugal type, non clog self priming pumps complete with valves, suction and delivery header and priming tank of an approved make of suitable capacity capable of handling minimum 7 mm size solids for untreated effluent with fan cooled induction motor with class 'B' insulation, mounted on a common structural base plate, suitable vibration eliminated pads of approved design for pump foundation, motor to be suitable for 400/440 volts, 3 phase, 50 cycles AC supply with rpm, to suit the corresponding pumps Capacity 4 m3/hr at 10m head (For transfer of sludge)
Air Blowers: Twin lobe positive displacement type, rotary air blowers of suitable type with V-belt drive, belt guard, base plate, inlet filter-silencer, flexible connectors, check valve, relief valve, pressure gauge and piping. Capacity- 130 m3/hr @ 5000 MMWG 2 Nos. (1w+1s),
Non- Clogging, freely moving PP media for MBBR reactors
Air Grids (1 set): The FAB tanks equipped with non clog Air Grids for 800m3/day sewage flow to supply sufficient air for the treatment process and maintain adequate circulation velocity to prevent solids from settling. No. of Diffusers : As required Non submerged air piping : MS Submerged Air Piping : Flexible braided pipe
Media for tube settler as per design requirement
Filter Feed pumps: Centrifugal type, monoblock, self priming pumps with bronze in impeller of an approved make and complete with valves, suction and delivery headers capable of handling clear water complete with fan cooled induction motor with class B insulation, mounted on a common structural base plate with 100mm dia pressure gauge with gunmetal isolation cock and suitable vibration elimination pads of approved design for pump foundation. Motor to be suitable for 400/440 volts, 3 phase, 50 cycle AC supply with rpm, to suit the corresponding pumps. Capacity 7.5 m3/hr at 30m head.
Treated Water Transfer pumps: Centrifugal type, monoblock, self priming pumps with bronze in impeller of an approved make and complete with valves, suction and delivery headers capable of handling clear water complete with fan cooled induction motor with class B insulation, mounted on a common structural base plate with 100mm dia pressure gauge with gunmetal isolation cock and suitable vibration elimination pads of approved design for pump foundation. Motor to be suitable for 400/440 volts, 3 phase, 50 cycle AC supply with rpm, to suit the corresponding pumps. Capacity 5.5 m3/hr at 55 m head. (For Flushing/ Irrigation Use)
Soft Water Transfer pumps: Centrifugal type, monoblock, self priming pumps with bronze in impeller of an approved make and complete with valves, suction and delivery headers capable of handling clear water complete with fan cooled induction motor with class B insulation, mounted on a common structural base plate with 100mm dia pressure gauge with gunmetal isolation cock and suitable vibration elimination pads of approved design for pump foundation. Motor to be suitable for 400/440 volts, 3 phase, 50 cycle AC supply with rpm, to suit the corresponding pumps. Capacity 5.5 m3/hr at 55 m head. (For HVAC)
Sump Pump SS Submersible Pump Capacity 5.0 m3/hr at 10 m head.
UV Sterilizer suitable for a flow rate of 7500 lph
Metering Type Dosing Pumps with tank Flow Rate : 0-6 lph Tank : 100 ltr HDPE
Multi Grade filter: FRP pressure sand multigrade filter with frontal piping, filter media and multiport valve. Filter Dia : 900 mm Filter Ht : 1800 mm Capacity 7.5 m3/hr at 3.0kg/cm2
Activated Carbon Filter: FRP pressure Activated Carbon filter with frontal piping, activated carbon media and multiport valve. Filter Dia : 900 mm Filter Ht : 1800 mm (a) Capacity 7.5 m3/hr at 3.0kg/cm2
Softener: FRP pressure Softener with frontal piping, Softener Resin, and multiport valve Filter Dia : 750 mm Filter Ht : 1800 mm Capacity 5.5 m3/hr at 3.0 Kg/cm2 Resin Quantity : 275 Ltrs
Pipe lines and valves: Galvanized Iron pipes (heavy class) conforming to IS:1239 complete with carbon steel fittings IS:1879 e.g. tees, crosses, plugs, sockets, elbows, reducers, supports and clamps, puddle flanges, etc., cutting chases including painting pipes and fittings with epoxy paint over a coat of primer.
Fabricating, supplying, erection, testing and commissioning of totally enclosed cubicle type free standing, floor mounted, compartmentalised, sectionalised, dust, damp and vermin proof, with suitable natural ventilation arrangement, front and rear accessible, lockable power cum control panel, fabricated from 2 mm thick MS sheet ( to give IP 52 protection ) powder coated with approved colour shade, heavy 4 strip sleeved aluminium / aluminium alloy bus bar, bus bar supports, interconnecting from busbars to outgoing switches / MCCBs including earthing the board suitable to accomodate the following including numbering etc., as required: Cubical panel as described above with following: Incoming As Required Indicating Panel As Required Bus Bar As Required OUTGOING a) Raw Sewage Pumps Qty : 02 Nos. b) Raw Effluent Pumps Qty : 02 Nos. c) Plant Room Sump Pumps Qty : 02 Nos. d) Sludge Pumps Qty : 02 Nos. e) Air Blowers Qty : 02 Nos. f) Filter Feed Pumps Qty : 02 Nos. g) Treated Water Transfer Pumps Qty : 02 Nos. h) Soft Water Transfer Pumps Qty : 02 Nos. i) UV Sterilizer Qty : 01 No. j) Screw Pump Qty : 1 No. k) Dosing Pumps Qty : 01 Nos Electrical Panel as per Details above
Complete Wiring mounted on Cable Trays for all equipments within the plant area
Providing & Fixing 01 No. Filter Press having 18 Plates of Size : 18" x 18"
Providing & Fixing Screw Pumps for feeding the filter Press capacity : 1000 lph @ 35 - 40 mtr head.
Instrumentation consisting of : Air Rotameter for FAB Tanks x 01 No. Air Rotameter for Sludge Holding Tank x 1 No. Air Rotameter for Equalization Tank x 1 No. Air Rotameter for Reaction Tank x 01 No. Air Rotameter for Air Lifting Arrangement x 01 No. Bulk Meter at outlet of UV (40 mm dia) x 1 No. Pressure Guages x 10 Nos Energy Meter (01 No.) Online pH Meter (01 No)
Bidder Name
Amount
Mani Infracon Pvt. Ltd.(GSTN-NA)
M/s Surender & Co.(GSTN-NA)
Description of Work / Item(s)
Laying and Jointing PVC Pipe. Heading
Brick work in C.M 1:5 mix including all labour charges etc complete
Brick work in C.M 1:5 mix using 2nd class ground moulded chamber burnt bricks with including cost and conveyance of all materials and including all labour charges etc complete
Plastering in C.M 1:5-12 mm thick with including cost and conveyance of all materials and including all labour charges etc complete
M/s Surender & Co.
Mani Infracon Pvt. Ltd.
Bidder Name
Mani Infracon Pvt. Ltd.
M/s Surender & Co.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .