Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance B 14 1 GIDC ELECTRONIC ZONE SECTOR 25 GHANDINAGAR 382 044 | GHANDINAGAR | GANDHINAGAR | GUJARAT | 382044 | Admitted-Finance |
| 2 | Admitted-Finance 17TH FLOOR UNIT NO 1 TOWER 1 PS SRIJAN CORPORATE TECH PARK PLOT NO 2 BLOCK EP GP SECTOR V SALT LAKE KOLKATA WEST BENGAL 700091 | KOLKATA | KOLKATA | WEST BENGAL | 700091 | Admitted-Finance |
| 3 | Rejected-Technical 119 120 120A ELECTRICAL ELECTRONICS INDUSTRIAL ESTATE PERUNGUDI CHENNAI KANCHEEPURAM INDIA | Rejected-Technical Techno Commercially Not AcceptableVendor has offered UPS System with DC Buck Boost converter. This is a deviation from the requirement specified in Material Requisition. |
Tender Value
Refer Docs
Closing Date
7 Jun 2021, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
LTHE
LARSEN AND TOUBRO HYDROCARBON ENGINEERING LIMITED, 5TH FLOOR, GATE NO 5, LARSEN AND TOUBRO CENTER, SAKI VIHAR ROAD, POWAI, MUMBAI, MAHARASHTRA 400072
INSTALLATION OF IND RESIDH DEMONSTRATION PLANT AT PANIPAT REFINERY PETROCHEMICALS COMPLEX
2021_REFHQ_135064_1
E1172-U81-SC-TD-063134
Limited
Electrical - All
Supply
180 days
Please refer tender documents
3 documents required · 3 mandatory
Exempted
9 Nov 2021
7 May 2021
8 Jun 2021
7 May 2021
7 Jun 2021
21 May 2021
7 May 2021 - 21 May 2021
120 days
110V AC, 40 kVA, UPS for Instrumentation Loads (DCS/Non-DCS/PLC Loads) Location: New “indResidH“ Substation AC UPS Input 415V AC, 3 phases, 50 Hz, Output: 40kVA, 110V AC 1 -ph & Neutral, 50 Hz, Dual Redundant Parallel UPS (2x100 %) with common bypass transformer. Each UPS system shall have thyristor-based rectifier and IGBT type inverter, static voltage stabilizer, static bypass switch and manual maintenance bypass switch (make before break type), touch screen LCD display. AC UPS shall be free standing, floor mounting type, Dust & vermin proof, Metal clad, Enclosure of IP 42 as minimum suitable for cable entry from bottom, interconnecting cabling between various units of UPS and all other accessories as mentioned in this requisition, Datasheets, single line diagrams. (Location: - “indResidH” Substation - AC UPS room)
Batteries Battery shall be Nickel Cadmium type with battery monitoring system, Battery backup time of each battery bank shall be 60 mins. Battery shall be sized based upon attached AC UPS SLD and IEEE-1115. Batteries shall be complete with battery racks, IP-55 Enclosure battery MCCB / boxes with cable glands and all other accessories as mentioned in this requisition, datasheets and single line diagrams. Battery MCCB box shall be suitable for installation in Zone-2, Gas group IIC, Temperature class T3. Cable length: Supply of Cable from “Battery Charger to Battery MCCB Box and “Battery MCCB box to Battery Bank” shall be in Vendor Scope. Approximate length between “Battery Charger to Battery MCCB Box and “Battery MCCB box to Battery Bank” is 25 meters (final length shall be confirmed during later stage). Location: Battery Room – “indResidH” Substation (Remarks: 1 Set of 100% capacity battery bank common for both each UPS module. Refer attached SLD, Appendix-G in MR)
ACDB: 110V AC, Single Phase, 50 Hz, 25kA for 1 sec, Separate ACDB, Floor mounting Fixed type, IP 42 minimum, Dust and Vermin proof, Metal Clad Enclosure, Suitable for 2 incomers & one Bus coupler along with indications, meters and other components as required, Cable entry from bottom. DP MCCB Protection for incomer & Bus coupler and DP MCB for outgoing feeders. Outgoing feeders shall be as per Appendix-G (Single Line Diagram for AC UPS, Doc. No. E1172-U81-EL-SLD-402203). Cable length: Supply of Cable from “AC UPS” to ACDB” shall be in Vendor Scope. Approximate length between “AC UPS” to ACDB” is 15 meters (final length shall be confirmed during later stage). ACDB shall have front access only. No rear access shall be provided. Location: (Location: - “indResidH” Substation - AC UPS room) (Remark: Refer attached SLD, Appendix-G in MR)
Mandatory Spares shall be as per Material Requisition (Refer Note-3 above)
Supervision of erection, commissioning and testing (Refer Note-7 above) Per diem charges (per person) for 8 hours work on normal working days (Monday to Saturday)
Supervision of erection, commissioning and testing (Refer Note-7 above) Overtime rate/ hour beyond normal 8 hours work on normal working days.
Supervision of erection, commissioning and testing (Refer Note-7 above) Overtime rate/hour for work on weekly off days/ holidays (as applicable at Project site).
Hitachi Hirel Power Electronics Pvt. Ltd.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .