| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.8 CrAccepted-AOC | ₹18.8 Cr | L1 | Accepted-AOC accepted |
| 2 | L2₹21.3 CrRejected-Finance | ₹21.3 Cr | L2 | Rejected-Finance rejected |
| 3 | L3₹21.7 CrRejected-Finance | ₹21.7 Cr | L3 | Rejected-Finance rejected |
| 4 | L4₹21.7 CrRejected-Finance | ₹21.7 Cr | L4 | Rejected-Finance rejected |
| 5 | L5₹23.8 CrRejected-Finance 3 4 520 TO 526 FLAT NO 303 PRAGATHI PRIDE APARTMENT BARKATHPURA HYDERABAD 500027 | HYDERABAD | TELANGANA | 500027 | ₹23.8 Cr | L5 | Rejected-Finance rejected |
Tender Value
₹22.0 Cr
EMD Value
₹32.0 L
Closing Date
3 Jun 2020, 3:00 pmClosed
CCE(RND)SOUTH
The Chief Construction Engineer (RND), PB No.1569, Akbar Road, Secunderabad - 03
PROVISION OF CONSTRUCTION OF INTEGRATED MAINTENANCE FACILITY FOR GSE FOR PROGRAMME MRSAM ARMY AT RCI, HYDERABAD
2020_DRDO_554588_1
83565/CIV/GSE/CON
Limited
Civil Works
480 days
RCI
As per NIT
2 documents required · 2 mandatory
₹3,000
CCE(RND)SECUNDERABAD
₹32.0 L
27 Jul 2020
27 Mar 2020
5 Jun 2020
27 Mar 2020
3 Jun 2020
23 Apr 2020
2 Apr 2020 - 6 Apr 2020
Amount
SUB HEAD - I : EARTH WORK:
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. (a) All kinds of soil.
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge.
Ordinary rock.
Hard rock (blasting prohibited).
Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. (a) All kinds of soil.
Excavation work by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms,lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m.
(a) Ordinary rock.
(b) Hard rock (blasting prohibited).
Credit of Hard rock
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth,consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Supplying and filling in plinth with river sand under floors, including watering,ramming, consolidating and dressing complete.
Supply and filling good earth brought from out side MOD land filling in layer not exceeding 20 cm thickness at all height and depth including levelling, watering compaction etc. all complete (Deduct for 5% voids).
Drilling holein rock with required Dia. As Per Manufacture Specification - Cleaning by Air vaccum cleaner including at all height and level, scaffolding and grouting reinforcement bar with and according to Hilti RE 500 or Wuerth make PE-500 EPOXY CHEMICAL etc. all complete.
(a) 12 MM Dia. Hole 250 mm depth with RE-500 or PE-500 epoxy chemical of Hilti/Wuearth Make or Equivalent.
(b) 16 MM Dia. Hole 250 mm depth with RE-500 or PE-500 epoxy chemical of Hilti/Wuearth Make or Equivalent.
(c) 20 MM Dia. Hole 250 mm depth with RE-500 or PE-500 epoxy chemical of Hilti/Wuearth Make or Equivalent.
SUB HEAD - II : ANTI TERMITE TREATMENT WORK:
Supplying chemical emulsion in sealed containers including delivery as specified. (a) Chlorpyriphos/ Lindane emulsifiable concentrate of 20%.
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : (a) Along the external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per linear metre including drilling and plugging holes etc.: (i) With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration.
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : (a) Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: (i) With Chlorpyriphos/Lindane E.C. 20% with 1% concentration.
SUB HEAD-III : PLAIN AND REINFORCED CEMENT CONCRETE WORK:
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
(a) 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size).
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses,parapets, coping, bed blocks, anchor blocks, plain window sills, fillets,sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing : a) 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size).
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge.“(Note :- Cement content considered in this item is @ 330 kg/cum.“Excess/ less cement used as per design mix is payable/recoverable separately).
(a) All works upto plinth level.
(a) All works above plinth level upto floor V level.
Deduction for not pumping of concrete to site of laying.
Add for using extra cement in the items of design mix over and above the specified cement content therein.
Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete,improve workability without impairing strength and durability as per direction of the Engineer-in-charge. (Note :- Cement content considered in this item is @ 330 kg/cum.Excess/less cement used as per design mix is payable/recoverable separately)
(a) All works upto plinth level.
(b) All works above plinth level upto floor V level.
Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete. a)Thermo-Mechanically Treated bars of grade Fe-500D or more.
Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III): 4 graded stone aggregate 12.5mm nominal size) including Providing & applying a coat of DAMP PROOF membrane approved on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil.
Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer's specification ( per 50 kg cement).
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.
Centering and shuttering including strutting, propping etc. and removal of form for:
(a) Foundations, footings, bases of columns etc. for mass concrete.
(b) Walls (any thickness) including attached pilasters, butteresses,plinth and string courses etc.
(c) Suspended floors, roofs, landings, balconies and access platform.
(d) Lintels, beams, plinth beams, girders, bressumers and cantilevers
(e) Columns, Pillars, Piers, Abutments, Posts and Struts.
(f) Stairs, (excluding landings) except spiral-staircases.
(g) Weather shade, Chajjas, corbels etc., including edges.
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentring at all levels, over a height of 3.5 m, for every additional height of 1 meter or part thereof (Plan area to be measured). (a) Suspended floors, roofs, landing, beams and balconies (Plan area to be measured).
Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
Providing and fixing in position Stainless steel Grade 304 plate-1.0 mm thick as per design for expansion joints. (a) 300 mm wide.
Providing and laying 40 mm wide expansion joints to roof as per details shown in the drawing and filling the same with filler board & back up rod of approved make and top 40 x 20 mm gap from finished surface shall be sealed with THIOFLEX 600 two part, polysulphide sealant, manufactured by Fosroc to BS 4254 :1983 after priming using Primer 7E. The Cost shall inclusive of sealant material, labour for necessary surface preparation, and application and excluding of filler board & back up rod.
SUB HEAD - IV : BRICK WORK:
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : (a) Cement mortar 1:6 (1 cement : 6 coarse sand
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: (a) Cement mortar 1:6 (1 cement : 6 coarse sand).
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : (a) Cement mortar 1:6 (1 cement : 6 coarse sand).
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1:4 (1 cement : 4 coarse sand) including Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry. (a) Cement mortar 1:4 (1 cement : 4 coarse sand).
Brick edging 7cm wide 11.4 cm deep to plinth protection with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 including grouting with cement mortar 1:4 (1 cement : 4 fine sand).
SUB HEAD - V : FINISHING :
Providing of 6mm cement plaster of mix in all surface with cement mortar 1:3 (1 cement : 3 fine sand) at all levels. .
Providing of 12 mm cement plaster of mix in all surface with Cement mortar 1:6 (1 cement : 6 fine sand) at all levels.
Providing of 15 mm cement plaster on the rough side of single or half brick / C.C wall of mix 1:6 (1 cement : 6 fine sand) at all levels.
Providing of 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge.
Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers.
White washing with lime to give an even shade : (a) New work (three or more coats)
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including water thinnable priming coat with cement primer Including with Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
Finishing walls with water proofing cement paint of required shade : (a) New work (Two or more coats applied @ 3.84 kg/10 sqm.
Finishing walls with Acrylic Smooth exterior paint of required shade : (a) New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm).
Applying priming coat:
With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/steel works
Painting with synthetic enamel paint on Steel Body of approved brand and manufacture to give an even shade Two or more coats on new work.
Varnishing on Wooden Surface with varnish of approved brand and manufacture with Two or more coats of glue sizing with copal varnish over an under coat of flatting varnish including with French spirit polishing with Two or more coats on new works including a coat of wood filler.
Providing & fixing chicken wire mesh at the junctions of RCC and C.C , 200mm overlapping on both sides with all necessary hardware etc., complete with guage and mesh size - 20swg and 20mm mesh
SUB HEAD - VI : FLOORING WORK:
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. Make of NITCO Company : Model name Exotica/Maxima series or ,Made of Somany Company : Model name Trecker/Sprinkler series or , Made of Kajaria Company : Model Name GaniliaCrema /Beige/Almono Made of Johnson /Equivalent.
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. (a) 40 mm thick with 20 mm nominal size stone aggregate
52 mm thick cement concrete flooring with concrete hardener topping,under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer's specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.
Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. (a) 18 mm thick.
Extra for making chequers of approved pattern on cement concrete floors,steps, landing, pavements etc.
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : (a) 25 mm thick
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.
Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours White,Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement: 4 Coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including grouting the joints with white cement and matching pigments etc., complete. Make of NITCO Company : Model name Exotica/Maxima series or ,Made of Somany Company : Model name Trecker/Sprinkler series or , Made of Kajaria Company : Model Name GaniliaCrema /Beige/Almono Made of Johnson /Equivalent.
Providing and laying Double Charged vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including grouting the joints with white cement and matching pigments etc., complete. Made of NITCO Company :Model name -Bermuda or Made of Somany ompany :Model name Celestial /Elegance series or Made of Kajaria company :Model name Super Glossy Nanotech K-6016/6018/6019/6101/6012 & Jhonson Make : Quarzet DK & Quarzet HL Or Equivalent a) Size of Tile 600x600 mm.
Providing and laying Double Charged Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1cement: 3 coarse sand), including routing the joint with white cement & matching pigments etc. Made of NITCO Company :Model name -Bermuda or Made of Somany ompany :Model name Celestial /Elegance series or Made of Kajaria company :Model name Super Glossy Nanotech K-6016/6018/6019/6101/6012 , Jhonson Make : Quarzet DK & Quarzet HL Or Equivalent. (a) Size of Tile 600x600 mm.
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : (a) Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. (a) Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Proving and Laying Vaccum dewatered cement concrete 1:1.5:3(1 cement ;1.5 coarse sand and 3 graded aggregate of 20mm)flooring in alternate panels of 3x4m including reinforcement 8mm at 200 c/c .Vaccum dewatered technic to accelerate the evaporation of excess water in green concrete using rigid or flexible suction mat incorporating filter layer and vaccum generators (80 to 90% vaccum to be applied at the rate of 3 to 5 minute per 25mm depth ) all as per specification including cutting grooves 4mmx20mm deep in flooring with diamond saw cutting machine before the concrete is seven days old including providing and filling the grooves with polysulphate sealant of approved make or equivalent (modified semi rigid epoxy joint filler ) including cost of required the panel shuttering work with steel channel and as per direction of Engineer-In- charge.The work shall be carried out by specialist agency approved by Engineer -in charge
Epoxy Flooring : Preparing the concrete floor surface using captive shot blasting machine .Cut open all construction joints to fill with epoxy putty using Nitocote VF or Equivalent .Same treatment will be carried out to treat shrinkage joints.Providing and laying one coat of Nitoprime 25 or equivalent .Providing and applying Nitoflor SL or equivalent conductive undercoat and overcoated with Notoflor SL or equivalent conduvtive top coat in 3 mm thick over primed surface at 7.5 sq mt per pack and finishing as per Forsroc specification .When measured for surface resistance in accordance with BS2050:1978 (A-1984) and DIN EN 1081 ,the static conductive topping including under coat shall be in range of 50-1000 K ohms . When tested for static decay as per Federal test method 101B ,Method 4046, the static conductive tppic shall take not more than a time of 0.01 seconds to decay with +5KV peak charge to 0% .The surface resistance of the conductive undercoat shall be in the range of 3-9 K ohms .Note : Copper strip will be provided to connet earthing point for safe discharge of charges .Make : Forsroc or Equivalent.
Providing and fixing 18 mm thick gang saw cut, mirror polished,premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size,approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement,mixed with matching pigment, epoxy touch ups, including rubbing, curing,moulding and polishing to edges to give high gloss finish etc. complete at all levels. a) Granite of any colour and shade. i) Area of slab over 0.50 sqm.
Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc.complete as per design approved by Engineer-in-Charge. a) Granite work.
Extra for providing opening of required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth. (a) Granite Stone of approved shade.
SUB HEAD - VII : WOOD WORK / ALUMINIUM WORK :
Providing and fixing pressed steel door frames conforming to IS: 4351,manufactured from commercial mild steel sheet of 1.60 mm thickness, including jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm,pressed mild steel welded or rigidly fixed together by mechanical means, with mortar guards,lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge: a) Profile C - 125 X 60 X 1.6 mm i) Fixing with adjustable lugs with split end tail to each jamb.
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. (a) 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws including Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters.
Extra for Not Providing and fixing IS : 12817 marked stainless steel butt hinges (heavy weight) with stainless steel screws etc. complete : (a) 125 x 64 x 2.5 mm.
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness .The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat.Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
Providing and fixing : (a) 30 mm thick Fiberglass Reinforced Plastic (F.R.P.) flush door shutter in different plain and wood finish made with fire retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate all around, with suitable wooden blocks inside at required places for fixing of fittings and polyurethane foam (PUF)/ Polystyrene foam to be used as filler material throughout the hollow panel, casted monolithically with testing parameters of F.R.P. laminate conforming to table - 3 of IS: 14856, complete as per direction of Engineer-in-charge.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling,C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : a) For fixed portion. i) Powder coated aluminium (minimum thickness of powder coating 50 micron):
For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) a) Powder coated aluminium (minimum thickness of powder coating 50 micron).
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS:12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineerin-charge. (a) Pre-laminated particle board with decorative lamination on both sides
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):
(a) With float glass panes of 5.50 mm thickness.
Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. (a) With stainless steel cover plate minimum 1.25 mm thickness.
Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. (a) Fixed to openings /wooden frames with rawl plugs screws etc.
Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868),transparent or dyed to required colour or shade, with nuts and screws etc. complete : (a) 300x16 mm.
Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : a) 150x10 mm.
Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : a) 125 mm.
Providing and fixing aluminium hanging floor door stopper, ISI marked,anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. a) Twin rubber stopper.
Providing and fixing of rubber nylon door buffer (dia of 40mm and 50mm long) on wall with rowl plug and screw.
Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm), with necessary accessories and screws etc. complete.
Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame,sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc.After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes shall be paid separately)
Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerancein dimension i.e. in depth & width of profile shall be acceptable. Variation in profile dimension in higher side shall be accepted but no extra payment on this account shall be made.
(a) Casement window single panel with S.S. friction hinges (300 x 19 x 1.9 mm), made of (small series) frame 47 x 50 mm & sash 47 x 68 mm both having wall thickness of 1.9 ± 0.2 mm and single glass pane glazing bead of appropriate dimension. (Area of window upto 0.75 sqm.) (Make: Fenesta/Kommerling).
(b) Casement window double panels with top fixed with S.S. friction hinges (350 x 19 x 1.9 mm) made of (small series) frame 47 x 50 mm, sash 47 x 68 mm & mullion 47 x 68 mm all having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension. ( Area of window upto 2.50 sqm). (Make: Fenesta/Kommerling).
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double action hydraulic floor spring type fixing rrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-incharge (Door handle, lock and stopper etc.to be paid separately).
Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0 mm thick & 2100 mm long with SS screws etc .complete as per direction of Engineer-in-Charge.
(a) Polyester powder coated minimum thickness 50 micron aluminium tubular handle bar.
Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete.
SUB HEAD - VIII : STEEL WORK:
Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Structural steel work riveted, bolted or welded in built up sections,trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer. (a) Using M.S. angels 40x40x6 mm for diagonal braces.
Supplying and fixing of Manual/Motorised Rolling Shutter , Curtain made of single skinned Galvalume steel laths with natural finish , Pressed galvalume steel hood & motor cover with natural finish, CE Certified CRS Compact Gear P.R.C. Make Indirect Drive Operator with Three station push button with deadmand control of approved make.
Providing and fixing of Galvanized steel flush doors with following specification : The door frame shall be single rebate profile of size 100 X 57 mm made out of 1.60 mm thick galvanized steel. The shutter shall be 45 mm thick fully flush made out of 1.20 mm thick galvanized steel both sides, unfill material shall be resin bonded honey comb craft paper for rigidity and sound insulations. Door frames and shutters shall be finished with two coats of epoxy zinc phosphate primer and finished paint shall be in polyurethane aliphatic grade for superior addition, scratch resistant etc. Inclusive of approval of shop drawings, gaskets & all other hardware etc.all complete. (Make : Gandhi Automation Pvt. Ltd. , Shaktimet Doors Pvt. Ltd or equivalents) Clear Size of doors shall be 3.0 m X 6.0 m to 5.0m X 6.0m
Providing and fixing mild steel round holding down bolts with nuts and washer plates complete.
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
SUB HEAD - IX : ROOFING & WATER PROOFING:
Supplying and fixing of precoated Zincalume / Galvalume sheet roofing of 0.5mm TCT -AZ-150, 550 mpa (Alumunium Zinc Alloy coating of 150 gms, per sqm total on both sides) as per AS: 1397 in cover width of 1000-1020 mm, (size, shape and pitch of corrugation as approved by Engineer-in-charge).The end rib shall be designed for anti-capillary action, to avoid any seepage of water through the lateral overlap. The feed material is manufactured out of nominal 0.45 mm Base Metal Thickness (BMT), Hi-strength steel with min. 550 MPa yield strength. The steel sheet shall be fastened with 25 μm zinc-tin alloy coated, Hex head, self-drilling screw as per AS 3566-2002 Class 3 fasteners of approved make with EPDM washer as per the requirement considering the profile shape and design load. Sheet should have protective guard film of 25 microns minimum to avoid scratches while transportation and should be supplied in single length upto 12meter or as directed by Engineer-in-charge.
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre,shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I.
wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills,diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : (a)12.5 mm thick tapered edge gypsum moisture resistant board. (Make : Gproc , L Strong , Armstrong)
Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc.
Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. (a)12.5 mm thick square edge PVC Laminated Gypsum Tile of size 595x595 mm, made of Gypsum plasterboard, manufactured from natural gypsum as per IS 2095 part I and laminated with white 0.16mm thick fire retardant PVC film on the face side and 12micron metalized polyester on the back side with all edges sealed with the face side PVC film which goes around and wraps the edges and is bonded to the edges and the back side metalized polyester film so as to make the tile a completely sealed unit.
Providing and laying integral cement based treatment for water proofing on horizontal surface at all depth below ground level for under ground structures as directed by Engineer-in-Charge and consisting of : i) Ist layer of 22 mm to 25 mm thick approved and specified rough stone slab over a 25 mm thick base of cement mortar 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound conforming to IS:2645 in the recommended roportion over the leveling course (leveling course to be paid eparately). Joints sealed and grouted with cement slurry mixed with water proofing compound. ii) 2nd layer of 25 mm thick cement mortar 1:3 (1 cement: 3 coarse sand) mixed with water proofing compound in ecommended proportions. iii) Finishing top with stone aggregate of 10 mm to 12 mm nominal size spreading @ 8 cudm/sqm thoroughly embedded in the 2nd layer. (a) Using rough kota stone.
Providing and laying integral cement based treatment for water proofing on the vertical surface by fixing specified stone slab 22 mm to 25 mm thick with cement slurry mixed with water proofing compound conforming to IS:2645 in recommended proportions with a gap of 20 mm (minimum) between stone slabs and the receiving surfaces and filling the gaps with neat cement slurry mixed with water proofing compound and finishing the exterior of stone slab with cement mortar 1:3 (1 cement : 3 coarse sand) 20 mm thick with neat cement punning mixed with water proofing compound in recommended proportion complete at all levels and as directed by Engineer-in-charge : (a) Using rough Kota stone
Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen and the like consisting of: (i) Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water proofing compound conforming to IS 2645 in recommended proportions including rounding off junction of vertical and horizontal surface. (ii) IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound in recommended proportion including rounding off junction of vertical and horizontal surface. (iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg. per sqm of area. (iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and pasted to each other with bitumen @ 1.7 kg/ sqm).
Providing and Placing in position suitable PVC water stops conforming to IS : 12200 construction and expansion joints between two rcc members and fixed to the reinforcement with building wire before pouring concrete etc. complete. (a) Serrated with central bulb (225 mm wide , 8-11 mm thk.)
Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs,balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs.
(c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. (d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep.
(e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : (i) With average thickness of 120 mm and minimum thickness at khurra as 65 mm.
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. (a) 110 mm diameter.
SUB HEAD - X : SANITARY INSTALLATIONS WORK:
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required : (Make: JAQUAR , SOLO SERIES , Modle No.: SLS-WHT-6751P for W.C & SLS-WHT-6201 for Flushing Cistern).
Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern,with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass,including painting of fittings and cutting and making good the walls and floors wherever required : (a) Single half stall urinal with 5 litre P.V.C. automatic flushing cistern.
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: (a) White Vitreous China Table Top Basin (JAQUAR Cat. No. -FLS-WHT-0539.
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm,including painting of fittings and brackets, cutting and making good the walls wherever required : (a) Kitchen sink with drain board. (i) 510x1040 mm bowl depth 225 mm.
Providing and fixing G.I. inlet connection for flush pipe connecting with W.C. pan.
Providing and fixing CP Brass 32mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in- charge.
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
Providing and fixing toilet paper holder : (a) C.P. brass.
Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. (a) 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gms.
Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : (a) 15 mm nominal bore (Make : Jaquar , Model No, - CON-037KN)
Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. (a) 15 mm nominal bore. (Make : Jaquar , Model No, - CON-107KN)
Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931. (a)15 mm nominal bore.
Providing and fixing S.S. grating, including setting in floor with cement mortar 1:3. with all complete as per direction of Engineer - in - Charge. (Make: KINGSTON , Accessories Series, Modle No.: AGR-ACS-39 or Equivalent).
Providing and Fixing Health Faucet Jaquar Cat. No. 573 (Allied Series) or equivalent make Kingston-AGR ACS 49, KOHLER Cat. No. 12925IN-CP (HEALTH FAUCET W/WHITE SDSPRAY, M HOSE) with flexible pipe and wall hook with each European W.C. Pan.
SUBHEAD - XI : WATER SUPPLY:
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall
(a) 20 mm outer dia pipes
(b) 25 mm outer dia pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.
(a) 15 mm nominal outer dia Pipes
(b) 20 mm nominal outer dia Pipes
Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External Work
(a) 25mm nominal outer dia pipes
(b) 40mm nominal outer dia pipes
(c) 65 mm nominal inner dia Pipes
(d) 80mm nominal outer dia pipes
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :
(a) 25 mm nominal bore.
(b) 32 mm nominal bore.
(c) 40 mm nominal bore
(d) 65 mm nominal bore
(e) 80 mm nominal bore
Providing and fixing ball (brass) valve of approved quality. High or low pressure, with plastic floats complete: (a) 25 mm nominal bore
Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design : (a) With common burnt clay F.P.S (non modular) bricks of class designation 7.5.
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. (a) Circular tank.
Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : (a) With common burnt clay F.P.S (non modular) bricks of class designation 7.5.
Providing & fixing BUTTERFLY VALVE with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified (a) 80 mm dia
Providing and fixing C.I. double acting air valve of approved quality with bolts, nuts, rubber, insertions etc. complete (The tail pieces, tapers etc if required will be paid separately). (a) 50 mm dia.
Providing and fixing in position C.I 560 mm dia cover with frame (Heavy duty) manhole cover of approved quality . Circular shape 560 mm internal dia.
SUBHEAD - XII : SOIL WASTE AND VENT PIPE AND FITTINGS WORK:
Providing and fixing SWR uPVC pipes (Type-B) confirming to IS 13592 : 1992 complete with all fittings e.g. plain or door bends, junctions, cowls, offsets, access pieces etc. jointing with rubber rings and solvent cement including fixing the pipes on wall face with MS galvanized holder bat clamps or suspended below ceiling with MS galvanized hangers/supports and fasteners all as approved by the engineer in charge including Cutting holes in walls, floors excavation, refilling and disposal of surplus earth wherever required and making good . The rates shall be inclusive of painting of all supports and clamps with a coat of red oxide primer and two or more coats of synthetic enamel paint of approved colour and Quality to give an even shade including surface preparation.(Sample of holder bat clamps,hangers / supports to be approved by the Engineer-in-Charge.) (a) 110 mm dia.
Providing and fixing uPVC deep seal 'P' or 'S' / Nahani trap of self cleansing design with or without vent arm with provision for connecting uPVC inlet fitting complete including cost of cutting and making good the walls and floors wherever required. (a) For 110mm inlet and 80mm outlet.
Providing and fixing uPVC threaded waste pipes (I.S:4985-2000) Class - 6 including all fittings e.g bends, junctions, elbows, tees, offsets etc. jointing with screwed joints including cutting holes in walls, floors excavation, refilling and disposal of surplus earth wherever required and making good.
(a) 32 mm nominal bore.
(b) 50 mm nominal bore.
(c) 80 mm nominal bore.
SUB HEAD - XIII: EXTERNAL WATER SUPPLY SYSTEM:
Providing and fixing G.I. pipes of following sizes complete with G.I. fittings including trenching and refilling etc.
a) 80 mm dia nominal bore
b) 65 mm dia nominal bore
c) 50 mm dia nominal bore
Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete :
a) 25 to 40 mm nominal bore.
b) 50 to 80 mm nominal bore.
Providing and fixing gun metal gate valve with C.I. wheel of approvedvquality (screwed end) :
a) 80 mm nominal bore
b) 65 mm nominal bore
c) 50 mm nominal bore
Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :
a) With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
SUB HEAD - XIV : ROAD WORK AND WATER HARVESTING:
ROAD WORK:
Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead upto 50 metres.
Supply and laying of moorum (of plasticity index <6) in road embankment to proper grade and level in layer of 150mm thickness and consolidating with road roller to achieve the modified proctor density of 97%, all complete as per drawing, specficiations and directions of Engineer-in-Charge.
Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all eads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge. (a) With material conforming to Grade-I (size range 75 mm to 0.075 mm) having CBR Value-30.
Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paverfinisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge.
Providing and applying tack coat using hot straight run bitumen of grade VG - 10, including heating the bitumen, spraying the bitumen with mechanically operated spray unit fitted on bitumen boiler,cleaning and preparing the existing road surface as per specifications : (a) On W.M.M. @ 0.75 Kg I sqm.
Providing and laying Dense Graded Bituminous Macadam using crushed stone aggregates of specified grading, premixed with bituminous binder and filler, transporting the hot mix to work site by tippers, laying with paver finisher equiped with electronic sensor to the required grade, level and alignment and rolling with smooth wheeled, vibratory and tandem rollers as per specifications to achieve the desired compaction and density, complete as per specificatons and directions of Engineer-in-Charge. (a) 50 to 100 mm average compacted thickness with bitumen of grade VG-30 @ 5% (percentage by weight of total mix) and lime filler @ 2% (percentage by weight of Aggregate) prepared in Batch Type Hot Mix Plant of 100-120 TPH capacity.
Providing and laying Non Pressure NP-2 class R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete
(a) 150 mm dia RCC pipes.
(b) 300 mm dia RCC pipes.
(c) 450 mm dia RCC pipes.
(d) 600 mm dia RCC pipes.
Painting road surface marking with adequate nos of coats to give uniform finish with ready mixed road marking paint conforming to IS : 164, on bituminous surface in white/yellow shade, including cleaning the surface of all dirt, scales, oil, grease and foreign material etc. complete. (a) New work (Two or more coats).
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).
WATER HARVESTING:
Providing Rain water harvesting pit of size 2m dia and 2.5m depth. The pit shall have 750mm of 40mm stone agreegate at the bottom over which there shall be 750mm of 40mm of stone aggregate and 1000mm of coarse sand filling respectively. Brick work allround the periphery of the pit 300mm below ground and 150mm of above.
SUB HEAD -XV : ARBORICULTURE / LANDSCAPING:
Supply of grass and planting by dibbling the area including watering & Maintenance of Lawn for 30 days or more till grass forms a thick lawn cushion free from weeds. With Bermuda Grass (15 cm x 15 cm apart) Including required filling with red soil or Agriculture good earth with One Year Maintenance after Completion of Work.
Trees:- Digging of pits of size 1x1x1m and refilling with good agriculture soil and well decomposed cattle manure in 4:1 ratio. Supply and planting of approved Tree species of healthy grownup saplings with good root system. Saplings should be of minimum 4 ft height from ground level after plantation. Maintenance includes, regular watering, de-weeding, loosening of soil fortnight, manuring with cattle manure and fertilizer, training, pruning, staking and spraying of insecticide and fungicide, Including One Year Maintenance after Completion of Work.
Shrubs: Digging of pits of size 0.60x0.60x0.60m and refilling with good agriculture soil and well decomposed cattle manure in 3:1 ratio. Supply and planting of approved Shurbs species of healthy grownup saplings with good root system. Saplings should be of minimum 2 ft height from ground level after plantation. Maintenance includes, regular watering, de-weeding, loosening of soil fortnight, manuring with cattle manure and fertilizer, training, pruning, staking and spraying of insecticide and fungicide, Including One Year Maintenance after Completion of Work.
Hedges: Digging of trenches of size 0.30 x 0.30m (width & depth) and refilling with good agriculture soil and cattle manure in 4:1 ratio. Maintenance includes, regular watering, de-weeding, loosening of soil fortnight, manuring with cattle manure and fertilizer, pruning, shaping and spraying of insecticide and fungicide, Including One Year Maintenance after Completion of Work.
Flower Beds: Digging upto 0.10m refilling with good soil and cattle manure in 3:1 ratio. Preparation of beds supply and planting of of healthy grown up plant material. Maintenance includes regular watering, de-weeding, manuring with manure and fertilizer.pruning, shaping and spraying of insecticide and fungicide, Including One Year Maintenance after Completion of Work.
Potted Plants: Supply and maintaining the Indoor and Outdoor potted plants in a good healthy and disease free condition of various varieties and in different type of pots.
Clearing jungle including uprooting of trees and saplings of girth 30 cm to 50 cm and replanting of uprooting trees as per direction of Engineer - in - charge.
SUB HEAD XVI : FURNITURE:
Supply and Laying of CABINETS SERIES PERFOM A130 F AA 1400 65 04 , Rack with bins for Fastener storage , Cabinet with 11 shelves depth 500 mm load capacity 100 kg , Load capacity: 800 kg. , Dimensions mm 1023(L) x 555(D) x 2000(H) Including: 3 size 272-4 blue stacking containers, 55 blue Multibox of size 3551 11 blue Multibox of size 3051, 77 guides rails for Multibox 66 safety rods for Multibox Make : Godrej or Equivalent.
Supply and Laying ESD Work station , Electrical Workstation with ESD Worktop , Workstation of overall dim mm: 1552(L) x 820(D) x 2220(H) - 1 ESD worktop with frame adjustable in height from 720 to 1138 mm - 1 cabinet with 3 Drawers each equipped with separate Locks - 1 perforated panels for Hanging Tools - 1 Set of 19 Standard Galvanized Hooks for Hanging Tools - 1 tilting shelf of Depth 220 mm 9 blue containers COMPAT mes. 2 art. FP CO C002A00 51 04 - 1 Power raceway with Sockets and Switches - 1 ALuminium Slide track with supports for hanging Overhead Lights - 1 Philips Overhead Light Make : Godrej or Equivalent.
Supply and placement of ARISTO TBL 1800 LH RU 1200 PDL 1800 x2100 x 750 mm of Make : Godrej or Equivalent.
Supply and placement of BRAVO High Back of Make : Godrej or Equivalent.
Supply and placement of BRAVO Visitor Chair of Make : Godrej or Equivalent.
Supply and placement of BRAVO Visitor Chair of Make : Godrej or Equivalent.
Supply and Placement of ARISTO TBL 1650 LH RU 1200 PDL 1650 x 1950 x 750 mm. of Make : Godrej or Equivalent.
Supply and placement of BRAVO Mid Back Chair of Make : Godrej or Equivalent.
Supply and Placing Large size steel almiraha full height of Make Godrej Slim Line with all complete.
Supply and placement of Documentation Rack (1829 x 915 x 458 mm) of Make : Godrej or Equivalent.
Supply and placement of Unlearn 2 Seater CPU (1500 x 600 x 680) of Make : Godrej or Equivalent.
Supply and placement of DIVA Visitor W/o Arms of Make : Godrej or Equivalent.
SUB HEAD - XVII : EXTERNAL SEWERAGE SYSTEM:
Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete:
(a)100 mm diameter.
(b)150 mm diameter.
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all around S.W pipe including bed concrete as per standerd design
(a)100 mm diameter.
(b)150 mm diameter.
Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: (a)150 x 100 mm size P type. (i)With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : (a) 200 mm dia RCC pipe
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) up to haunches of RCC pipes including bed concrete as per standard design : (a) 200 mm Dia.
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions,total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) : (a) With common burnt clay F.P.S. (non modular) bricks of class designation 7.5.
Extra for depth for manholes : (a) Size 90x80 cm. (i) With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
SUB HEAD - XVIII : EXTERNAL DRAINAGE WORK:
Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. (a) All kinds of soil.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: (a) Cement mortar 1:6 (1 cement : 6 coarse sand)
Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement. (a) 20 mm cement plaster.
SUB HEAD - XIX : EOT CRANE WORK:
Part-I: - Supply 20 Tonne EOT Crane:
Design, manufacture and supply of Double Girder EOT Cranes with all speeds 'VVVF' Drive control and micro speed arrangement for Hoist, CT & LT as per the specifications given in Annexure-IV and conforming to IS 807/IS 3177 and other relevant IS standards of the latest revisions as shown below complete with all taxes, duties and other charges such as transportation to site, loading and unloading at stores/building, where to be installed etc.,movement of material to work spot including the cost of paint as required. The Crane shall be designed for earthquake and sesmic qualification. Span to be measured by the Bidder at Site and it shall be his sole responsibility to provide span suitable.
Supply of 20 Ton capacity Double Girder crab type EOT Crane with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revision. All drives should be provided with alternative parallel path with DOL starter for main speed only. Building : Maintenence Building-1No Span: 20 + 0.5 mts Lift: 6 mts. Bay length: 80 mts.
Supply of shrouded bus bar system with double shoe copper current collections system complete with support tracks, cable loops, junction boxes and cable from main supply point to crane festoons with all necessary fixtures.
Supply of material for Rails section 50 Square bar of prime material in standard length, complete with mounting arrangement at the building over the crane girder including painting of rails with approximate colour code as approved by the dept.
Part-II: - Erection, testing and commissioning :
Erection, testing and commissioning of EOT crane and other allied items mentioned in above item of Part-I as per the relevant IS standards and as mentioned in the technical specifications given in Annexure-III of this Tender Enquiry.
Erection, testing and commissioning of 20 Ton capacity crab type EOT crane mentioned above of Part-I as per the relevant IS standards inclusive of installation of complete Crane completion of all electrical and mechanical works including performance tests with No load, Full load and over load testing as per the approved QA Plan etc complete.
Erection testing and commissioning of shrouded type current collection system complete as per the item mentioned above over the crane bay including tapping of supply for electrical panel testing & handing over the crane as per the approved QA plan etc complete.
Erection, testing & commissioning of Rail section 50 Square bar mentioned in above item with mounting arrangement and fixing hardware etc., complete over the bay length to match the span of the crane within the permissible accuracy levels for span in height variation as per the QA Plan etc complete.
Part-I: - Supply EOT CRANE 5.0 Tonne:
Design, manufacture and supply of Double Girder EOT Cranes with all speeds 'VVVF' Drive control and micro speed arrangement for Hoist, CT & LT as per the specifications given in Annexure-IV and conforming to IS 807/IS 3177 and other relevant IS standards of the latest revisions as shown below complete with all taxes, duties and other charges such as transportation to site, loading and unloading at stores/building, where to be installed etc.,movement of material to work spot including the cost of paint as required. The Crane shall be designed for earthquake and sesmic qualification. Span to be measured by the Bidder at Site and it shall be his sole responsibility to provide span suitable.
Supply of 5 Ton capacity Double Girder crab type EOT Crane with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revision. All drives should be provided with alternative parallel path with DOL starter for main speed only. Building : Maintenence Building-1No Span: 20 + 0.5 mts Lift: 6 mts. Bay length: 80 mts.
Supply of shrouded bus bar system with double shoe copper current collections system complete with support tracks, cable loops, junction boxes and cable from main supply point to crane festoons with all necessary fixtures.
Supply of material for Rails section 50 Square bar of prime material in standard length, complete with mounting arrangement at the building over the crane girder including painting of rails with approximate colour code as approved by the dept.
Part-II: - Erection, testing and commissioning :
Erection, testing and commissioning of EOT crane and other allied items mentioned above of Part-I as per the relevant IS standards and as mentioned in the technical specifications given in Annexure-III of this Tender Enquiry.
Erection, testing and commissioning of 5 Ton capacity crab type EOT crane mentioned above of Part-I as per the relevant IS standards inclusive of installation of complete Crane completion of all electrical and mechanical works including performance tests with No load, Full load and over load testing as per the approved QA Plan etc complete.
Erection testing and commissioning of shrouded type current collection system complete as per the item mentioned above over the crane bay including tapping of supply for electrical panel testing & handing over the crane as per the approved QA plan etc complete.
Erection, testing & commissioning of Rail section 50 Square bar mentioned above with mounting arrangement and fixing hardware etc., complete over the bay length to match the span of the crane within the permissible accuracy levels for span in height variation as per the QA Plan etc complete.
SUB HEAD - XX : WATER COOLER :
Supply , installation testing and commissioning of storage water cooler with storage capacity of 80 liters and cooling capacity of 40 liters suitable for operation on 230V +10% , 50 HZ, full stainless steel body including multistorage RO Purification system , 2 KVA voltage stabilizer etc complete Make Wate Cooler : Voltas / Blue Star / Usha. Water Purifier : Eureka Forbes / Kent / ION Exchange. Stabilizer : Keeline / V- Guard
SUB HEAD - XXI : FIRE FIGHTING SYSTEM :
Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required : Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered with anti vibration pads. (a) 2850 lpm at 88 m Head.
Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft,mechanical seal conforming to IS 1520. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. (a) 2850 lpm at 88 m Head.
Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. (a) 180 lpm at 88 m Head.
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
a) 25 mm dia
b) 32 mm dia
c) 40 mm dia
d) 50 mm dia
e) 65 mm dia
f) 80 mm dia
g) 100 mm dia
h) 150 mm dia
i) 200 mm dia (wall thickness 6.3 mm)
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : (a) Single headed Gunmetal.
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
a) 40 mm dia
b) 50mm dia
c) 65 mm dia
d) 80 mm dia
e) 100 mm dia
f) 150 mm dia
g) 200 mm dia
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :
a) 40 mm dia
b) 50mm dia
c) 65 mm dia
d) 80 mm dia
e) 100 mm dia
f) 150 mm dia
g) 200 mm dia
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts,washers etc.as required :
a) 40 mm dia
b) 50mm dia
c) 65 mm dia
d) 80 mm dia
e) 100 mm dia
f) 125 mm dia
g) 150 mm dia
h) 200 mm dia
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.
a) 80 mm dia
b) 100mm dia
c) 150mm dia
d) 200mm dia
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : a) Gun Metal
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585. 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. a) 30 m.
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : a) Gun metal.
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : a) 4 way - 150 mm dia M.S. Pipe.
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. a)150mm dia.
Supply, laying, testing and commissioning of centrifugally Cast Ductile Iron pipes conforming to IS 8329:2000 class K9, with Cement Mortar Lining (CML) inside as per IS 455:2989 along with Bituminous coating outside suitable for socket and spigot type (DISS) joints for following sizes and testing the joints for leakage (if any) and making good hydrant system. (a) 150 mm Dia.
Supply, fixing, testing and commissioning of centrifugally Cast Ductile Iron fittings/Specials (Socket and Spigot type) conforming to IS 9523: 2000, Class K9, with Cement Mortar Lining (CML) as per IS 455: 1989 inside and bituminous coated outside ISI marked such as Bends, Elbows, Tees, Flanged Spigots, Collars, flanges (flange rating PN 16) etc testing the joints for leakage (if any) and making good hydrant system.
(a) All Socketed Tee, 150 mm x 150 mm x 150 mm dia
(b) Double Socketed Tee with Flanged Branch, 150 mm x 150 mm x 100 mm dia
(c) All Socketed 90deg bend, 150 mm dia
(d) All Socketed 45deg bend, 150 mm dia
(e) All socketed 22.5deg. Bend, 150 mm dia
(f) Reducer socket, 150 mm x 100 mm
(g) Socketed collar, 150 mm dia
(h) Flanged Socket, 150 mm dia
(i) Flanged Spigot,150 mm dia
Providing Push-on-joints to the above ductile cast iron pipes and specials including cost of jointing materials & testing of joints: (a) 150 mm Dia.
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : a) 300 mm dia. R.C.C. pipe
SUB HEAD - XXII : COMPRESSED AIR SYSTEM:
Supply ,Installation,testing and Commissioning of contact cooled screw air compressor of 250CFM capacity at working pressure of 7.5bar including Air cooled air cooler & Oil cooler,star delta starter,microproccessor based intellisys control panel mounted on common skid.
Supply,Installation,Testing & Commissioning of Air Dryer of Capacity 282 CFM with working pressure of 7-14 bar.
Supply,Installation,Testing & Commissioning of verical Air reciever with standard accessories like pressure gauge,safety valve,drain valve etc complete with max working pressure of 10kg/cm2.
Supply, Installation, Testing and of handing over of reciprocating lubricated 2 stage air cooled industrial air compressor , piston displacement-90 CFM to 110 CFM with FAD not less than 75-80 CFM and max pressure 12 kg/sq.cm complete with electric motor inter cooler, suction filter, electrically operated unloader, belt guard, mounted on MS skid suitable for foundation. Oil level switch shall be provided with oil for first 50 hrs oil change. -Ingersoll-Rand.
Supply, Erection, Testing & Commissioning of Following items SS Tubes / Pipes, Valves & Fittings.
a) 1/2"SS Tube incl. supports
b) 1/4"SS Tube incl.supports
c) 1/2" SS BALL VALVE
d) 1/4"SS BALL VALVE
e) SS Union TEE-1/2"OD
f) SS Reducing Union Tee-1/2"x 1/2"x1/4"
g) SS Union-1/2"OD
h) SS Union Elbow-1/2"OD
i) SS Reducing Union- 1/2"x1/4"OD
j) SS Tube Cap-1/2"OD
k) SS Union Tee-1/4"OD
l) SS union-1/4"OD
m) SS Tube Cap-1/4"OD
SUB HEAD - XXIII : HVAC WORK:
Water Chilling Unit: Supply, installation, testing & commissioning of modular type scroll type air cooled water Chilling machine each having minimum nominal cooling capacity as mentioned below. Modules shall operate in master slave combination with automatic run time equalization between the modules. Nominal conditions: Cooling: LWT 7 Deg C, Water Flow 0.172 cu mtr/(h.kW) & 41 Deg C outdoor temperature DBT, with Minimum COP 3.35. Mutiple compressors in hermetic construction only as per OEM design, complete as per specifications. Suitable Nos & suitable capacity squirrel cage induction motor with class 'F' insulation suitable for operation on 415 volts +10% , 50 Hz, A.C. supply. Suitable Nos. & suitable capacity starter in IP 55 protection. First charge of R410 A refrigerant and oil duly charged at factory. 1 No. - Matching Air Cooled condenser with copper tubes and aluminium fins and 2 speed fans for noise control. 1 No. - Matching Cooler of Shell and Tube / BPHE type as per OEM standard. 1 Lot - Refrigerant piping fittings, valves, accessories to inter connect compressor, condenser, chiller and expansion valve.
1 Set - Control panel with display comprising of Controls. It shall also be equipped with protection and monitoring devices such as H/L Pressure switch/ Thermal and Current Overload Protector. 1 Lot - DP/ Flow switches at inlet and outlet of chiller, water drain & air purge valves, wherever required. Lot- suction line and chiller insulation. Lot-frame work for mounting the above condenser, chiller, compressor and motor with base plate complete with antivibration pads/ springs. Lot- Initial/ first charge of refrigerant gas & compressor oil duly charged at factory. Lot- RCC/ cement concrete foundation for equipment. Fins shall be 10-12/inch with hydrophobic coating to give 3-5 times higher corrosion resistance. Package mounted Electical suitable Star Delta starters for compressor motors along with No volt coil, overload releases & single phase prevention devices other safeties & controls Electrical wiring and interconnecting control wiring for motors, starters & protective devices. (a) Scroll Chiller- 35 TR (Actual at Ambient Temperature ) (3W+1S)
AIR SOURCE WATER HEATER: Supply, Installation, Testing and Commissioning of electrically operated modular type Air Source Hot Water Generator of following nominal capacity having Controller and Thermostat so that required qty. of hot water is generated at required temperature with nominal variation, including necessary electrical panel with automatic Controls including inlet and outlet connections and suitable for outdoor installation (Makes- Daikin Mcquay , Carrier , York ) Modular scroll type air source water heating machine; modules shall operate in master slave combination with automatic run time equalization between the modules. Nominal Design conditions: Outdoor DB/WB temperature 20 Deg C/ 15 Deg C, initial water tank temperature 15 Deg C & Final Tank Temperature 55 Deg C, Minimum COP 4.35. The equipment shall be capable of operation from -20 to 43 Deg C DB ambient temperature. Suitable Nos & suitable capacity squirrel cage induction motor with class 'F' insulation suitable for operation on 415 volts +10% , 50 Hz, A.C. supply. Suitable Nos. & suitable capacity starter in IP 55 protection. First charge of R410 A refrigerant and oil duly charged at factory.
1 No. - Matching Air Cooled condenser with copper tubes and aluminium fins 1 No. - Matching Water Side heat exchanger of Shell and Tube / BPHE/ Co Axial Tube in Tube type as per manufacturer's design. 1 Lot - Refrigerant piping fittings, valves, accessories to inter connect compressor, condenser, chiller and expansion valve. 1 Set - Control panel with display comprising of Controls. It shall also be equipped with protection and monitoring devices such as H/L Pressure switch/ Thermal and Current Overload Protector. 1 Lot - Tank, Pumps DP/ Flow switches at inlet and outlet water drain & air purge valves, wherever required. Lot- suction line and required insulation. Lot-frame work for mounting the above with base plate complete with antivibration pads/ springs. Lot- Initial/ first charge of refrigerant gas & compressor oil duly charged at factory. Lot- RCC/ cement concrete foundation for equipment. Heating capacity : 80 KW Actual Flow Rate : 64 Usgpm (a) Air Source HWG as Above (2W+1S).
Chilled Water Primary Pumps : Supply, Installation, Testing, Commissioning and handing over of Vertical inline split coupled Pump of capacity 92 USGPM at 30 Meters Head fitted with suitable Motor (TEFC and IP 55) chilled water including mechanical seal and coupling guard and ss impeller necessary accessories etc complete. Suitable Nos & suitable capacity squirrel cage induction motor with IE5 class 'F' insulation suitable for operation on 415 volts +10% , 50 Hz, A.C. supply. max speed of pump shall be 3000 RPM. 3 working and 1 standby, Suction guide and Triple Duty valve shall be supplied along with the pumps,Each pump shall have Variable Frequency Drive integrated to motor , with IP 55 protection and isolaton switch. The VFD shall comply with IEEE-519 and having built-in input chokes, for harmonic supression on current (THID) less than 30% to 35% only.The drive shall be having open protocole connectivity (Modbus / Bacnet / N2 / FLN). each VFD shall be capable of displaying Flow and Head of pump..(Head given is tentative,before procurement of pumps Actual head should be calculated as per site conditions and get it aprroved by the consultant)
Hot Water Pumps: Supply, Installation, Testing, Commissioning and handing over of Vertical inline split coupled Pump of capacity 64 USGPM at 22 Meters Head fitted with suitable Motor (TEFC and IP 55) chilled water including mechanical seal and coupling guard and SS Impeller necessary accessories etc complete. Suitable Nos & suitable capacity squirrel cage induction motor with IE2 class 'F' insulation suitable for operation on 415 volts +10% , 50 Hz, A.C. supply. max speed of pump shall be 3000 RPM. . Pumps shall be Three in numbers in a combination of 2 working and 1 standby, that will complete one set.(Working Temperature upto 90 c) Suction guide and Triple Duty valve shall be supplied along with the pumps.(Head given is tentative,before procurement of pumps Actual head should be calculated as per site conditions and get it aprroved by the consultant)
Floor Mounted Type Air Handling Units: Supplying, installing, testing and commissioning of factory built Floor Mounted double skin type air handling units made of 40 mm thick panels consisting of pre plasticized G.I casing made of thickness 0.6 mm outside layer and G.I sheet of thickness 0.6 mm inside layer with polyurethane foam (PUF) insulation of density 42 kg/m3 factory injected between them by injection moulding machine, complete with Direct Driven Backward Curved Aerofoil Plug Type Fans with VFD's with aluminium finned copper tubes (tubes thickness not less than 0.5 mm),filter sections with 50 mm thick washable synthetic type pre filter having efficiency 90% down to 10 micron,fine filters having efficiency 99% down to 5 micron along with AOP cell i.e, UV lamp with quad metallic coating (rhodium, silver, copper, titanium) with ppc sleeve to prevent spillage having conformity to UL 1598 CAN/CSA C222 EN60335-1, EN60335-2-65, EU standards with pest repellant ceriticate to submitted along with submittals,backward curved plug fan with aerofoil design blades with TEFC (IEE-3) suitable for VFD operation at 415 ± 10% volts, 50 Hz,
3 phase, A.C supply, mixing box ,drain connections with drain valve, Flexible connection,stainless steel drain pan, necessary vibration isolation arrangement etc, arrangement etc. TP isolator with MS enclosure box should be Provided. etc, complete as per specifications of following capacities: (a) 32000 cfm with 6 Rows Cooling Coil & 2 Row Heating Coil,55 TR, 65 mm static pressure.
Fresh air unit (for VRV): Supply, installation ,testing and commissioning of ventilation Ceiling Suspended Fan Sections of Single Skin Construction made of 18 G pre plasticized GI sheet, belt driven DIDW centrifugal forward curve fan with vibration isolators and canvas connection , squirrel cage induction motor with class-F insulation (IEE-3), mounted within the housing and all other details as in the drawings & specifications. Fan section supplied,filter sections with 50 mm thick washable synthetic type pre filter having efficiency 90% down to 10 micron,fine filters having efficiency 99% down to 3 micron with extruded aluminum frame as detailed in the drawings. The fan motor shall be suitable for operation on Single speed , the motor with Class-F insulation, 415 ± 15 Volts, 50Hz, Ac power.The fan static pressure shall be 80 mm WC static. (a) Fresh Air CFM=2000
Ventilation: Inline Fans: Supplying, Installing, Testing and Commissioning of Inline fans complete with motor, supporting frame, gravity louvres,etc. as per drawings and specifications.
(a) 850 CFM , @ 15mm Static
(b) 350 CFM ,. @ 15mm Static
AHU's Controls/Three Way Modulating Valve: Supply, Installation , Testing & Commissioning of Three way Modulating type Flow Control Valves:
(a) Water flow rate 120-252 USGPM
(b) Water flow rate 62-120 USGPM
(c) Modulating Thermostats
Plumbing (Insulated Chilled / Hot Water): Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled/hot water piping inside the building (with necessary clamps, vibration isolators, and fittings but excluding valves, strainers, gauges etc.) . as per specifications and as required. Chicken wire mesh and sand cement plaster for the following: where ever required. The Pipes size 150mm & below shall be M.S. heavy class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. & from minimum 7mm thick M.S. sheet for pipes of 400 mm dia. & above.
Insulation Thickness Range 1. DIA 20 -100 MM - 25 MM 2. DIA 100-150 MM -40 MM 3. DIA 150-250 MM -50 MM 4. DIA 300 -450 MM -65 MM 5. DIA 450 & above MM -75 MM
Supplying, fixing, testing and commissioning of following PN-16 Rating valves, strainers, gauges in the chilled water plumbing duly insulated to the same specification as the connected piping and adequetly supported as per specifications. Butterfly Valves
Motorized Butterfly Valves: Providing and fixing the following motorized butterfly valves for chilled water as per specifications (a) 80 MM
Balancing Valves: Providing and fixing the following motorized butterfly valves for chilled as per specifications:
Y - Strainers:
Pressure Gauges: Providing and fixing pressure gauge with gauge cock, thermowell. complete as per specifications and drawings.
Thermometers with thermowell: Providing and fixing thermometer Mercury filled V form type complete as per speci-fications and drawings.
Flow Switches: Providing and fixing water flow switch on chilled water outlet complete as per specifications and drawings.
Automatic Air Vents: Providing and fixing auto airvent purging valve complete as per specification and drawings.
Expansion tank: Supplying, installation, testing and commissioning of PVC Tank with vent and draing connections with float valve, quick fill,overflow, and control valve etc as required.Tank should be closed from top with the removable type man hole cover plate with handle for cleaning purpose.All pipe points should have ball valves fitted on tank.Non return valve to be fitted at the tank outlet along with ball valve.
(a)1000 LTRS Chilled water
(b) 500 LTRS Hot water
Drain Piping: Supply,installation,testing and commissioning of rigid PVC piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber class ‘O’. Providng and fixing pipes with all necessary fittings, supports and insulation.
Ducting: Supply, fabrication, installation, balancing and commissioning of factory fabricated GI sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings of following gauges as per SMACNA standard:-
(a) Thickness 24 G sheet
(b) Thickness 22 G sheet
(b) Thickness 20 Gsheet
Grilles/Diffusers: Supply,installation, testing and commissioning supply and return air grilles/ diffusers as per specifications and drawings including fixing frame of G.I./wooden in false ceiling/walls.
(a) Aluminium supply air grill with VCD
(b) Aluminium return/exhaust air grill without VCD
(c) Aluminium return/exhaust air Diffuser without VCD
(d) Aluminium exhaust/fresh air louvers
(e) Aluminium Jet Nozzle ball type 400 Dia
Insulation: Supply and installation of Thermal insulation material for Non-Exposed to weather Ducts with Closed Cell Class O Nitrile Rubber Elastomeric Insulation of Density 40 - 55 Kg/m3, Thermal Conductivity of 0.038 W/mk at 300Celcius Mean Temp. and µ≥7000 (without any additional vapour barrier) and with factory laminated chemically treated glass cloth of suitable color (Green for Supply Ducts and Red for Return Ducts) of 7mill / 0.18mm thickness tested for UV resistance as per EN ISO 4892-2 Method A; to be applied on Ducts using manufacturer's recommended Rubber based Adhesive, as per the approved specifications. The joints are to be sealed with 3mm thick nitrile rubber tapes pre-laminated with chemically treated glass cloth of matching color of duct insulation. The ducts are to be supported with duct supports made from PET foam as load taking member embedded in nitrile rubber foam sheet with outer metal face made of aluminium. 19 MM thick (Non Exposed) Supply Air Ducts
Supply and installation of Thermal insulation material for Exposed Ducts with Closed Cell Class O Nitrile Rubber Elastomeric Insulation of Density 40 - 55 Kg/m3, Thermal Conductivity of 0.038 W/mk at 300Celcius Mean Temp. and µ≥7000 (without any additional vapour barrier) and with factory laminated 3 layered composite non-metallic cladding of 230 micron in thickness having having as an intermediate layer with special UV protective coating and PVC backing tested for UV resistance as per EN ISO 4892-2 Method A; to be applied on Ducts using manufacturer's recommended Rubber based Adhesive, as per the approved specifications. The joints are to be sealed with self adhesive silver tapes of 30mm width. The ducts are to be supported with duct supports made from PET foam as load taking member embedded in nitrile rubber foam sheet with outer metal face made of aluminium.Where ever required on the exposed part it should be coated with 3 Layers of Fevicol weather protekt Coat.25 MM thick (Exposed) Supply Air Ducts
Duct Acoustic Lining: Supply and fixing of acoustic lining of supply air duct and plenum with 15 mm thick Engineered Nitrile Rubber open cell foam having a Noise Reduction Coefficient of 0.55 with Density 140 - 180 Kg/m3 passing Class 1 Fire Performance test as per BS 476 Part 7, Air Erosion test for 10,000 fpm air velocity as per ASTM C 1071-05 and with built-in antimicrobial protection. The material should pass Fungi Resistance Test as per DIN EN ISO 846 Method A and Bacterial Resistance Test as per DIN EN ISO 846 Method C; to be applied using manufacturer's recommended Rubber based Adhesive in a blend of solvents.
VRV/VRFSystem: Supply, Installation, testing and commissioning of AIR COOLED & INVERTER BASED VARIABLE REFRIGERANT VOLUME / VARIABLE REFRIGERANT FLOW MODULAR TYPE AIR CONDITIONING SYSTEM with R410A suitable for 415 ± 10% , 50 Hz. The unit shall consist of indoor units and external condensing units and other accessaries as listed below complete in all respects as under: Outdoor Unit: SITC Modular type outdoor units equipped with highly efficient inverter type scroll compressor(s) with special precoated heat exchanger, low noise condenser fan housed in compact housing duly powder coated. Outdoor units shall have both cooling & heat pump mode, and environmet friendly refrigerant R-410A.The C.O.P shall be confirmed by vendor at full and part load at 43.3 deg C ambient temperature..Complete with M.S mounting stand of approved design for outdoor unit.Nitogen Flushing before gas charging.Pressure testing should be done after installation.Anti corrosive coating should be done at site. (a) 22 HP.
Indoor Units: Supply,Installation, testing and commissioning of both interconnected with copper refrigerant & drain pipe of required length, insulation, full charge of refrigerant gas and oil, M.S. base frame duly primered & painted, supports etc. complete as per specifications and drawings. Cassette type Indoor units: Supply,Installation, testing and commissioning of Imported Air Cooled VRV/VRF Cassette type Indoor units equipped with pre-filter, fan section with low noise fan, multispeed motor, coil section with DX coil, electronic expansion valve, outer cabinet, insulation, pipe connections,control and power panel with corded remote control etc. etc. of various capacities as per specifications and drawings
Installation &Allied Works: Y-joints & header etc above complete as per specification and drawings.
Supply,Installation, testing and commissioning of Centralised remote controllers for operation & status monitoring of VRV/VRF indoor units
Refrigerant Piping: Supply,installation,testing and commissioning of Interconnecting non exposed refrigerant pipe work with (19mm/13 mm thick) , Class 'O', k value-0.035 w/mk minimum, Density not less than 55 Kg/cu.m closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps.
(a) 41.3 mm O.D. (insulation : 19 mm)
(b) 34.9 mm O.D. (insulation : 19 mm)
(d) 28.6 mm O.D. (insulation : 19 mm)
(d) 22.2 mm O.D. (insulation : 13 mm)
(e)19.1 mm O.D. (insulation : 13 mm)
(f) 15.9 mm O.D. (insulation : 13 mm)
(g) 12.7 mm O.D. (insulation : 13 mm)
(h) 9.5 mm O.D. (insulation : 13 mm)
(i) 6.5 mm O.D. (insulation : 13 mm)
Supply,installation,testing and commissioning of Interconnecting exposed refrigerant pipe work with (19mm thick) , Class 'O', k value-0.035 w/mk minimum, Density not less than 55 Kg/cu.m closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps Refrigerant piping will be coated with three layers of feviprotekt (only pidilite) weather coating.
41.3 mm O.D. (insulation : 19 mm)
34.9 mm O.D. (insulation : 19 mm)
28.6 mm O.D. (insulation : 19 mm)
15.9 mm O.D. (insulation : 19 mm)
Control & Transmission Wiring: Supply,installation,testing and commisioning of control cum transmission wiring of 2 core x 1.5 sqmm copper in suitable 25 MM PVC conduits between indoor and out door unit & outdoor units to central remotes controllers.
Electrical Control Panel: Plant Room AC PANEL-1 (Workshop Building): Supplying, assembling, erecting, connecting, testing and commissioning Outdoor type of dust, damp and vermin proof free floor standing factory built sheet steel enclosed non-drawout modular type Panel fabricated out of suitable sized angle iron and flats, base channel and covered with 2.0mm thick PCRC sheet, duly painted complete with earth bus, aluminium bus bar, numbering & sign writing, interconnection & including the cost of connection through bus bar / copper conductor flexible connection with all accessories, rotary handles,phase barriers etc. complete as shown in drawing & as per specifications and mounted with the followings etc. complete as required. (All the starters should have NO/ NC contacts for remote/ fire control facility etc. complete) Incoming: 1 Nos 630 A 4P MCCB, 35 KA 4P,complete in all respects as mentioned in specifications and as required with following accessories: Digital flush type class- I accuracy with power load manager, showing V, A, KVA, KWH etc. with 3 Nos. current transformers of 1250/5A ratio, 10 VA Class 1.0 metering. 1 Set of RYB phase indicating & ON/OFF/TRIP LED lamps with 2Amps. SP MCB's backup. Bus Bars:
A.C. Panel-2 (For Annexe Building): Supplying, assembling, erecting, connecting, testing and commissioning Outdoor type of dust, damp and vermin proof free floor standing factory built sheet steel enclosed non-drawout modular type Panel fabricated out of suitable sized angle iron and flats, base channel and covered with 2.0mm thick PCRC sheet, duly painted complete with earth bus, aluminium bus bar, numbering & sign writing, interconnection & including the cost of connection through bus bar / copper conductor flexible connection with all accessories, rotary handles,phase barriers etc. complete as shown in drawing & as per specifications and mounted with the followings etc. complete as required. (All the starters should have NO/ NC contacts for remote/ fire control facility etc. complete). Incomer: 1 No. 225 Amps MCCB TP+NL incoming 1 No. 325. Amps aluminium conductor bus bar duly sleeved 1 No. electronic energy meter with CTs. 1 No. Ammeter with ASS & CTs. 1 No. voltmeter with VSS. 3 Nos. phase indicating lamps 3 Nos. On,Off,Trip indicating lamps
Weather Proof isolators: Supply, installation, testing and commissioning of out door weather proof switch box of continuous welded construction, fabricated out of 2 mm thick G.I. sheet complete with water tight gasket with front openable and lockable door including earthing, painting, glands, danger boards etc. suitable for mounting on wall with M.S. angle iron frame of size 40x40x6 mm consisting of relevant I.S. specifications and drawings. Weather proof box with MCCBs of suitable ratings near the outdoor units for isolations for VRV Outdoor Units.(63 Amps)
Electrical cable: Supply of PVC insulated armoured aluminium /Copper conductor cables from main panel boards to various equipments through walls/ceiling with appropriate clamps and fixing arrangements, termination etc. as per specifications and drawings.
(a) 3 1/2 Core - 50 mm2
(b) 4 core - 16 mm2
(c) 4 core - 10 mm2
(e) 4 core - 6 mm2
Laying of PVC armoured aluminium /Copper conductor cables in existing cable trays from main panel boards to various equipments through walls/ceiling with appropriate clamps and fixing arrangements, termination etc. as per specifications and drawings.
(a) 3 1/2 Core - 50 mm2
(b) 4 core - 16 mm2
(c) 4 core - 10 mm2
(e) 4 core - 6 mm2
Termination: Supplying and making end termination with brass compression gland and aluminium lugs for following size of Pvc insulated and pvc sheated / XLPE aluminium conductor cable of 1.1 Kv grade as required
(a) 3 1/2 Core - 50 mm2
(b) 4 core - 16 mm2
(c) 4 core - 10 mm2
(d) 4 core - 6 mm2
DDC Controller: Supply, Installation, Testing & Commissioning of Standalone Intelligent Microprocessor based Programmable DDC with inbuilt HMI, Onboard Modbus port, with Process bus for network functionalities based on KNX Protocol. It should have SD card interface for application and operating system upgrade & operating temperature range should be -20 to 60 degree.Celsius. It should include suitable Enclosures with all accessories including necessary switchgear, step down transformer, internal power and control cabling (excluding power & control cable to Fan), complete in all respect & as required to suit the site conditions etc.
Field devices-Supply, Installation, Testing & Commissioning of Air Differential Pressure Switch with all complete.
Field devices: Supply, Installation, Testing & Commissioning of Duct Temperature & RH Sensor with all complete.
Supply, Installation, Testing and Commissioning of Temperature and RH setpoint adjustor Device with all complete.
Supplying & laying of signal cables. (2 core x 1.5 Sq.mm), PVC insulated, Shielded tinned copper conductor cable with all Complete.
Supply & Laying of MS Conduit 25 mm for Signal & Communication Cable with all Complete.
Supply & Laying of GI Flexible Pipe with all Complete.
SUB HEAD - XXIV : INTERNAL ELECTRICAL WORK:
Lights Points: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. NOTE : The rate for point wiring shall include the wiring from switch board to (light/switch/fan) including all accessories. (a) Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. (a) Group C
SUB MAIN WIRING: Supply and Wiring with the following size 1100V grade FRLS PVC insulated Copper conductor multi strand wires in & including heavy duty FRLS PVC conduit concealed in wall/ceiling/above false ceiling , including junction boxes, bends, elbows including and terminated with suitable lugs. with all accessories etc., complete.
(a) 2 runs of 2.5 Sq.mm wires with 1run of 2.5 Sq.mm wires including 25 mm dia conduit (For DB TO SB).
(b) 4 runs of 6 Sq.mm wires with 2 run of 6 Sq.mm wire in 32 mm dia PVC conduit.
Exhaust Fans: Supply and Installation of heavy duty Exhaust fans of 305mm Sweep with Metallic blades and gravity louvres shutters including all accessories etc., complete.
Wall Mounted Fans: Supply and Installation of wall mounted fans of Minimum 400mm Sweep with atleast 3 speed, oscillation and tilt mechanisam to direct air where it is needed. including all accessories etc., complete.
Light Fixtures: Supply, Installation, Testing & Commissioning of the following LED Light Fixtures with driver , heat dissipating element all necessary accessories. (Makes : Philips / CG / GE/ Equivalent)
(a) 120W LED high bay light similar to (CROMPTON CAT NO LHB11-120-CDL/60-HPM or Wipro or Equivalent)
(b) 70W LED Flood light similar to (CROMPTON CAT NO -LFL-80-CDL/60-M or Wipro or Equivalent).
(c) 35W LED light similar to (CROMPTON CAT NO -LSTS-36-CDL-M or Wipro or Equivalent).
(d) 36W LED Recess Mounted Square Light similar to (CROMPTON CAT NO LCTLRNE-36-FO-CDL or Wipro or Equivalent).
(e) 18W LED Recess Mounted Square Light similar to (CROMPTON CAT NO- LSCSM-18W-CDL or Wipro or Equivalent).
(f) 40W LED Tube Light Batten similar to (CROMPTON CAT NO-CIS-300-40-57-SL-DP-NGR or Wipro or Equivalent)
(h) 20W LED Tube Light Batten ceiling / Wall Mounted similar to (CROMPTON CAT NO-CIS-300-20-57-SL-DP-NGR or Wipro or Equivalent )
(i) 18W LED Recess Mounted Round Light similar to (CROMPTON CAT NO -LCDEP-18-NW or Wipro or Equivalent ).
(j) 12W LED Recess Mounted Round Light similar to (CROMPTON CAT NO -LCDEP-12-CDL or Wipro or Equivalent ).
(k) 9W LED Recess Mounted Round Light similar to (CROMPTON CAT NO -LCDEP-09-CDL or Wipro or Equivalent ).
Supply and Wiring with the following size 1100V grade FRLS PVC insulated Multistrand Copper conductor wires laid in & including suitable size heavy duty FRLS PVC conduit concealed in wall / above false ceiling junction boxes, bends, elbows including junction boxes, bends, elbows including and terminated with suitable lugs,including all accessories complete etc.,
(a) 2runs of 2.5Sq.mm wires with 1run of 1.5 Sq.mm wire in 25 mm dia conduit (For Lighting).
(b) 2runs of 2.5Sq.mm wires with 1run of 2.5 Sq.mm wire in 25 mm dia conduit (For Bay Lighting)
Supply ,Installation ,Testing and commissioning of TPN MCB Double door Distribution boards dust and vermin protected and rated for 415V Three Phase AC supply operation including incoming MCB /ELCB as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in concealed in wall after necessary chase cutting with finishing/surface in wall including all fixing materials required. MCBs shall conform to IS : 8828 and ELCB shall conform to IS :12640. All MCBs shall be 'C' Curve. DBs shall be provided along with required wire adopter boxes around the DB as required and dummys for spare ways in the DB (No claim shall be allowed for the same).
(a) 4Way TPN MCB DB (Horizontal type) with 25A ,4P MCB as incomer, 3Nos,20A, 30 mA 2Pole RCCB as Sub-incomer and 6 nos 6-10A SPMCBs as outgoings. (LDB)
(b) 6Way TPN MCB DB (Horizontal type) with 32A ,4P MCB, 100 mA 4Pole RCCB as incomer and 18 nos 6-25A SPMCBs as outgoings.(LPDB)
SPNDB: Supply ,Installation ,Testing and commissioning of SPN MCB Distribution boards dust and vermin protected and rated for 230V Single Phase AC supply operation including incoming MCB /ELCB as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in concealed in wall after necessary chase cutting with finishing/surface in wall including all fixing materials required. MCBs shall conform to IS : 8828 and ELCB shall conform to IS :12640. All MCBs shall be 'C' Curve. DBs shall be provided along with required wire adopter boxes around the DB as required and dummys for spare ways in the DB (No claim shall be allowed for the same).
(a) 8Way SPN MCB DB with 25A, 30 mA 2 Pole RCBO as incomer and 6 nos 6-10A SPMCBs as outgoings.(LDB)
Outgoings: 100A,25KA TPN MCCB With ON, OFF & TRIP LAMPS – 3 Nos 80A, 25KA 4P MCCB With ON, OFF & TRIP LAMPS– 3 Nos 63A, 25KA TPN MCCB With ON, OFF & TRIP LAMPS– 9 Nos 32A, 25KA TPN MCCB With ON, OFF & TRIP LAMPS– 6Nos 16A, 25KA TPN MCCB With ON, OFF & TRIP LAMPS– 7 Nos 16A, 10KA DP MCB 'C' Curve With ON, OFF LAMPS–9Nos
SUB HEAD - XXV : POWER WIRING:
Supply and fixing of modular type single phase 6A universal Socket with 6A switch with front plate and anodized GI box including all fixing accessories.
Supply and fixing of modular type single phase 6/16A 6 pin Socket with 16A switch with front plate and anodized GI box including all fixing accessories.
Supply and Wiring with the following size 1100V grade FRLS PVC insulated Multistrand Copper conductor wires laid in & including suitable size heavy duty FRLS PVC conduit concealed in wall / above false ceiling junction boxes, bends, elbows including junction boxes, bends, elbows including and terminated with suitable lugs,including all accessories complete etc.,
(a) 2runs of 2.5Sq.mm wires with 1run of 2.5 Sq.mm wire in 25 mm dia conduit (For 6A Sockets).
(b) 2runs of 4Sq.mm wires with 1run of 4 Sq.mm wire in 25 mm dia conduit (For 16A /20A Sockets).
(c) 4 runs of 6 Sq.mm wires with 2 run of 6 Sq.mm wire in 32 mm dia conduit.
(d) 4 runs of 10 Sq.mm wires with 2 run of 6 Sq.mm wire in 32 mm dia conduit.
Supply ,Installation ,Testing and commissioning of TPN MCB Double door Distribution boards dust and vermin protected and rated for 415V Three Phase AC supply operation including incoming MCB /ELCB as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in concealed in wall after necessary chase cutting with finishing/surface in wall including all fixing materials required. MCBs shall conform to IS : 8828 and ELCB shall conform to IS :12640. All MCBs shall be 'C' Curve. DBs shall be provided along with required wire adopter boxes around the DB as required and dummys for spare ways in the DB (No claim shall be allowed for the same).
(a) 6Way TPN MCB DB (Horizontal type) with 32A ,4P MCB as incomer, 3Nos 25A, 100 mA 2 Pole RCCB as Sub-incomer and 12 nos 16-20A SPMCBs as outgoings.
(b) 8Way TPN MCB DB (Horizontal type) with 32A ,4P MCB as incomer, 3Nos 25A, 100 mA 2 Pole RCCB as Sub-incomer and 18 nos 16-20A SPMCBs as outgoings. (PDB-3,4)
(c) 12Way TPN MCB DB (Horizontal type) with 63A ,4P MCB as incomer, 3Nos,40A 100 mA 2 Pole RCCB as Sub-incomer and 30 nos 20A SPMCBs as outgoings. (PDB-1,2)
SPNDB: Supply ,Installation ,Testing and commissioning of SPN MCB Distribution boards dust and vermin protected and rated for 230V Single Phase AC supply operation including incoming MCB /ELCB as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in concealed in wall after necessary chase cutting with finishing/surface in wall including all fixing materials required. MCBs shall conform to IS : 8828 and ELCB shall conform to IS :12640. All MCBs shall be 'C' Curve. DBs shall be provided along with required wire adopter boxes around the DB as required and dummys for spare ways in the DB (No claim shall be allowed for the same).
(a) 8Way SPN MCB DB with 25A, 30 mA 2 Pole RCBO as incomer and 6 nos 6-10A SPMCBs as outgoings.
EARTHING: Supply, installation, testing and commissioning of G.I. Earth station, with 40mm dia 2500mm long GI pipe,including construction of brick pedestal, providing meshed ,CI cover and other civil Engineering works,spreading a homogenous mixture of salt, charcoal around the pipe etc, completely as per IS 3043, 1987 or latest revision.
Supply and laying of following size strips including all necessary inter connections with earth station and equipments including excavation and back filling etc complete.
50 x 5 MM GI Flat
25 x 5 MM GI Flat
Supply and fixing of 1C x 10Sqmm PVC Insulated Flexible Copper Cable(Green)
8 SWG GI wire
Supply and fixing of following size GI Perforated type cable tray made out of 2mm thick sheet with GI Covers including MS supports for fixing 'the tray, anchor fasteners etc complete as 'required.
300mm wide x 75 mm depth
150mm wide x 75 mm depth
100mm wide x 50 mm depth
50mm wide x 50 mm depth
1.1KV Cables: Supply of following size 1.1KVgrade XLPE insulated armoured aluminium / Copper conductor cable. The cable shall conform to IS 7098.
3.5C X 35 Sq.mm AR.Aluminium
3.5C X 25Sq.mm AR.Aluminium
4C X 16Sq.mm AR.Aluminium
4C X 10Sq.mm AR.Aluminium
4C X 6Sq.mm AR.Aluminium
4C X 10 Sq.mm Copper
4C X 6 Sq.mm Copper
4C X 4 Sq.mm Copper
3C X 10 Sq.mm Copper
3C X 6 Sq.mm Copper
3C X 4 Sq.mm Copper
3C X 2.5 Sq.mm Copper
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1. KV grade of following size on cable tray as required.
Upto 35 sq. mm (Clamped with 1mm thick saddle)
END TERMINATIONS: Supply, laying and commissioning of Out Door /Indoor, Double compression / ordinary end terminations for the cable specified below with compression type steel gland,Bi-metallic lugs using crimping tool,Insulation tape,Identification tags etc., including end termination.
3.5C X 35 Sq.mm AR.Aluminium
3.5C X 25Sq.mm AR.Aluminium
4C X 16Sq.mm AR.Aluminium
4C X 10Sq.mm AR.Aluminium
4C X 6Sq.mm AR.Aluminium
4C X 10 Sq.mm Copper
4C X 6 Sq.mm Copper
4C X 4 Sq.mm Copper
3C X 10 Sq.mm Copper
3C X 6 Sq.mm Copper
3C X 4 Sq.mm Copper
3C X 2.5 Sq.mm Copper
SUB HEAD - XXVI : UPS WIRING:
Supply and fixing of modular type single phase 3 Nos 6A 5pin Socket controlled by 1 No 16A Switch, front plate and anodised GI box including all fixing accessories.
Supply and fixing of modular type single phase 6/16A 6 pin Socket with 16A switch with front plate and anodized GI box including all fixing accessories.
SUBMAINS/CIRCUIT MAINS/POWER WIRING : Supply and Wiring with the following size 1100V grade FRLS PVC insulated Copper conductor wires laid in & including suitable size heavy duty FRLS PVC conduit concealed in wall / above false ceiling junction boxes, bends, elbows including junction boxes, bends, elbows including and terminated with suitable lugs.
(a) 2 runs of 2.5 Sq.mm wires with 1run of 2.5 Sq.mm wires in 25 mm dia conduit (6A Sockets, UPS DB TO SB)
(b) 2 runs of 4 Sq.mm wires with 1run of 4 Sq.mm wires in 25 mm dia conduit (16A Sockets)
Supply ,Installation, Testing and commissioning of TPN MCB Double door Distribution boards dust and vermin protected and rated for 415V Three Phase AC supply operation including incoming MCB / ELCB as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in flush with wall including all fixing materials required. MCBs shall conform : 8828 and ELCB /RCCB shall conform to IS : 12640
(a) 8Way TPN MCB DB (Horizontal type) with 32A ,4P MCB as incomer, 3Nos 25A, 100 mA 2 Pole RCCB as Sub-incomer and 18 nos 6-20A SPMCBs as outgoings.
(b) 12Way TPN MCB DB (Horizontal type) with 40A ,4P MCB as incomer, 3Nos,32A 100 mA 2 Pole RCCB as Sub-incomer and 30 nos 6-20A SPMCBs as outgoings.
VTPN DB (UPS INPUT DB): 4Way VTPN MCB DB (Vertical type) with 80A ,4P MCB as incomer and 2+1 Nos TP 40A MCBs as outgoings.
VTPN DB (UPS OUTPUT DB): 8Way VTPN MCB DB (Vertical type) with 80A ,4P MCB as incomer and 4+2 Nos TP 40A/32A MCBs, 1+5 nos SP 25A MCBs as outgoings.
Supply ,Installation ,Testing and commissioning of SPN MCB Distribution boards dust and vermin protected and rated for 230V Single Phase AC supply operation including incoming MCB /ELCB as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in concealed in wall after necessary chase cutting with finishing/surface in wall including all fixing materials required. MCBs shall conform to IS : 8828 and ELCB shall conform to IS :12640. All MCBs shall be 'C' Curve. DBs shall be provided along with required wire adopter boxes around the DB as required and dummys for spare ways in the DB (No claim shall be allowed for the same).
(a) 8Way SPN MCB DB with 25A, 30 mA 2 Pole RCBO as incomer and 6 nos 6-10A SPMCBs as outgoings.
Supply and fixing of 2mm thick Aluminium Raceways with clamping as per standards.including chipping where ever necessary finishing complete as required. Line and level should match with finished floor level after finsishing the race ways.
(a) 100mm wide X 40 mm depth
Supply of following size 1.1KVgrade XLPE insulated armoured Copper conductor cable. The cable shall conform to IS 7098.
1C X 10 Sq.mm Copper
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1. KV grade of following size on cable tray as required.
(a) Upto 35 sq. mm (Clamped with 1mm thick saddle)
Supply, fixing and commissioning of Indoor end terminations for the cable specified below with Single compression type steel gland,Bi-metallic lugs using crimping tool,Insulation tape,Identification tags etc., including end termination.
1C X 10 Sq.mm Copper
Earthing: Supply, erection, testing and commissioning of conventional Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories,excavation,refilling and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required As per IS-3043/87 with latest amendments.
Supply and laying of following size strips including all necessary inter connections with earth station and equipments including excavation and back filling etc complete.
(a) 25mmx5 mm Copper strip
(b) 8 SWG GI wire
SUB HEAD-XXXIV - TELEPHONE WIRING & LAN CONDUITING
Supply and laying of 25mm dia. Heavy duty FRLS PVC conduit concealed in wall/ ceiling/floor including all accessories such as junction boxes, conduit bends, etc completed as required for Telephones/ Lan etc. Complete.
Supply and fixing of Telephone outlet (RJ11) with anodised GI box with front plate and plug in type telephone socket .
Supply and installation of Krone connectors in junction box complete as required.
Supply and laying of 2 pair 0.5mm dia PVC insulated Copper conductor Telephone wire conforming to DOT Specification.
Supply and laying of following Copper conductor, Jelly filled, armoured cable including excavation brick protection,backfilling, sand cushioning with all accessories etc complete.
10 pair Cable
20 pair Cable
50 pair Cable
Supply and fixing of LAN outlet (RJ45) with anodised GI box with front plate,with all accessories etc complete,
Supply and laying of CAT 6 Cable in existing conduit with all accessories etc complete .
Supply and fixing of 16 ports internet switch
Supply and fixing of 24 ports internet switch
SUB HEAD - XXVII : SHOP ELECTRICS:
INDUSTRIAL SOCKETS :
Supply and fixing of factory made 1-phase 16/20 A SP Metalclad socket with 20A DP MCB in MS box including all fixing accessories.
Supply and fixing of factory made 3-phase 32 A TPN+E Metalclad socket with 32A TP MCB in MS box including all fixing accessories.
Supply and fixing of factory made 3-phase 63 A TPN+E Metalclad socket with 63A TP MCB in MS box including all fixing accessories.
Supply ,Installation ,Testing and commissioning of TPN MCB Double door Distribution boards dust and vermin protected and rated for 415V Three Phase AC supply operation including incoming MCB /ELCB as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in concealed in wall after necessary chase cutting with finishing/surface in wall including all fixing materials required. MCBs shall conform to IS : 8828 and ELCB shall conform to IS :12640. All MCBs shall be 'C' Curve. DBs shall be provided along with required wire adopter boxes around the DB as required and dummys for spare ways in the DB (No claim shall be allowed for the same).
(a) 8Way VTPN MCB DB (Vertical type) with 100A ,4P MCB as incomer and 5+1 Nos TP 32A MCBs, 4+2 nos SP 20A MCBs as outgoings.
SUB HEAD - XXVIII : SPECIAL EARTHING:
Supply, erection, testing and commissioning of maintenance free earth station consisting of 65 mm dia 3m long Copper electrode capsule field with earth enhancing compound sealed at both ends and brazed lead for connection at one end, suitable for direct installation at site with brass bolt at the top end with nuts & washers including masonary enclosure, CI cover with frame and interconnection alongwith earth pit identification MS board and as required spreading of earth enhancing chemical compound etc. complete . Scope also includes excavation in all type of soil, back filling and making the area neat etc. complete.
Supply and laying of following size strips with DMC Insulated supports including excavation,back filling etc,complete., with necessary inter connections with earth station and equipments .
(a) 50 x 5 mm Copper strip.
(b) 25 X5mm Copper strip
Supply,Installation,Testing and commissioning of static disharge plate/ handle to ensure that there is no charge on the Human Body before entering any ESD safe area.
SUB HEAD - XXIX : LIGHTNING PROTECTION:
Providing maintanance free earth station with consisting of ' - 40mm dia, standard length (as per equipment supplier) electrode capsule, filled with earth enhancing compound, seald at both ends and brazed lead for connection at one end, suitable for direct installation at site, at a depth of 2.5 Mtrs. '- Earth Enhanced compound up to a depth of 2.0 meters around the electrode capsule. '- Brick chamber & CI Cover complete.
Supply and laying of following size earth strips including excavation and refilling of earth when laid in ground and with all fixing accessories when laid on the parapet with necessary interconnections with earth station and equipments.
(a) 50 X 5mm GI Strip laid in Ground
(b) 32 X 5mm Aluminium strip conductor with DMC insulated supports.
(c) 32 X 5mm Aluminium strip conductor with DMC insulated supports & including PCC Blocks.
Supply and installation of vertical air termination with 40mm Dia copper hollow sphere with spikes, fixed on 1000mm length, 25mm dia copper rod including PCC block and all fixing accessories.
SUB HEAD - XXX : DG SET WITH SYNCH PANEL:
320 kVA DG Set with DG Synch Panel & Acoustic Enclosure: Supply of Prime duty 320KVA DG set with AMF panel, acoustic enclosure suitable for 75 db(A) sound level reduction to be measured at 1 mtr. from the enclosure. Cost should cover D.G. set control panels,necessary control and metering, indication /annuciation & other accessories.
The diesel generating set shall be continuous rating, 3 phase, 415 volts, 50 cycles (A.C). Supply comprising of a totally enclosed air/water cooled diesel engine with multi-cylinders developing suitable BHP not less than following capacity at 1500 RPM with 10% overload for one hour in 24 hours with 1no. 990.0ltrs. day tank, standard accessories like fly wheel, lubricating oil cooler, "A" class governor, heavy duty fuel wheel and lubricating oil filter, oil bath air filler, lubricating oil pressure gauge, end exhaust manifold, standard set of tools with adjustable spanners, screw drivers, feeder gauge, cylinder head to cover, joint cylinder head to exhaust, element lube oil filter, 12/24 volts electric starting equipment complete with standard battery, dynamo, cut-outs, ammeter, necessary
wiring, pressure gauge, starter etc and heavy duty Residential type exhaust silencer and vertical hot air duct both logged with asbestos rope, save oil trays, exhaust piping of required length, standard wall/floor mounted fuel with level indicator and piping and drip proof alternator, self excited, self regulated, screen protected, with excitation system, capable of delivering the rated system output at 415 volts, 3 phase, 0.8 PF, 50 Hz, 4 wire, running at 1500 RPM, conforming to IS-4722- 1968 with voltage regulation +/- 5% of rated voltage from no load to full load.
To submitt drawing showing , SLD with rating equipments / make etc., and overall lay out with dimensions, plan, elevations an sections and got approved prior to commencing of manufacturing.
The scope also includes the following;
Supply, delivery of the DG set & Synch Panel at site.
Specific Fuel Consumption Test
Unloading of the DG set at Required Location of Installation & test at manufacture's place.
Technical support & supervision during commissioning of DG Set & Synchronizing Panel.
To get Battery charged and to test Battery charger.
Testing of the DG Set with Supply of Consumable.
Painting of the parts damaged during Transportation or Installation
Power & Control cabling between D.G. Panel & D. G. Set, syncronising Panel & alternator to MCCB inside the enclosure.
D.G. set should have exhaust chimney of Suitable Length as per statutory requirement with suitable M.S. structure complete between exhaust of engine till out let point for discharging fuel gas. Drawing of which should be submitted for approval.(Necessary cost to shall be included.)
The rate quoted shall be for the entire job including exhaust piping complete up to trial test. No extra rates to be quoted for any items for the DG set.
All Necessasary control cables of between DG set, AMF panel / Sync Panel, MLTP and Battery charger shall be part of supply. Necessasary BOM shall be submitted during approval process.
To prepare & submit as-built drawing and handing over document to end user.
Scope also includes preparing necessary drawing submitting to authorities, getting their approval / sanction and final certificate including NOC from pollution board (if required) to energize the D G Set.
Supply, erection, testing and commissioning of exhaust M.S. piping suitable for 320 KVA Dgset with flexible connections, thermal insulated asbestos / rockwool lagging with chicken mesh and aluminium sheet wrapping over the exhaust pipes and silencer inside the generator room and with two coats of anti-corrosive primer coating and two coats of heat resistant paint for exposed piping outside the building. The exhaust pipe shall be taken minimum 3.0mtrs. above the height of the building. The rate shall also include cost of necessary supports, steel brackets, scoffolding etc., all complete as required.
Supply and erection of structural support for exhaust pipe using necessary MS frame work. The structural support shall be made out of MS frame work using adequate size MS angles. The vendor shall visit site and quantify the steel requirement and submit the quote along with the GA drgs.
Supply & Installation of 25mm dia, MS class 'C' fuel pipes with required valves and accessories.
Supply and installation of hand pump, to pump the storage fuel from barrels to the Day tank with flexible hose pipes etc.,
Supply and installation of intermediate storage fuel tank of capacity 990 ltrs. With inlet, outlet and drain pipe with plug and all necessary valves and accessories as required.
L.T.CONTROL CABLES Supply,Laying, Testing and commissioning of 1.1 KV grade PVC insulated armoured COPPER conductor cable of the following size including laying in built up trenches, cable trays, on wall including clamping
4C x 2.5 Sqmm
9C x 2.5 Sqmm
Termination of the following cables with single compression cable glands and also with suitable size Copper lugs including supply and fixing of Lugs.
4C x 2.5 Sqmm
9C x 2.5 Sqmm
Earthing Supply, installation, testing and commissioning of G.I. Earth station, with 40mm dia 2500mm long GI pipe,including construction of brick pedestal, providing meshed ,CI cover and other civil Engineering works,spreading a homogenous mixture of salt, charcoal around the pipe etc, completely as per IS 3043, 1987 or latest revision.
Supply, erection, testing and commissioning of conventional Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories,excavation,refilling and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required As per IS-3043/87 with latest amendments.
Supply and laying of following size strips including all necessary inter connections with earth station and equipments including excavation and back filling etc complete.
25mm x 5 mm Copper strip
50 x 5 MM GI Flat
25 x 5 MM GI Flat
SUB HEAD - XXXI : EXTERNAL POWER SUPPLY:
MAIN PCC: EB Incoming: 1000A,50KA 4P ACB with O/C, S/C,E/L Micro process Based Release – 1 No
Outgoings : 800A,50KA TP+N ACB (EDO) with ON, OFF , TRIP LAMPS, MFM & CT– 2 Nos 400A,36KA 3P MCCB with ON, OFF , TRIP LAMPS, MFM & CT– 1 No 400A,36KA TP+N MCCB with ON, OFF , TRIP LAMPS, MFM & CT– 2Nos 32A,25KA TP+N MCCB with ON, OFF , TRIP LAMPS, MFM & CT– 2Nos 25A,25KA TP+N MCCB with ON, OFF , TRIP LAMPS, MFM & CT– 1No
Note : All Capacitors shall be Delta connected and rated for 440V and of MPP Heavy Duty type. The Capacitors shall be provided in the Panel itself with proper ventilation arrangements All Contactors in this panel shall be capacitor switching Contactors Outgoings : 200A TP MCCB with 100kVAR Capacitor Duty Contactor and Capacitor Bank with 7% Detuned LC Filter -1 set. 100A TP MCCB with 50kVAR Capacitor Duty Contactor and Capacitor Bank with 7% Detuned LC Filter -1 set 63A TP MCCB with 25kVAR Capacitor Duty Contactor and Capacitor Bank with 7% Detuned LC Filter -1 set 20A TP MCCB with 10kVAR Capacitor Duty Contactor and Capacitor Bank with 7% Detuned LC Filter -2 sets. 16A TP MCCB with 5kVAR Capacitor Duty Contactor and Capacitor Bank with 7% Detuned LC Filter -1 set
Supply,installation,Testing and commissioning of 11KV, 800A Indoor HT Vacuum Circuit Breaker Panels consisting of number of Breakers as given below. The VCBs shall be with Motorised Spring Charging(24V DC) mechanism and shall be as per detailed specifications. All VCBs shall have auxilary Relays and Annunciation as specified in Technical specifications.The Closing & Tripping Coils shall be suitable for 24 V DC . Seperate CTs are to be provided for Protection and Metering of Burden and class of Accuracy as specified in Specifications . All VCBs Shall have provision for remote On/Off and remote On/Off indications wired upto terminal block. HT VCB PANEL AT METERING YARD & AT SOURCE STATION 800A VCBs with Volt meter with Bus PT for incoming VCB, Ammeter with CTs, PF Meter, two Overload & one Earth Fault digital relays . Phase Indication Lamps, Breaker On/Off/ Trip and Spring Charge, and Trip Circuit healthy Indications.
11KV Cable & Termination: Supply of ISI Marked 3 Core 185 Sq.mm XLPE insulated 11 KV armoured cable Aluminium conductor.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11KV grade of following size direct in ground including excavation, sand cushoning, protective covering and refilling the trench etc as required.
(a) Above 120 sq.mm and upto 400 sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
(a) Above 120 sq.mm and upto 400 sq.mm
Supply and Installation of cable end terminatation kit, heat shrinkable Push on type Densons/ Raychem/ Elastimold make suitable for 11 KV XLPE cable 3 Core 185 Sq.mm
Supplying and Installation of Medium Voltage cable end box outdoor type suitable. for 11 KV, 185 Sq.mm 3 Core MV cable complete with gland bushing and jointing material
Transformer with On Load Tap Changer (OLTC): 630kVA , 11kV/433V Distribution Transformer Supply, installation, testing and commissioning of 630 kVA , 11kV/433V, Dyn11, Oil Cooled ONAN type double copper wound, delta star connected Outdoor distribution Transformer as per IS - 1180, Level - II operating on 3 phase, 50 Hz 4 wire & neutral earthed system continuously rated for a full temperature rise in oil not exceeding 50 Deg.C.at maximum ambient temp. of 50 Deg. C. complete with necessary radiator first filling of new transformer oil & standard fitting as below complying with I.S 2026/1977 & 1981 standards.
ON load tap changing range steps -5 to +10 % insteps of 2.5% on H.V and L.V. for variation should be provided. The H.V. shall be connected Delta & Secondary with star connection. The transformer should have cable-end boxes on 11KV side suitable for up to 3 core 185 Sq.mm. XLPE cable & on 433V side suitable for cables (as per SLD) as per requirement complete with test certificates from manufacturers. Transformer vendor has to arrange for inspection and factory acceptance test as detailed in specification.
Oil conservator with filling Hole & Cap - 1 No. Thermometer pocket with 6" dial type thermometer switch alarm & trip contacts - 2 No's.. Silica-gel breather with charge - 1 No. Plain oil level gauge - 1 No. Drain / Sampling / Filter valve -1 No. Top Filter Valve - 1 No. Explosion vent with Diaphragm - 1 No. Rating & Diagram plate - 1 No. Additional neutral bushing for earthing - 1 No. Bi directional Roller - 4 No's. Earthing terminals - 2 No's. Lifting lugs - 2 No's. Air release plug. - 1 No. Double float buchholz relay with Alarm and trip contacts . Etc as to complete the job as required by Engineer-in-Charge
1.1KV Cables: Supply of following size 1.1KV grade XLPE insulated armoured aluminium / Copper conductor cable. The cable shall conform to IS 7098.
3.5C X 400 Sq.mm AR.AL
3.5C X 300 Sq.mm AR.AL
3.5C X 240 Sq.mm AR.AL
3.5C X 185 Sq.mm AR.AL
3.5C X 150 Sq.mm AR.AL
3.5C X 120 Sq.mm AR.AL
3.5C X 95 Sq.mm AR.AL
3.5C X 70 Sq.mm AR.AL
3.5C X 50 Sq.mm AR.AL
4C X 6 Sq.mm CU
4C X 4 Sq.mm CU
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
(a) Upto 35 sq. mm
(b) Above 35 sq. mm and upto 95 sq. mm
(c) Above 95 sq. mm and upto 185 sq. mm
(d) Above 185 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
(a) Upto 35 sq. mm
(b) Above 35 sq. mm and upto 95 sq. mm
(c) Above 95 sq. mm and upto 185 sq. mm
(d) Above 185 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required
(a) Upto 35 sq. mm
(b) Above 35 sq. mm and upto 95 sq. mm
(c) Above 95 sq. mm and upto 185 sq. mm
(d) Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1. KV grade of following size on cable tray as required.
(a) Upto 35 sq. mm (Clamped with 1mm thick saddle)
(b) Above 35 sq. mm and upto 95 sq. mm (Clamped with 25x3mm MS flat clamp)
(c) Above 95 sq. mm and upto 185 sq. mm (Clamped with 25/40x3mm MS flat clamp)
(d) Above 185 sq. mm and upto 400 sq. mm (Clamped with 40x3mm MS flat clamp)
END TERMINATIONS: Supply, laying and commissioning of Out Door /Indoor, Double compression / ordinary end terminations for the cable specified below with compression type steel gland,Bi-metallic lugs using crimping tool,Insulation tape,Identification tags etc., including end termination.
Outdoor:
(a) 3.5C X 400 Sq.mm AR.Aluminium
(b) 3.5C X 300 Sq.mm AR.Aluminium
(c) 3.5C X 240 Sq.mm AR.Aluminium
(d) 3.5C X 185 Sq.mm AR.Aluminium
Indoor:
(a) 3.5C X 150 Sq.mm AR.AL
(b) 3.5C X 120 Sq.mm AR.AL
(c) 3.5C X 95 Sq.mm AR.AL
3.5C X 70 Sq.mm AR.AL
3.5C X 50 Sq.mm AR.AL
(d) 4C X 6 Sq.mm CU
(e) 4C X 4 Sq.mm CU
L.T.CONTROL CABLES: Supply,Laying, Testing and commissioning of 1.1 KV grade PVC insulated armoured COPPER conductor cable of the following size including laying in built up trenches, cable trays, on wall including clamping
(a) 4C x 2.5 Sqmm
(b) 9C x 2.5 Sqmm
Termination of the following cables with single compression cable glands and also with suitable size Copper lugs including supply and fixing of Lugs.
(a) 4C x 2.5 Sqmm
(b) 9C x 2.5 Sqmm
Supply and fixing of following size GI Perforated type cable tray made out of 2mm thick sheet with GI Covers including MS supports for fixing 'the tray, anchor fasteners etc complete as 'required.
300mm wide x 75 mm depth
150mm wide x 75 mm depth
100mm wide x 50 mm depth
50mm wide x 50 mm depth
Earthing
Supply, installation, testing and commissioning of G.I. Earth station, with 40mm dia 2500mm long GI pipe,including construction of brick pedestal, providing meshed ,CI cover and other civil Engineering works,spreading a homogenous mixture of salt, charcoal around the pipe etc, completely as per IS 3043, 1987 or latest revision.
Supply, erection, testing and commissioning of conventional Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories,excavation,refilling and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required As per IS-3043/87 with latest amendments.
Supply and laying of following size strips including all necessary inter connections with earth station and equipments including excavation and back filling etc complete.
25mm x 5 mm Copper strip
50 x 5 MM GI Flat
25 x 5 MM GI Flat
SAFETY ITEMS & MISSELLENIOUS: Supply, Installation, Testing and commissioning of the Following Safety and Fire fighting accessories as per standards and specification:
(a) Fire Extinguishers - 4.5 KG CAPACITY CO 2 Confirming to IS 2878 fitted with discharge bend pipe and horn fitted on wall
(b) Rubber Mats 11 KV, size 2 m x 1 m
(c) Rubber Mats 415 V, size 2 m x 1 m
(d) Shock treatment Chart with wooden frame and glass
(e) First Aid Box
(f) Sand bucket with stand with 3 Nos of buckets with canopy
(g) 415 V Danger Boards
(h)11 KV Hand Gloves
(i) Providing and Laying of non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with Stiff mixture of cement mortar in the proportion of 1:2 (1 Cement :2 fine Sand ) including testing of joints complete.
(j) 300mm Dia. R.C.C Pipe
(k) 150mm Dia. R.C.C Pipe
Supply and laying of following size FRLS PVC conduits on surface /floor/wall/ceiling including necessary clamps, hardware and minor civil works. The rate shall include drilling and making good and paint for proper finish, if required and shall match with the existing / New finish of the building. All the equipments or tools required for the proper installation of PVC Conduit shall be under Contractor scope only .No separate provision shall be given by the Client.
(a) 25 mm dia PVC conduit
(b) 32 mm dia PVC conduit
SUB HEAD - XXXII : AREA LIGHTING:
Supply, erection, testing and commissioning of steel stepped and swaged tubler poles of 9mtr. Long (410 SP25) (1.5mtr below Ground) with base plate, earthing studs,1.5Mtr out reach single arm, FRP terminal box, 2nos 40mm dia class B GI Pipe, 0.75mtr. Long each for incoming and outgoings cables, including excavation in all types of soil, PCC 1:2:4, PCC Pedestal complete with painting with black bitumin paint inside the coping for embedded portion and two coats of Zinc chromate primer and two coats of Aluminium paint externally for length above the ground. The pole shall be with FRP Junction box consisting of 10A SP MCB. The wiring from Junction box to Light fixture shall be carried out with 3core 2.5sq.mm Copper conductor cable. The pole shall be fixed with 90W LED Lamp with fixture including supply of Condrolgear / driver and lamp etc complete as required. (Make: Wipro cat no LR02-102-XXX-57-G2 / Philips cat no BRP410)
Supply, installation, testing and comissioning of astronomical time switch capable of 3 O/P (1 Per Phase) suitable for 3 Phase supply in feeder pillar / Fabricated DB for External Lighting & Landscape Lighting with Automatic switching ON & OFF of street lights at Sunset / Sunrise wth manual over ride facility with 12/24 Hour Display format with suitable battery and indication for relay status i.e programming at site complete as required - Outdoor Type 3 Ph MCB DB with Metal Door - considered with Astronomical Timer / Day Light Sensor / as directed by Engineer in charge. Incomer : 40A,1 No - 4P MCB Outgoings : 6 Nos of 20Amps TPN MCB, 6 Nos 10A SP MCB 'C' Curve
MV Cables: Supply of following size 1.1KVgrade XLPE insulated armoured aluminium / Copper conductor cable. The cable shall conform to IS 7098.
(a) 4C X 16 Sq.mm AR.Aluminium
(b) 4C X 10Sq.mm AR.Aluminium
(c) 4C X 6Sq.mm AR.Aluminium
(d) 4C X 4 Sq.mm AR.Copper
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
(a) Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
(a) Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
(a) Upto 35 sq. mm
Supply, fixing and commissioning of Out Door /Indoor, Double compression / ordinary end terminations for the cable specified below with compression type steel gland,Bi-metallic lugs using crimping tool,Insulation tape,Identification tags etc., including end termination.
(a) 3.5C X 35 Sq.mm AR.Aluminium
(b) 4C X 10Sq.mm AR.Aluminium
(c) 4C X 6Sq.mm AR.Aluminium
(d) 4C X 4 Sq.mm Copper
Providing spiral coil earthing with 8SWG GI wire including spreading of salt & Charcoal as per IS 3043/87 with lastest amendments.
SUB HEAD-XXXIII - FIRE ALARM SYSTEM
Supply and laying of 25mm dia PVC FRLS Conduits run on surface of wall/ above false ceiling/ concealed in wall along with all fixing accessories/ materials.
Supply, laying, testing and commissioning of twisted pair 2x1.5sq.mm 650V grade shielded PVC insulated copper conductor flexible wires through existing FRLS PVC conduit.
Supply installation testing and commissioning of analogue addressable type photo electric smoke detectors with LED indication lamp along with complete fixing accessories.
Supply installation testing and commissioning of analogue addressable type photo electric Heat detectors with LED indication lamp along with complete fixing accessories.
Supply installation testing and commissioning of analogue addressable type hooters with all fixing materials.
Supply installation testing and commissioning of analogue addressable type Manual call points and fixing accessories
Supply and installation of suitable Repeater panel with all interconnections to work along with the fire alarm control panel along with all accessories in complete.
Supply and commissioning of fault isolator module for isolation in case of fault or repair
Supply and commissioning of Control modules so as to trip of AC and other related devices in case of fire or smoke and to activate existing PA system Amplifier
Supply, laying and testing of requied core, multimode OM3 corrugated steel tape LSZH, armoured, loose tube gell- filled optical fiber cable, the rate shall include the cost of joint enclosure and splicing of Optical Fiber cables, patchcords and also other accessories as required complete etc.
Supply, installation testing and commissioning of weather proof type analogue addressable Manual call points with glass and hammer on standpost made out of 1500mm long 50x50x5mm Glavanised channel fixed in ground with concrete coping as required.
Supply of 8 Way Wago / Phonix terminal connector in weather proof MS Junction box inxluding painting and all installation materials etc., as required.
Supply, installation, testing and commissioning of 2.5Km range siren with weather proof motor with 220V 50HZ AC supply operation with required power contactor, MPCB for control all in a weather proof enclosure near motor including all installation materials as required.
SVC PROJECTS PVT LIMITED
Vishal Infrastructure Ltd
INTER CONTINENTAL CONSTRUCTIONS (INDIA) LIMITED
SAI CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid