GARRISON ENGINEER
GE I R and D Chandipur Post Chandipur PIN 756025
REPAIR MAINTENANCE OF E AND M EQUIPMENT AT FIREFIGHTING INSTALLATIONS FIREFIGHTING AUTOMATION SYSTEM CONTROL PANELS REPLACEMENT OF MS DI PIPES AND CLEANING OF STATIC WATER TANKS AT PXE ITR AND LCs AREA AT CHANDIPUR
2023_MES_623208_1
8879/CDP
Open Tender
Civil Works
Item Rate
270 days
Chandipur
As per Tender Documents
8 documents required · 8 mandatory
₹500
GE I R AND D Chandipur
₹70,000
Yes
21 Dec 2023
14 Oct 2023
18 Nov 2023
14 Oct 2023
16 Nov 2023
28 Oct 2023
Amount
NOTE (Applicable for all items) :- The bidders/contractors are advised to read tender document & all corrigendum / amendments and General conditions of contracts before entrying/quoting the rates.
Cleaning and Repairing of Fire Static Tank of capacity 100000 Gln for fire fighting system by draining out the water and taking out the sludges from the bottom of the static water tank and cleaning mossy on the walls of the tank and scrapping by wire brush and brooms, repairing the erroded surface surface with cement plaster and applying two coats of while lime and writing the date of cleaning on white paint over black painted surface complete all as specified and directed. (Note:- Location- PXE Tech area, Magzine area , ITR Tech area and Lcs area)
All as per Sl Item No 1 here in before but of capacity 75000 Gln
All as per Sl Item No 1 here in before but of capacity 50000 Gln
All as per Sl Item No 1 here in before but of capacity 30000 Gln
All as per Sl Item No 1 here in before but of capacity 20000 Gln
All as per Sl Item No 1 here in before but of capacity 10000 Gln
Excavation in trenches not exc 1.5 wide and not exc 1.5 mtr deep and getting out in soft soil for laying pipes complete all as specified .
Returning and filling in soils , including spreading ,levelling ,watering and well ramming in layers not exc 25 cm thick complete all as specified .
Removal of excavated material to a distance not exc 50 mtr away from starting point and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed
Cutting of PCC road / hard standing / floor, etc. exc. 45 cm. and not exc. 90 cm in depth and width 45 cm (min) for laying of pipe, tubing, etc. and making good and finished & matching the disturbed surfaces with existing surfaces complete all as specified and directed.
Cutting of exsiting Bituminous road exc. 45 cm. and not exc. 90 cm in depth and width 45 cm (min) for laying of pipe, tubing, etc. and making good and finished & matching the disturbed surfaces with existing surfaces complete all as specified and directed.
Material and labour for taking up UNSV DI water mains with spigot and socket ends of any class including all fittings complete all as specified and directed by Engineer -in -charge for 150 mm dia bore pipe complete all as specified and directed.
Material and labour for taking up UNSV DI water mains with spigot and socket ends of any class including all fittings complete all as specified and directed by Engineer -in -charge for 100 mm dia bore pipe complete all as specified and directed.
Supply and laying of ductile iron (DI) pipe spigot and socket ends class 'K-9' suitable for tyton joint or any length properly laid in trenches all as specified and directed by Engr-In-Charge of 150 mm dia bore pipe complete all as specified and directed. (Make - Electro steel/Rashmi Metaliks/Tata or equivalent)
Supply and laying of ductile iron (DI) pipe spigot and socket ends class 'K-9' suitable for tyton joint or any length properly laid in trenches all as specified and directed by Engr-In-Charge of 100 mm dia bore pipe complete all as specified and directed. (Make - Electro steel/Rashmi Metaliks/Tata or equivalent)
Supply and fix DI fitting for spigot socketed pipe , bends ( any type , radius and angle ) tapers any type , (straight , bend increasing , decreasing or double socket etc ) tee pieces single branch , Y junction double branch , cross of size - up to 150 mm dia complete all as specified and directed.
Labour only for taking out sluice valve of 80 mm dia bore including re- facing, re- grinding of shutter and re - fixing the same including providing rubber insertion sheet , gland packing rope , nuts , bolts and washers etc to make the sluice valve leak proof and free. operational all as specified and directed by Engr -in - charge for the following sizes .Note - :- Rate of rubber insertion sheet,nut,bolts,washers etc will deemed to be included in the item rate.
All as per Sl Item No 17 above but size of 100 mm dia bore.
All as per Sl Item No 17 above but size of 150 mm dia bore.
Supply and fix in repair CI sluice valve flanged of class PN 1.6 conforming to IS - 14846 complete with iron wheel head , SS/Gun metal spindle and check nut , including jointing material such as rubber insertion nuts, bolts and washers etc complete of 80 mm dia bore pipe . Make - Kirloskar/upadhaya/Leader/Zoloto or eqvlnt.
All as per Sl Item No 20 above but size of 100 mm dia bore.
All as per Sl Item No 20 above but size of 150 mm dia bore.
All as per Sl Item No 20 above but size of 200 mm dia bore.
Supply and fix in repair CI Non - Return Valves , ISI marked , heavy duty , flanged type including rubber sheet & nut bolts etc complete all as specified by the Engr-in-charge for 80 mm dia bore Make - Kirloskar/Upadhaya/Leader/Zoloto or equivalent
All as per Sl Item No 24 above but size of 100 mm dia bore
All as per Sl Item No 24 above but size of 150 mm dia bore
All as per Sl Item No 24 above but size of 200 mm dia bore
Supply and fix in repair 80 mm dia pipe foot valve as per IS-4038 of cast iron with brass diaphragm heavy duty screwing type complete of the following sizes .Make-Kirloskar/Kartar/Leader/Upadhaya
All as per Sl Item No 28 above but size of 100 mm dia
All as per Sl Item No 28 above but size of 150 mm dia
Supply and fabrication of fire hydrant hose box of size 800mmx 600mmx 250mm made of 18 mm gauge MS sheet with 3 mm thick double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet and 40mmx 40mm x 6mm thick iron angle support at 1.5 mtr height including grouting, painted FIRE with red outside and brilliant white inside box including taking down old unserviceable all as specified .
S&F in repairs fire fighting canvas hose pipe, fire chief brand, cotton synthetic fibre, circular woven jacketed rubberized fabric reinforced rubber lined (RRL) , 35.7 Kg/cm2 burst pressure and 22 Kg/cm2 proof pressure, 63 mm dia of 15 mtr long with male and female GM coupling of 63 mm dia all as specified . (Make – Zenith/ Jyoti/Fire Shield).
S&F in repairs fire fighting Branch pipe gun metal 63mm instantaneous inlet, made threaded outlet, 15mm bore nozzle short all as specified . (Make – Zenith/ Jyoti/Fire Shield)
S&F in repairs fire fighting GM landing valve (Hydrant valve single headed) with 80 mm NB flanged inlet brass spindle 63 mm dia female oblique outlet including rubber washer all as specified and directed by Engineer – in – Charge. (Make – Zenith/ Jyoti/ Fire Shield).
Repairs only to broken fire hydrant hose box with 3 mm thick steel work including cutting,welding and jointing/brazing with repair to double door with replacement of 4 mm thick glasses and door frame made of 16 gauge MS sheet and painting all over the surface area with one coat of primer and two coats of synthetic enamel red paintwith painted 'FIRE' with black outside including taking down fire box from its position and refixing again after repairs all as specified .
Supply and Fix sensors and contactors including its wiring cables and accessories suitable as per site requirment for complete autonomation of Main Pumps and Jockey Pump completeat Fire pump houses as directed by Engr-in-charge. (Location - Magzine, FP-1 and FP-II Fire pump ) all as specified .
Dismantling and taking down the electric motor of fire pump set 100 HP capacity and transporting to work Shop and carrying out servicing/ maintenance of motor unit as per the following maintenance work:- (a) Opening of electric motor and cleaning/ removing dust from Armature and field coil (b) Cleaning of used/ old lubricated substance (c) Cleaning of starter and rotor unit (d) Checking and tightening of coupling, nuts, bolts and replacement of rubber insert. (e) Carrying out heat varnishing with varnish solution of best quality for field and armature coil. (f) Replacement of oil worn out bearings. (g) Reassembling the complete motor and carrying out testing at work Shop and transporting back to installation and coupling with pumping set including necessary alignment, cable connection all as directed.
Disconnecting the suction and delivery pipe line and electric connections ofunserviceable centrifugal pump of head-90 m, discharge-180 cum per hour, Model No-DSM 100/36 Make-Kirlosker coupled with electric motor 100 HP, 3 Phase and removing it from its position carefully and transporting to the work shop and refixing the same in its original position after servicing including replacement of bushes , machining the pump shaft to suit in new bushes all as specified and as directed. Note : (i) Consumable stores like cotton waste/cleaning materials lubricants , gland packing metal filling , machining and transportation from site to work shop are deemed to be included in rate quoted
Disconnecting and taking out the electric driven Jockey pump Motor of capacity 18.5 KW (Kirloskar make), by disconnecting the pump motor coupling, inlet and outlet pipe line for foundation. Repair to Motor by replacement of burn out windings of stator/rotor, coupling and bearing, repairing of worn out spare parts , reassembling the motor after repairs, including replacement of all nuts, bolts, washers, gland packing, greasing etc and fixing the motor in its original position / foundation and testing on load complete and all as directed and as specified.
Disconnecting and taking out the electric driven Jockey pump of discharge capacity 500 LPM at 7.5 kg/sqcm by disconnecting the pump motor coupling, inlet and outlet pipe line for foundation etc. Repair to pump by replacement of worn out gland cap, gland bush, coupling and bearing, repairing of worn out shaft, impeller by suitable re-metalling, finishing up to suitable size and doing necessary heat treatment, replacement of impeller key with new one including necessary heat treatment, reassembling the pump after repairs, including replacement of all nuts, bolts, washers, gland packing, greasing etc and fixing the pump in its original position / foundation and testing on load complete and all as directed and as specified.
Supply and fixing in repairs PVC insulated and sheathed Copper Flexible Cable cable, 3 core, multistranded copper conductor of 1100 volts grade conforming to IS-694, of size 6.0 sqmm in PVC conduit from starter to sewage pump complete.
Supply and fixing in repairs PVC insulated and sheathed Copper Flexible Cable cable, 3 core, multistranded copper conductor of 1100 volts grade conforming to IS-694, of size 10 sqmm in PVC conduit from starter to sewage pump complete.
S&F on load change over switch 200 Amps 4 pole for open mount including taking down old change over switch all as directed. (Make – Havells/L&T/ C&S/ Standard )
S&F in repairs on load change over switch 100 Amps 4 pole in existing panel including taking down old one complete all as directed. (Make – Havells/L&T/ C&S/ Standard )
S& F in repair off load change over switch side handle operated in SS Sheat enclosure of rating 100 Amps four poles all as specified and directed. (Make – Havells/L&T/ C&S/ Standard )
S&F MS ERW pipe of 80 mm dia pipe with provision of necessary MS bend, MS flange etc, by cutting and welding and painting with two coats of synthetic enamel paint over a coat of primer and testing including taking down old MS pipe. (Make – Bansal/ Tata/ Jindal)
S&F MS ERW pipe of 100 mm dia pipe with provision of necessary MS bend, MS flange etc, by cutting and welding and painting with two coats of synthetic enamel paint over a coat of primer and testing including taking down old MS pipe. (Make – Bansal/ Tata/ Jindal)
S&F MS ERW pipe of 150 mm dia pipe with provision of necessary MS bend, MS flange etc, by cutting and welding and painting with two coats of synthetic enamel paint over a coat of primer ant testing including taking down old MS pipe.(Make – Bansal/ Tata/ Jindal)
M&L for structural steel work in,foundation frame of pump and moter as per existing size , stairs. Including cleats, brackets etc for replacement of UNSV parts complete including dismantling all as specified and directed.
M & L for cement concrete in foundations, filling and mass concrete type D2 1:4:8 using 40 mm grade stone aggregate
M & L for cement concrete in copping type B1 1:2:4 using 20 mm graded stone aggregate
M & L for rendering 10mm thick cement plaster on fair faces of concrete surfaces finished even and smooth (with out using extra cement)
M & L for Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25m depth below ground level) with top edge of the plate not less than 1.5 m below ground level connected to galvanised earth strip of size 25 x 4 mm by mean of bolt, nuts, check nuts and washer of galvanised iron steel all as shown in electrical plate No 3 of SSR Part - I, connected earthing test point and testing on complete all as specified and directed Note :- Rate also include necessary excavation and earth work in any type of soil, PCC pit 1:3:6 type C2, CI cover, funnel with watering pipe GI pipe light grade20 mm, wire mess, GI Protection pipe 40mm dia medium grade, test point, connecting lead/strip from test point to main switch or eqipment to be connected.
Supply & fixing in replacement of earth continuity conductor GI strip 25 x 4 mm.
S&F in repair digital multi function VAF + PF meter 3 phase in existing panel including taking down old one complete all as directed. (Make – Havells/ standard/ L&T).
S&F in repair Single phase preventer in existing panel including taking down old one complete all as directed. (Make – Havells/ Minilac / L&T).
S&F of over load relay 19-25 amp,including taking down one all as directed.(Make – Havells/ standard/ L&T).
S&F of over load relay 9-13 amp,including taking down one all as directed.(Make – Havells/ standard/ L&T).
S&F in repair power contactor of capacity 95 Amps, AC3, 415 volts main contactor coil voltage 110 Volt with 2 NO + 2 NC, including taking down old one all as directed. Make – BCH/Siemens/L&T
S&F pressure gauge 100 mm dia type 10 Kg/sqcm. including taking down old u/s pressure gauge. Make-RMCO or equivalent as approved.
S & F in repair LED Panel indicator lamp of any type to match with existing and of colour Red, Yellow, Blue. 22 mm DIa Make-C&S/L&T
M&L for painting to Fire boxes and exposed pipe lines of steel / iron surfaces of any description, over 10 cm in width or girth, not otherwise described after preparation of old painted surface, with one coat of red oxide primer and two coats of synthetic enamel paint as per colour code and all as directed and approved.
Supply and fix rubber seat washer as per IS 937 for fire fighting hydrant valve after taking down old one complete as specified.
Supply and fix female outlet stainless steel as per IS: 3444 Gr.1 outlet adapter for fire fighting hydrant valve after taking down old one complete as specefied.
PODDAR SALES CORPORATION
Bidder Name
KRISHNA ENTERPRISES
PODDAR SALES CORPORATION
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .