| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.0 LAccepted-Finance | ₹15.0 L | L1 | Accepted-Finance financially compliant |
| 2 | L2₹15.3 LAccepted-Finance 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | ₹15.3 L | L2 | Accepted-Finance financially compliant |
Tender Value
₹15.4 L
EMD Value
₹30,800
Closing Date
3 Jan 2020, 11:00 amClosed
EXECUTIVE ENGINEER(CIVIL)
Near gate no-1, AIIMS Raipur, Hospital Administrative Block, Project Cell.
Supply, Installation, testing and commissioning of Inverter type VRF or VRV Air Conditioning System for 166 seat Lecture theatre Ground floor ,Medical college AIIMS Raipur
2019_IMSRP_506883_4
18/EE/AIIMS/RPR/2019-20
Open Tender
Job Works
60 days
AIIMS RAIPUR CHATTISHGARH
please go through the NIT documents
2 documents required · 2 mandatory
₹0
₹30,800
2 Mar 2020
21 Dec 2019
4 Jan 2020
21 Dec 2019
3 Jan 2020
21 Dec 2019
Amount
Supply, Installation, Testing & Commissioning of Modulating outdoor units (Cooling) along with additional refrigerant top up, with single / Multi scroll inverter compressors, to be able to work till 52 degree centigrade, and work with flexible to operate even under extreme low load condition i.e less than 30 % . It should come with special pre-coated fins, panel, corrosion resistant & hydrophilic treatment coated condenser, electrical & microprocessor panel, with or without isolating valves, factory gas charged for proper functioning of the units, having following approximate capacities. with the criteria of delivering 100 % capacity at 43 degree Centigrade &nonstop cooling upto 52 degree Centigrade. The unit shall also have heating provision during winter season. Capacity as listed below.
18 HP Top discharge system
Supply, Installation, Testing & Commissioning of Inverter VRF - Ceiling Mounted VRF connected Cassette type Indoor Unit and Panel with compact cooling coil inside falls ceiling each comprising of compact cooling coil, electronic expansion valve, multi speed fan motors, dynamically balanced blowers, built in drain pump with electronic level sensor, synthetic washable / plasma media filter including insulation and suitable for remote control operation suitable to operate from central remote control an installation from ceiling .with all required support, anchor fastners hardware, interconnecting refrigerant copper piping, valves, supports etc including termination at nearest power outlet with copper wires of suitable capacity and rating in metallic flexible conduit and interlocking in outdoor units (unit shall confirmed to the detailed specification of tendered document and providing power / control cabling/ earthing of indoor unit complete with supplying of all material in all respect as per specifications and any other items required to make the system complete as required.
3.6TR-945CFM ,With Refnets & Remote Controller
Supplying, fixing and Testing of refrigerant copper piping between indoor to outdoor with tie rods & supports clamp .Supporting should be at distance of 1.2 Mtr not less than that and with necessary tie rods &brackets,supports,saddles, clamps, hangers , vibration-isolators and fittings such as bends, tees etc.as required . 41.3mm dia
Supplying, fixing and Testing of refrigerant copper piping between indoor to outdoor with tie rods & supports clamp .Supporting should be at distance of 1.2 Mtr not less than that and with necessary tie rods &brackets,supports,saddles, clamps, hangers , vibration-isolators and fittings such as bends, tees etc.as required . 34.9mm dia
Supplying, fixing and Testing of refrigerant copper piping between indoor to outdoor with tie rods & supports clamp .Supporting should be at distance of 1.2 Mtr not less than that and with necessary tie rods &brackets,supports,saddles, clamps, hangers , vibration-isolators and fittings such as bends, tees etc.as required . 28.6mm dia
Supplying, fixing and Testing of refrigerant copper piping between indoor to outdoor with tie rods & supports clamp .Supporting should be at distance of 1.2 Mtr not less than that and with necessary tie rods &brackets,supports,saddles, clamps, hangers , vibration-isolators and fittings such as bends, tees etc.as required . 22.2mm dia
Supplying, fixing and Testing of refrigerant copper piping between indoor to outdoor with tie rods & supports clamp .Supporting should be at distance of 1.2 Mtr not less than that and with necessary tie rods &brackets,supports,saddles, clamps, hangers , vibration-isolators and fittings such as bends, tees etc.as required . 19.1mm dia
Supplying, fixing and Testing of refrigerant copper piping between indoor to outdoor with tie rods & supports clamp .Supporting should be at distance of 1.2 Mtr not less than that and with necessary tie rods &brackets,supports,saddles, clamps, hangers , vibration-isolators and fittings such as bends, tees etc.as required . 15.9mm dia
Supplying, fixing and Testing of refrigerant copper piping between indoor to outdoor with tie rods & supports clamp .Supporting should be at distance of 1.2 Mtr not less than that and with necessary tie rods &brackets,supports,saddles, clamps, hangers , vibration-isolators and fittings such as bends, tees etc.as required . 12.7mm dia
Supplying, fixing and Testing of refrigerant copper piping between indoor to outdoor with tie rods & supports clamp .Supporting should be at distance of 1.2 Mtr not less than that and with necessary tie rods &brackets,supports,saddles, clamps, hangers , vibration-isolators and fittings such as bends, tees etc.as required . 9.5mm dia
Supplying, fixing and Testing of refrigerant copper piping between indoor to outdoor with tie rods & supports clamp .Supporting should be at distance of 1.2 Mtr not less than that and with necessary tie rods &brackets,supports,saddles, clamps, hangers , vibration-isolators and fittings such as bends, tees etc.as required . 6.4mm dia
Supply and fixing of insulation of 9 mm nitrile rubber insulation to copper pipe complete as required after applying two coats of cold setting adhesive (CPRX compound) .
9 mm nitrile rubber
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.
32 mm Dia
Supply and fixing of 6 mm nitrile rubber insulation on UPVC Drain pipe complete as required after applying two coats of cold setting adhesive (CPRX compound) .
Supplying and fixing of MS of (40X40X5)mm stand for condensing (Outdoor) unit ,Size –1480 mm(L)*820mm(W)*300(H)}
Electrical Panel board for operating VRV/ VRF AC System along with LED indicator ,necessary equipments required to run AC System fitted in Electrical panel Box as per specifications of AIIMS RAIPUR .Panel suitable for 25 KW motor ,5 blower of AC System & incomer .
Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Supply & Fixing 25sq.mmx4 core circular flexible pvc insulated ,pvc sheathed copper cable direct on the wall with clips complete as required
Supply & fixing Earthing Cable -10 SWG (Copper), Complete as required.