Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹25.4 LAccepted-AOC 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | 1 | Accepted-AOC Accepted being L1 | |
| 2 | 2₹27.9 L+₹2.5 L (9.88%)Rejected-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NEW DELHI | DELHI | DELHI | 110006 | 2 | Rejected-Finance Rejected due to not L1 | |
| 3 | 3₹29.5 L+₹4.2 L (16.4%)Rejected-Finance WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | 3 | Rejected-Finance Rejected due to not L1 | |
| 4 | 4₹29.6 L+₹4.3 L (16.9%)Rejected-Finance | 4 | Rejected-Finance Rejected due to not L1 | |
| 5 | 5₹35.1 L+₹9.8 L (38.5%)Rejected-Finance RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | 5 | Rejected-Finance Rejected due to not L1 |
Tender Value
₹43.5 L
EMD Value
₹87,000
Closing Date
23 Sept 2024, 6:00 pmClosed
GE UTILITY ELEC SUPPLY
GE UTILITY ELEC SUPPLY DELHI CANTT-10
PROVN OF 04 HIGH MAST LIGHT IN RRRC UNDER GE U ES DELHI CANTT 10
2024_MES_669650_1
GE ELEC/D-35/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE UTILITY ELEC SUPPLY
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
GE UTILITY ELEC SUPPLY
₹87,000
Yes
4 Nov 2024
2 Sept 2024
24 Sept 2024
2 Sept 2024
23 Sept 2024
16 Sept 2024
Amount
Excavation in trenches not exceeding 1.5 metre wide & not exceeding 1.5 meter in depth for foundation, laying of cable or pipe (where provided for protection of cable or fixing with poles and stays) and getting out in any type of soil including trimming the sides and forming bottom surfaces to required levels complete all as specified and directed by the Engg-in-Charge.
Removing surplus excavated soil to a distance n.exc. 50 metre and depositing where directed at a level n.exc.1.5 metre high from the starting point complete all as specified and directed by the Engg-in-Charge.
Returning, filling in trenches in soft/loose soil in layers n.exc. 25 cm after laying of cables including spreading, levelling, and well ramming complete all as specified and directed by the Engg-in-Charge.
M&L for sand filling in trenches with clean dry unwashed sand free from sharp particles, gently punning around the cables as cable protection complete all as specified and directed by the Engg-in-Charge.
Supply and laying brick old size, sub class 'B' brunt bricks laid in trenches as cable cover across the cable in trenches complete all as specified and directed by the Engg-in-Charge.
Supply and fixing of galvanized High mast light suitable for 8 lantern LED flood light Luminaries symmetrically fitted along with their control gear and having two point suspension system with stainless steel wire rope of 6 mm dia 7/19 gauge and double drum winch with luminaires mounting arm, pulley assembly, aviation obstruction light, lighting arrestor spike including earth work and RCC foundation as per height 20 Mtr with complete all as specified and directed by the Engg-in-Charge with the following technical specification:- (a) MAST STRUCTURE:- The high Mast shall be of continuously tapered, polygonal cross section polygon type (Minimum 16- Sides) of 20 Mtrs. in height presenting good visual appearance and shall be based on proven design to given assured performance, reliability and service. The Mast shall have an approximate top diameter of say 150 mm to 200 mm and bottom diameter of 350 mm to 450 mm, The weight of the Mast shall not exceed more than 1600 kgs, excluding weight of Luminaire, to maintain good elasticity of slender structure. (b) MAST CONSTRUCTION :- The Mast shall be fabricated from special steel plates of BS EN 10025 grade, cut and folded to form polygonal section and shall be telescopically jointed and fillet welded. The welding shall be in accordance with BS: 5135. The procedural weld geometry and the workmanship shall be exhaustively tested by the radiography on the completed welded and certificates submitted. The Mast shall be delivered in only 2 sections without any circumferential welding at site, which shall be joined together by slip-stressed-fit method. The joining shall be with stressing equipment, thus forming the sleeve joint. No site welding or bolted the joint will be accepted. The overlap distance shall have full penetration of longitudinal welds. The base plate of the mast shall be at least 25 mm. thick. An adequate door opening min 1400mm x 300mm shall be provided at base of each mast such as to permit clear access to equipment like winches, cable pug and socket, etc. The opening shall be complete with a close fitting vandal resistant, weather-proof door provided with a heavy duty lock. For metal protection of the Mast, the entire fabricated Mast shall be hot dip galvanised internally and externally, having minimum average thickness of 65 microns. (c) DYNAMIC LOADING:- The Mast structure shall be designed for an assumed maximum reaction arising from the maximum wind speed at Mendhar and measured at a height of 10 Mtrs. above ground level . The design life of the Mast shall be min. 25 years. Wind excited oscillation shall be damped by the method of construction and adequate allowance made for the related stresses. The offered High Mast shall be a tested design.
(d) FOUNDATION:- The tenderer shall see the site closely and minutely with regard to the nature of the soil, average depth of decomposed garbage and debris at proposed Mast locations and the other site conditions before working out the type of foundation and specifications for the proposed High Mast. The tenderer shall be responsible for the design of the foundation and safe erection and installation of the High Mast in mechanically and structurally safe working condition for the design life of the Mast as per manufacture design The load bearing (safe) capacity of the soil shall be indicted by purchaser to decide the type of foundation and its specifications. The holding down bolts shall be at least 20 nos. of high tensile strength and shall be supplied complete with anchor plate of 6 mm thick for casting into the foundation. The ensure correct vertically and horizontality of bolt alignment. (Note : Cost of foundation as per specification of manufacturer shall be deemed to be included in the rate quoted by the contractor)
(e) LANTERN CARRIAGE:- The fabricated lantern carriages shall be provided for holding fittings and control gear provided on each High Mast. The lantern carriage shall be of special design and of durable steel tube construction designed to act as electric conduit with cable holes fully protected by grummets. The diameter of the lantern carriage shall be suitable so as to hold designed number of LED floodlight fittings, as specified in the tender design along with the control gear boxes and lantern. The lantern carriage shall be fabricated in three parts joined by bolted flanges with SS bolts with nuts to enable easy removal from the erected mast for replacement/ maintenance purpose. The carriage shall be supported/ suspended by three wire ropes for better stability. The lantern carriage Assembly shall not touch the lower surface of the Mast. The carriage design and fabrication shall be such that the lantern carriage will suit the lanterns and their control gear boxes to be used in the work. The Lantern Carriage shall be so installed that it does not cause any damage to the surface of the Mast and is provided with protective buffer arrangement. The complete Lantern carriage shall be hot dip galvanised after fabrication. The weather - proof cast aluminum junction boxes (IP-66) shall be provided on the Lantern carriage assembly from which the inter- connections will be made to the designed number of floodlight fittings and lanterns on the carriage. (f) MECHANICAL ARRANGEMENT:- For installation and maintenance purpose, it will become necessary to raise or lower the lantern carriage assembly. To enable this, a suitable winch arrangement shall be provided in the base of the Mast, complete with top pulley, winch stainless steel wire ropes and winch driving power tool. (i) WINCH:- The winch shall be of completely self-sustaining type. the winches shall be of self- sustaining type by means of an oil bath and the lubrication shall be of recommended quality. Termination of the ropes of the winch shall be in such a way, that it does not involve distortion or twisting of the rope configuration. At least 6 turns of rope shall remain in tension on the drum even when the lantern carriage is fully lowered. the winch shall be designed to be installed or removed form the door opening at the base of the mast. The winch drums shall be grooved to ensure mechanically strong, stable and tidy rope lay with no chances of rope slippage or skippage. The winch shall be capable of operation by hand or by means of external power tool. Integrated power tool with worm is not acceptable. A test certificate shall be supplied along with each winch in support of the maximum load operated by the winch and for the safety of operation at the full load rotation. A handle shall also be provided for hand operation of the winches.
(ii) TOP PULLEY ASSEMBLY:- The top pulleys shall be of a diameter, appropriately large enough to accommodate the steel wire ropes and the multicore electric cable. The material of construction of the pulley blocks shall be non- corrosive and made of dia cast (LM-6) aluminum alloy. The pulley assembly shall be complete with self lubricating bearing and stainless steel spindle. (iii) STAINLESS STEEL WIRE ROPES:- Stainless steel wire shall be AISC 316 grade 7/ 19 construction 2 Nos ropes for winch and 3 Nos for lantern carriage, 6 mm dia having a breaking load capacity of 2350 kg complete with stainless steel thimbles. The end for connection to the winch drum shall be fitted with thimbles and the thimbles shall be secured by copper compression splices.
(g) CABLE AND CABLE CONNECTIONS :- The connections shall be made with flat core flexible round sheath power cables of appropriate rating as per the schedule. The base compartment of the High Mast shall have one terminal box for terminating the incomer cable. The maintenance cables equal to that within the Mast and fitted with travelling cable 5 core 4 sqmm flexible having plug socket shall be provided to energize lanterns while in lowering position by hooking up at the base compartment socket supply. Similarly, the provision shall be made for electric supply at the base compartment to enable operation of the external power tool for lowering or rising of the lantern carriage assembly. The trailing cables of the lantern carriage rings shall be terminated by means of metal cased plug and socket provided in the base compartment to enable flexibility. (h) WINCH DRIVING POWER TOOL :- The electric driven tool shall be single speed, (1.2 Mt/min) reversible three phase & hand operated motor. The power tool shall be complete with very robust remote control switch such that the tool can be operated from safe distance of 5 Mtrs. There shall be and arrangement for self alignment off power tool which can be self supported during operation. Manual handle shall be provided for hand operation of the winches. The capacity rating and speed of the electric motor used in the power tool shall be specified by the tenderers. (j) LIGHTNING FINIAL & AVIATION OBSTRUCTION LIGHTS:- One number heavy duty hot dip galvanised lighting finial shall be provided for each mast. Suitable aviation obstruction lights of reliable design and reputed manufacturer shall be provided on top of each mast.
Supply, installation, testing & commissioning HIGH MAST LT panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,outer body made out of 3.15 mm thick & inner shell made out of 2.00 mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated , The cubicle shall have frame work, bottom & 45 CM long four legs of size 50 x 50 x 6 mm Angle iron, aluminium main busbar of 1.5 times to the rating of Incommer switch gear & for out goings 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 SQMM, complete comprising with following accessories all as specified and directed by the Engr-in-charge. (Note: Feeder pillar box shall be mounted on PCC 1:2:4 type B-1 (with 20 mm graded stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item). ( Note:-All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at with 4000 Amps 65 KA, should be submitted by the contractor before executing the job) INCOMING:- (i) MCCB 4P 40 A, 10 KA with SPREADER Link -01 Set (ii) HIGH MAST light controls:- (iii) Contactor 32 A (AC3), 3P,- 01 No. (iv) Digital AstroTimer - 01 No. (v) Control MCB SP 6A- 03 Nos. (vi) MCBTP 16-32 A - 02 Nos. (vii) REV- FWD Starter, 05 HP:- (a) Contactor 12A (AC3), 3P,- 02 Nos. (b) OLR 5-8 A - 01 No. (c) Push button( ON/OFF, Rev/ Fwd)- 04 Nos. (d) Indicator UP/ DOWN- 02 Nos.
Supply, installing, testing and commissioning in replacement of factory made and tested Bus bar chamber outdoor type with canopy made out of 3.15 mm CRCA MS sheet, and 40x40x5mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front opening type, with apron for cable entry closing locking arrangement ,of size 450mm x 450mm x 300mm with 4 Nos 500 Amps aluminium bus bar and with 250 Amp MCCB, 4 pole, 36 KA, 415 Volt 50 Hz including excavation, earth work and platform for the Bus bar chamber with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed sotne aggregate on top and grouting bolts etc for Bus bar chamber. The platform shall be such that it is of a height 45 cm above the nearest road level.
S&F of LED flood light Fitting 200 watt LED, suitable for mounting on High Mast Light structure, IP-66 protection, single peice pressure die cast aluminium housing high grade powder coated finish with heat resistant toughned clear glass cover for lamp and control gear compartment with high voltage surge protection device up to 5 KV, with bolts,nuts & washers complete all as specified and directed by the Engg-in-Charge.
Supply, laying and testing cable XLPE insullated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core complete all as specified and directed by the Engg-in-Charge.
Supply, laying and testing cable XLPE insullated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 3.5 core complete all as specified and directed by the Engg-in-Charge.
Supply, laying and testing cable XLPE insullated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 3.5 core complete all as specified and directed by the Engg-in-Charge.
Supply and laying GI tubes light grade ISI marked , galvanized, 50 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable complete all as specified and directed by the Engg-in-Charge.
Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 40 to 80mm bore and making good both ends complete all as specified and directed by the Engg-in-Charge.
Earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth strip 32x6 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical plate number 5 of MES SSR part-I(1991) complete all as specified and directed by the Engg-in-Charge. (a) Excavation and earth work for drilling hole for electrode in any type of Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed (d) 15 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing.
Supply & installing steel tubular swaged poles type 410 SP-31 (9 mtr long) of approx wt.147 kg conforming to IS 2713 (Part-II), complete with cast iron/MS plate 6mm thick and of size 300x300mm, final taper, pole cap, bolts, nuts, washers & screw etc including excavation, earth work, PCC foundation,PCC coping,GI pipe for cable protection etc. and GI bracket for fitting mounting, complete all as per manufacturer's instructions and as specified and as directed by E-in-charge. NOTE:- The unit rate in this item is deemed to be included the cost of exacavation and earth work in any type of soil,PCC foundation 1:4:8 type D-2 , PCC coping 1:2:4 type B-1 as in steel tubular pole and GI bracket made of GI pipe medium grade 40 mm bore, 1.5 mtr long for fixing of street light fitings along with clamps. The steel pole shall be painted by bituminious paint total length inside and up to planting depth outside and remaining portion of pole painted with two coat of aluminium paint over a coat of red oxide complete all as specified and directed.
Supply & installing steel tubular swan neck poles type 410 SP-31 (9 mtr long) of approx wt.147 kg conforming to IS 2713 (Part-II), complete with cast iron/MS plate 6mm thick and of size 300x300mm, final taper, pole cap, bolts, nuts, washers & screw etc including excavation, earth work, PCC foundation,PCC coping,GI pipe for cable protection etc. and GI bracket for fitting mounting, complete all as per manufacturer's instructions and as specified and as directed by E-in-charge. NOTE:- The unit rate in this item is deemed to be included the cost of exacavation and earth work in any type of soil,PCC foundation 1:4:8 type D-2 , PCC coping 1:2:4 type B-1 as in steel tubular pole and GI bracket made of GI pipe medium grade 40 mm bore, 1.5 mtr long for fixing of street light fitings along with clamps. The steel pole shall be painted by bituminious paint total length inside and up to planting depth outside and remaining portion of pole painted with two coat of aluminium paint over a coat of red oxide complete all as specified and directed.
S&F of LED street light Fitting 70 watt LED, IP-66 protection, single peice pressure die cast aluminium housing high grade powder coated finish with heat resistant toughned clear glass cover for lamp and control gear compartment with high voltage surge protection device up to 4.5 KV, prewired conductor to fitting with 3 core 1.5 sqmm pvc insulated cable complete all as specified and directed by the Engg-in-Charge.
S&F of bracket made out of GI tubing bended at proper angle of size 40mm dia,light grade 1.5 mtr long including painting with two coat of aluminium paint over one coat of red oxide to the bracket etc complete all as specified and directed by the Engg-in-Charge.
S&F in replacement KIOSK box wheather proof including made out of one piece mounted SMC base and door pole mounted hinged door size 333x233x120mm out side and 300x200x105mm inside dimensions comprising of aluminium bus bar 4 strips for 3 phase and neutral 63 Amps and 6A MCB SP with base including embossing/painting of danger notice of size not less than 10cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of KIOSK box body alongwith suitable size of clamp, nut, bolt and washer for fixing of KIOSK box on pole complete all as specified and directed by the Engg-in-Charge.
S&F MS clamp (suitable for holding street light bracket on steel/PCC pole) made out of 40 mm wide 6 mm thick flat iron with M.S nuts bolts 50 mm long 10 mm dia -3 Nos with flat washer (3mm thick) -02 No for each including painting with two coat of aluminium paint over one coat of red oxide to the M.S clamps complete all as specified and directed by the Engg-in-Charge.
Supply, drawing, connecting & testing of 3 core, 1.5 Sqmm PVC insulated and PVC rounded sheathed, copper conductor (flexible) industrial cable 1100 Volts grade conforming to IS-694 on steel tubular pole/PCC Pole from KIOSK box to light fittings including PVC conduit and providing suitable copper lugs all complete all as specified and directed by the Engg-in-Charge. Note : Steel tubular pole shall be measured and paid separetely.
S&F MS angle iron, flat,Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size complete all as specified and directed by the Engg-in-Charge.
S&F 3.15mm dia MS wire 75x75mm mesh , made up into mattress or cages appx 2.00 mtr height and fixed with flate iron /angle by welding in position complete all as specified and directed by the Engg-in-Charge.
M&L for 2 coat of synthetic enamel painting over a coat of red oxide to MS wire fencing including preparation of surface complete all as specified and directed by the Engg-in-Charge.
Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Engr-in-charge.
Commercial Traders (BID ID -3103932)
mayur enterprises (BID ID -3098827)
Microsys Controls India (BID ID -3109000)
MV Engineers And Contractors (BID ID -3098026)
Rajindera Enterprises (BID ID -3108645)
Ridhi engineers and builders (BID ID -3107232)
Vijay Electricals (BID ID -3107805)
M/s VINOD KUMAR SHARMA (BID ID -3108826)
DS CONSTRUCTION (BID ID -3106975)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .