Assistant Engineer, P.W.Dte., B.M.C. ESD
office of Assistant Engineer, P.W.Dte., B.M.C. ESD
SITC of 6 KVA on-line UPS at Radiotherapy Department under Burdwan Medical College and Hospital, Purba Bardhaman.
2024_WBPWD_779662_1
WBPWD/AE/BMCESD/NIeQ-05/24-25
Open Tender
Electrical Work/ Equipment
Item Rate
21 days
Purba Bardhaman
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,700
10 Feb 2025
5 Dec 2024
20 Dec 2024
5 Dec 2024
18 Dec 2024
5 Dec 2024
Amount
Supply, Installation, Testing & Commissioning of 6 KVA 1 ph/ 1ph IGBT Microprocessor based based DSP controlled PWM technology double conversion true on line UPS System having in built isolation Transformer at output, Input voltage range is 160-295V AC, Input THD<3% on liner load & THD<5% on non liner load, crest factor 3:1(max), Output voltage 208-240V AC, Efficiency 85%~92%, pure sine wave.The static bypass switch shall automatically transfer the critical load to bypass input supply without interruption after the logic senses one of the following conditions ups overload beyond rating, Battery runtime expired and bypass available for Inverter failure. Fatal error in control system. The static bypass switch shall be equipped with a manual means of transferring the load to bypass and back to inverter. Also UPS should have separate manual bypas switch. DC voltage 216 Volt the UPS sould be connected with battery bank consisting of required no of 12V, total 12480 VAH SMF VRLS battery which can provide minimum back up of 60 minutes on full load with open M.S Rack installation of battery & making necessary connection with suitable size of necy length copper wire, cable etc. (Make: AVO/ APC/ Numeric & Battery Make- Exide power safe / Amara Raja) Terms & Conditions:- 36 months onsite warranty on complete installation inclusive of spare parts, battery etc. from the date of installation.
UPS Technology & Capabilites
i) True online configuration with double conversion
ii) Fully digital control with three Digital Signal Processor including rectifier, Invertor, Charger. Protections Advanced electronic protection for device safety backed with MCBs, Fast acting fuses, High speed pulse blanking.
iii) Input power factor to load>0.99
iv) Main back feed protection
v) Lightning Protection Device
Overload Capacity
110% for 10 minutes, 125% for 1 minutes, 150% for 5 Second. 103% for continious.
UPS Display Panel
The Display panel should capable for display of following measurement/ as per standard availability of specified manufacturer.
i) Input - Voltage/ Frequency/ Current.
ii) By- pass - Voltage/ Frequency.
iii) Output - Voltage/ Frequency/ Current.
iv) Battery - Voltage/ Current/ history data/ residual capacity/ charging status.
v) Load - KVA/ KW/ Percentage
vi) Others standard measurement as per manufacturer standard & IS specification.
B) The display panel should also capable to display following indication
i) DC bus boltage - High/ Low
ii) Inverter - Overload / Short Circuit/ Low
iii) Over Temperature -Battery / By-pass/ Inverter
iv) Fault - Rectifier/ By-pass / Inverter/ Paralleling
v) Fuse failure- Input / Output
vi) Battery - Low/ Overcharged
vii) Mains - On / Fail / High / Low / Single Phasing
Switchgear:
MCB / MCCB for Input, Battery, Output & Manual Bypass Switch.
Alarms
The UPS should generates an audioble alarm for following condition.
Mains failour
Battery Low
UPS Over Load (>_ 110 %)
Fault
Shout Down
Battery Bank / Charger/ Rack
i) Minimum charger rating- 10% of battery AH rating offered
ii) Battery recharge time (after complete discharge) to 90% capacity -8-10 Hrs.
iii) Battery Protection - DC MCCB (Internal/ External)
iv) Battery End Cell Voltage - 1.75 V
v) Automatic float cum boost charging capability with settable float & boost charging voltage & current levels and boots charger time.
UPS Physical Condition
i) Operating Temperature- 40°C
ii) Humidity: 90% RH (Non Conditioning)
iii) Protection Class - IP-20
iv) Type of Cooling - Forced Air
v) Noice Level - <60db at 1 mtr distance
vi) All the electronic cards inside shall be with conformal coating to protect from harsh / Moist environment.
vii) UPS panel should have Dust filter protection with sensor.
viii) Monitoring Software: UPS Monitoring Software on Windows XP Platform
ix) Communication: RS 232, RS 485, SNMP Provided
x) Remote Monitoring features available.
Certification
ISO 9001: 2015, ISO 14001: 2015, ISO 18001, OHSAS 18001 CE Marking:IEC/EN 62040-1-1, IEC/EN 62040-2(EMC Emission),IEC/EN 62040-3(performance & Design)
Static Bypass Switch :-
i) The statich shall consist of fully rated Silicon Controlled Rectifiers (SCRs)
ii) The static bypass switch shall automatically transfer the critical load to bypass input supply without interruption after the logic senses one of the following conditions Inverter overload beyond rating. Battery runtime expired and bypass available. Inverter failure. Fatal error in control system.
iii) The static bypass switch shall be equipped with a manual means of transferring the load to bypass and back to inverter.
iv) Also UPS should have separate manual bypas switch.
Terms & Condition
i)Any Problem must be set right with 24 hrs after reporting.
ii) Two mobile nos of different responsible person must be specified alongwith offer for reporting of problems in future.
Carrying cost of battery and UPS to Burdwan site along with installation, fitting & fixing of accessories etc.
Supplying and fixing Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc. [D1/2b].
a) 240 Volt, DP, 63 A (Make:L&T/Havells/Legrand)
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required (Make: Havells/Gloster/Finolex). [E9/1]
i) 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC
S&F 32 A DP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and ncecessary conection (Make: Legrand/ABB/Siemens).
Rates to be quoted will be inclusive of all taxes incl. GST. No other additional charges will be applicable in addition to the quoted rates.
Dcon Enterprise (BID ID -5868383)
Rajalakshmi Enterprise (BID ID -5872399)
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .