Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.0 LAccepted-AOC 329 COD COLONY KOYLA NAGAR PO KIDWAI NAGAR KANPUR 208011 | KANPUR | KANPUR | UTTAR PRADESH | 208011 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹10.9 L+₹1.6 L (17.5%)Rejected-Finance 212 B 8 PARDEWANPUR LAL BANGLA KANPUR 208007 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208007 | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹14.4 L+₹5.1 L (55.1%)Rejected-Finance | L3 | Rejected-Finance Not Being L1 |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
16 Nov 2022, 6:00 pmClosed
GE I R and D Kanpur
GE I R and D Kanpur DMSRDE Complex, GT Road Kanpur 208013
REPAIR/REPLACEMENT MAINT OF EXTERNAL ELECTRIFICATION TO UNDERGROUND LT CABLE, LT PANELS, EARTHING CONTROL PANELS SERVICING CONNECTION AT TECH AND DOMESTIC AREA (WMC, MES COLONY, 60 SCIENTIST HOSTEL) AT GE(I) R and D KANPUR.
2022_MES_558856_1
8307/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE I R and D Kanpur
As Per NIT
8 documents required · 8 mandatory
₹500
GE I R and D Kanpur
₹30,000
Yes
16 Jan 2023
20 Oct 2022
18 Nov 2022
20 Oct 2022
16 Nov 2022
3 Nov 2022
20 Oct 2022 - 2 Nov 2022
Amount
Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables,foundation filling of poles or stays and for rerouting of cables.
All as per item No1.00 but depth exc 1.5 mtr but not exc 3.00 mtr
Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each all as required.
Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point.
M&L for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm, thick after laying, stretching and testing the cable
M&L for Sub class ‘B’ bricks old size. laid dry flat over the cable abutting each other, length of cable equal to width of brick all as required.
Supplying and laying un-reinforced precast concrete cable cover, class HV, type , size 300mm x 180mm x 40mm complete all as specified and directed. Make: Mehtab tiles Indore/Hind Mosaic Tiles Upleta. Note: Purchase voucher and manufacturer test certificate shall be submitted by contractor while claiming payment.
M&L for pre cast cement concrete ( 1:4:8) type D2 using 40mm graded stone aggregate for oundation filling of poles as mass concrete.
M&L for pre cast cement concrete ( 1:3:6) type D2 using 40mm graded stone aggregate for foundation filling of stays.
Demolition of cement concrete (un-reinforced) in ground, floors or pavings not exceeding 15 cm thick below or above ground level complete all as specified.
M & L for PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in floor / hard-standing, surface finished even and smooth without using extra cement to match with the existing surface complete all as specified.
M&L for drilling manually in soft / loose soil under road / hard standing / culvert / nala of suitable bore for protection cable & pipe upto 80 mm bore complete all as specified. Note: Depth of bore shall not be more than 1 Mtr from original ground level.
Taking out carefully unserviceable LT UG cable of size 6 Sqmm to 35 Sqmm from trenches and relaying same after repairs in same or other indicated location and testing complete all as directed. ( Note: Earth work, sand, bricks will be measured and paid separately)
Taking out carefully unserviceable LT UG cable of size 50 Sqmm to 240 Sqmm from trenches and relaying same after repairs in same or other indicated location and testing complete all as directed. ( Note: Earth work, sand, bricks will be measured and paid separately)
Taking out carefully unserviceable HT UG cable of size 70 Sqmm to 185 Sqmm from trenches and relaying same after repairs in same or other indicated location and testing complete all as directed. ( Note: Earth work, sand, bricks will be measured and paid separately)
Disconnecting electrically and taking out old unserviceable LT UG cables any type of size 6 Sqmm to 25 Sqmm 2 core all as spfd and directed.
Supply and laying to wall or poles or fixing or passing through pipe, in replacement of 1100 volts grade heavy duty cable with XLPE insulated aluminium multistranded conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and overall PVC sheathed 16 sq. mm nominal cross section 2 core in service connections all as required and directed. Make of cable : Gloster/Havells/ Paragon/ Grandlay/Kalinga. (Note : Incl making good all distributed wall surfaces/ flooring/tilling to match with existing specification)
All as per srl item No 17.00 above but cable of size 10 Sqmm 2 core.
All as per srl item No 17.00 above but cable of size 6 Sqmm 2 core.
Disconnecting electrically and taking out old unserviceable LT UG cables any type of size 25 Sqmm to 95 Sqmm 3.5 core all as spfd and directed.
Disconnecting electrically and taking out old unserviceable LT UG cables any type of size 120 Sqmm to 240 Sqmm core all as spfd and directed.
Supply and laying in trenches or fixing to wall/pole or passing through pipe in replacement of XLPE insulated heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 25 Sqmm 3.5 core.Make of cable ICL/ICC/Gloster/Havells/ Paragon/ Grandlay/Kalinga. (Note : Incl making good all distributed wall surfaces/ flooring/tilling to match with existing specification)
All as per srl item No 22.00 above but cable of size 35 Sqmm 3.5 core.
All as per srl item No 22.00 above but cable of size 50 Sqmm 3.5 core.
All as per srl item No 22.00 above but cable of size 70 Sqmm 3.5 core.
All as per srl item No 22.00 above but cable of size 95 Sqmm 3.5 core.
All as per srl item No 22.00 above but cable of size 120 Sqmm 3.5 core.
All as per srl item No 22.00 above but cable of size 150 Sqmm 3.5 core.
S&F in replacement of Cable jointing kit for 1100 volt grade cable for outdoor/indoor termination end joint heat shrinkable type complete with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 16 to 35 Sqmm 3.5/4 core.
All as per item No 29.00 above but for 6 to 25 Sqmm 2 core size.
All as per item No 29.00 above but for 50 to 95 Sqmm size.
All as per item No 29.00 above but for 120 to 185 Sqmm size.
All as per item No 29.00 above but for 225 to 300 Sqmm size.
S&F in replacement of cable jointing kit for 1100 volt grade cable for straight through termination heat shrinkable type complete with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 10 to 16 Sqmm 3.5/4 core.
All as per item No 34.00 above but for 25 to 50 Sqmm size.
All as per item No 34.00 above but for 70 to 150 Sqmm size.
All as per item No 34.00 above but for 185 to 240 Sqmm size.
Disconnecting electrically and taking out old unserviceable HT UG cables any type of size 95 to 120 Sqmm 3 core all as spfd and directed.
Supply, laying in trenches or passing through pipe/ducts, fixed to wall or poles XLPE insulated screened XLPE sheathed galvanized steel strip or wire armoured electric power cable with alumn conductor of cross sectional area 95 Sqmm 3 core 11 KV rated suitable for earthed system including testing and commissioning all as specified and directed Note : (Excavation and earth work, sand cushioning brick covers and GI pipe etc shall be measured and paid separately. Make of cable:- Gloster/ Polycab/ Incab/ Universal/ CCI/Havells
All as per item No 39.00 above but HT 11 KV cable of size 120 Sqmm.
Supply and fix in replacement of cable straight through jointing kit for 11 KV grade cable termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm. Make of cable end box:- Denson/ M seal/ 3 M.
Supply and fix in replacement of cable straight through jointing kit for 11 KV grade cable termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm. Make of cable end box:- Denson/ M seal/ 3 M.
Supply and fix cable end jointing kit for 11 KV grade cable for indoor termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm. Make of cable end box:- Denson/ M seal/3 M.
Supply and fix cable end jointing kit for 11 KV grade cable for indoor termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm. Make of cable end box:- Denson/ M seal/ 3 M.
Supply and fix cable end jointing kit for 11 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm. Make of cable end box:- Denson/ M seal/ 3 M.
Supply and fix cable end jointing kit for 11 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm. Make of cable end box:- Denson/ M seal/3 M.
Dismantling from insulators and taking down ACSR conductor any size from HT/LT over head lines and depositing to MES store yead.
Dismantling insulator any type and any size from LT over head lines and fixing other side or depositing to MES store yard.
Dismantling, cross arms, clamps, supports made of channels or angle section etc including nuts and bolts and setting aside all as required at site or directed.
Dismantling stay assy complete including excavation for taking out PCC block breaking of PCC block for taking out MS plate and depositing iron item to MES store yard and removing of PCC from site.
Dismantling PCC/steel poles any type and any size including excavation for taking out pole, breaking of PCC block with due care and setting aside for reuse or depositing to MES stores yard.
Unbinding from insulators ACSR conductor any size of LT/HT over head line for repairs. Re-stretching of ACSR conductor to achieve proper sag and rebinding to the insulators using alumn/GI binding wire and making all existing cable connections all as required at site.
S&F Aluminium conductor of any size with steel reinforced all as specified and directed.
Supply and fix galvanized steel wire any size to LT over head line as continuous earth or fabrication of guarding cradles all as required at site or directed.
Supply, errecting and installation of steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9 metres long) duly painted with two coat of black bituminous paint through out, internally and externally up to planning depth and painting remaining portion of pole with two coat of aluminium paint to the entire exposed surfaces over one coat of red oxide primer making/painting three Nos circular strips each of 30 cm wide with one yellow and 02 Nos black colour strip synthetic enamel paint and marking pole number with black paint all as spfd and directed. (Note : Excavation, earth work, PCC work shall be measured and paid separately under respective items)
M&L for cross arms, bracings, supports, clamps and back plates fabricated from steel section including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape ors size as indicated or directed and inclusive of oneprimer coat, one under coat and one finishing coat of alumn paint.
Disconnecting electrically, dismantling from foundation with due care and setting aside LT/HT fedder pillar box any type any size with all accessories.
Supply and installation, connecting eclectically & commissioning in replacement of LT feeder pillar box outdoor type of size 0.90 x 0.60 x 0.50 Mtr size factory fabricated made out of MS sheet of thickness 3.15 mm front door openable with locking arrangement mounted on angle iron legs made out of angle iron of size 40x40x6mm, 1.5 mtr long, 1.0 mtr above ground level and 0.50 mtr embedded in PCC blocks of size 0.30x0.30x0.50 mtr- 04 Nos duly painted with two coats of synthetic enamel paint over a coat of red oxide complete with 200 amps rated copper bus bar suitable for 3 phase 4 wire supply system duly drilled holes and making all cable connection with proper thimbles mounted on epoxy based post insulators and one MCCB 200 Amps 4 pole 415 Volt, 35 KA of make : Legrand/ Schneider/Havells/L&T complete all as required at site.
M&L for stay assy complete with MS stay plate of size 300x300x6mm thick, stay rod 16mm dia, stay bow, nuts, bolts and check nuts of GI all as shown in EP No 01 of SSR Part-I of 1991 or directed by Engr-in-charge ( Excavation, PCC, and loop type insulators will be measured separately).
M&L for loop type insulator large size with overall dimensions 90x140mm with clearance of hole 25.5 mm vitreous white brown or green.
Fixing only insulator any type and any size from HT/LT over head lines.
S&F Pin type, porcelain, vitreous, brown insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade
M&L in replacement of for GI tubing light grade 80mm bore with fittings laid for protection of cable under road crossing fixed to walls or pole complete all as specified and as directed. (Clamps for fixing pipe, nuts, bolts washers shall be measured separately)
All as per srl item No 63.00 above but 50mm bore
All as per srl item No 63.00 above but 40mm bore
S&F in replacement of bus bar chambers 300 mm long iron clad with 4 Nos 200 Amp rated copper strips complete fixed flush wall and making good the disturbed wall surfaces all as a required at site or directed.
All as per srl item No 66.00 above but with 4 Nos 100 Amp.
Repair, maint and of broken doors for LT panel and bus bars by welding and incl fixing of new hinges and other material as required at site complete all as spfd and directed.
Removal of unwanted vegetation/bushes/small plants shrubs around the water/electric supply installations/ inside the valve pit and surface excavation not esceeding 15 cm depth leveling the ground and removing the excavated material to a distance exceeding 50 M.
M & L for cutting, trimming of branches along the OH conductor of LT/ HT line within 2 mtr distance along both side of line and strictly all branches in one place as directed by Engineer-in-Charge.
S&F in replacement of MCCB 4 Pole 415 Volts 3 phase 400 Amps 36 KA, thermal magnetic release S1 -01 No (incoming). Make : Legrand/Siemens 3WL (ETU45B) / Schneider NW (6.0A)/L&T/ABB
All as per item No 71.00 above but MCCB 250 Amps 35/36 KA.
All as per item No 71.00 above but MCCB 100 Amps 25 KA.
All as per item No 71.00 above but MCCB 160 Amps 36 KA.
All as per item No 71.00 above but 63 Amps 25 KA.
All as per item No 71.00 above but MCCB 3 pole 100 Amps 25 KA.
All as per item No 71.00 above but MCCB 3 pole 160 Amps 36 KA.
Detection of any type of fault in HT/LT underground Line (laid in soil at plane area or forest area) with the help of Cable fault locator machine. Cable fault locator with carring vehicle will be brought by the cable fault detection agencies. Span of faulty cable will be trace out by the agencies by meggering HT cable. Note : 1. Detection of fault in one span of length will be measured as one Job either machine placed from one side or both side of the cable. 2. Technicians will be employed by the working agencies. 3. Earth work and taking out will be measured and paid seperately. 4. Material for repair and replacement measured and paid saperately. 5. One job shall be measured if the fault has successfully identified by the fault locator machine or removing moisture in the cable if required.
Servicing of switch air break gang operated device (GOD) 200 amps, 11/6.6 KV, by cleaning moving / fix contact jaw ,MS jumper / MS jumper carrier including replacement of ACSR Jumpers with PG clamps, nut bolts etc and providing white petroleum jelly and making all connection tightened and aluminium lugs etc complete and testing on full operating etc all as specified and directed.
Transportation of Transformer from site E/M yard to workshop for repairing and from workshop to site /E/M yard after repair etc of capacity upto 750 KVA all as specified and directed. NOTE : The rate deemed to be included of transportation charges.
Material and labour for dismantling of complete HV/LV coils of transformer upto 400 KVA (11/6.6/0.433 KV) and segregating, serviceable and unserviceable coils, serviceable coils shall kept aside for reuse after complete varnishing and testing of each coil including removal of complete core and accessories such as HV / LV bushings with metal parts, oil temp indicator ,winding temp indicator and disconnection of OTI, WTI all as specified and directed by Engineer-in-Charge. Note : 1. Rewinding of defective HV / LV Coils shall be measured and paid seperately. 2. The rate deemed to be included of all tools and plants.
Dismantlling top cover of transformer of capacity upto 400 KVA , any make for repair / replacement of HT / LT bushing of transformer or for replacement of top cover gasket or for inspection of transformer or for minor internal repairs of transformer all including draining carefully transformer oil as required / upto the required level and refilling the same, re fixing the top cover of transformer after completion of the work including testing on completion complete all as specified and directed. Note - spare parts will be measured and paid separately
Dismantling old u/s HT 11 KV bushes and fixing in replacement of HT Bushes porcelain, vitreous with brass spindle, threaded with washer, nuts, lock and rubber seal suitable for transformer of capacity up to 400 KVA.
Dismantling old u/s LT bushes and fixing in replacement of LT bushes porcelain Vitreous with brass spindle threaded with washers nuts, locknuts and rubber seal for indoor/outdoor transformer of capacity up to 400 KVA.
Repairs to the leaks of transformer from tap switch/ fins/ any pats of body, by replacing gasket / seal , or Repairs to the leaks of transformer body / fins, by welding / brazing etc complete all as specified and directed.
M&L for taking out old burnt winding and rewinding of HT/LT coil of different type, capacity and make of transformer with approved quality supper enamelled copper wire/ strip of approved make of suitable gauge and number of turns along with allied materials like cork sheet, fibre glass insulations, paper insulations, cotton/ Empire tap and tube wooden blocks bolts, nuts and washer (Brass) soldering and other packing material etc. all as required at site or directed.
S&F Top gasket made of 3mm thick cork sheet with suitable holes for 11/6.6/0.433 KV transformer of any type/capacity including providing suitable size of bolts, nuts and washer for transformer top cover complete for any capacity/size transformer all as specified.
M&L for Open the cover of transformer any type/size on site and filling in with new transformer oil low viscosity of approved make as per IS-335 of 1992 including heating of oil and die-electric strength 40 KV when tested at 4mm gap all as specified.
S&F in replacement of temperature gauge circular dial type of standard size and dia suitable for indoor/outdoor type transformer upto 400 KVA.
M&L for replacement and full fill up fresh silica gel in assembly at site complete all as spfd.
Taking down carefully transformer any capacity, any make, any type from pole / plinth by dismantling, dis-connecting HT & LT sides, earthings of transformer, supporting angles / cross arms, shifting / transporting transformer carefully from the site and shifting/refixing in other location under GE Kanpur after cleaning and making all electrical/earthing connections all as spfd and directed.
M&L in replacement of earthing complete with galvanised cast iron earth plate electrode of size 600x600x6.3 mm thick as earth electrode with top edge of the earth plate not less than 1.5mtr below ground level using GI wire 4mm dia as earth continuity conductor connected to earth plate by means of GI thimbles nuts bolts washers all as directed including providing earth wire protection pipe GI light grade15mm dia from earth plate to main switch board/panel, watering pipe 20mm dia with wire mesh and funnel at top, earth pit and RCC pit cover in PCC 1:3:6 adequate quantity of charcoal dust and salt all around the erth plate, earth work in any type of soil remaing surplus excavated material all as required at site and specified in EP No 5 of SSR part I 1991 or directed incl testing on competion.
All as per srl item No 92.00 above but connected to galvanised iron strip 32x6mm earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electric plate No 3 connected to earth test point all as specified.
M & L for fixing earthing strip 32 x 6 mm aluminium strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required, In Repair,complete all as specified & directed.
santosh electronics
S B ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .