| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.0 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹16.7 L+₹5.7 L (51.7%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹17.5 L+₹6.5 L (58.7%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹19.6 L+₹8.6 L (78.2%)Rejected-Finance | L4 | Rejected-Finance L4 | |
| 5 | L5₹22.9 L+₹11.9 L (108.2%)Rejected-Finance | L5 | Rejected-Finance L5 |
Tender Value
₹17.5 L
EMD Value
₹35,000
Closing Date
30 Sept 2020, 6:00 pmClosed
Shri Niranjan Lal GE(S) BTD
Garrison Engineer (South) Bathinda Mil Stn
REPAIR REPLACEMENT OF INTERNAL UNSERVICEABLE POINT WIRING REWIRING FITTING FIXTURE DBs SUB MAIN WIRING SWITCHES AND CONNECTED ACCESSORIES OF OTM OF ZONE J WORKS UNDER AGE E/M-IV OF GE(S) BATHINDA MIL STN
2020_MES_371167_1
GE(S) BTD-22/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BATHINDA MIL STN
As per NIT
8 documents required · 8 mandatory
₹500
GE(S) BATHINDA
₹35,000
Yes
28 Nov 2020
21 Aug 2020
2 Oct 2020
21 Aug 2020
30 Sept 2020
18 Sept 2020
22 Aug 2020 - 31 Aug 2020
Amount
Taking down carefully existing unserviceable copper / aluminum point wiring (light, fan, socket) complete including removal of unserviceable fittings such as switches, switch-sockets, ceiling roses, etc and removing the retrieved materials from dismantling including making good the disturbed surface of walls, floors, ceilings etc to match with the adjoining work complete all as specified and directed by Engineer-in-Charge.
M&L point wiring for one light point / exhaust fan point /ceiling fan point controlled by one switch with 1.5 Sqmm (nominal area) PVC insulated, unsheathed multi strand copper conductor cable FR-LSH in and including concealed PVC conduit 20 mm dia, medium duty, ISI marked including new, steel terminal sunken boxes including suiable laminated sheet of thickness 3.00mm for one light point, fan point , controlled by one switch on the same board with other switch or independent including PVC insulated unsheathed 1.5 Sqmm multi stranded copper conductor cable FR-LSH connected to common earth dolly complete including cutting, chasing the surface and then making good the same in CM (1:3) and finishing the surface to match with existing surface etc complete all as specified and directed. (Note :- Switches, sockets etc shall be measured and paid for separately under appropriate items of Sch 'A' ).
All as per item No 2 but for socket outlet 5 pin, 6 Amp on same board complete all as specified and directed by Engineer-in-charge.
All as per item No 2 but for socket outlet 5 pin, 6 Amp on independent board complete all as specified and directed by Engineer-in-charge.
All as per srl item No.2 (here-in-before) but for one socket outlet 6 pin, 6/16 Amp with cable of 2.5 Sq mm, multi stranded copper conductor FRLSH cable on the independent board including provision of 2.5 Sq mm PVC insulated unsheathed with single core, multi stranded copper conductor FRLSH cable as earth wire to common earth & connecting to earth dolly complete all as specified and directed by Engineer-in-Charge.
All as per item No 2 here in before but for one light point controlled by two way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No 2 here in before but for call bell point complete all as specified and as directed by Engineer-in-Charge.
M & L for point wiring for one light / fan point controlled by one switch with 1.5 Sqmm (nominal area) PVC insulated, unsheathed multi strand copper conductor cable FR-LSH in existing conduit, and existing sunken boxes but including 3 mm thick phenolic laminated sheet top cover for sunken boxes flush to surface for one light point/fan point, controlled by one switch on the same board with other switch or independent including PVC insulated unsheathed 1.5 Sqmm copper conductor cable FR-LSH connected to common earth dolly complete including cutting, chasing the surface and then making good the same in CM (1:3) complete all as specified and directed by Engineer-in-charge. (Note :- Switches, sockets etc shall be measured and paid for separately under appropriate items of Sch 'A' ).
All as per item No 8 but for socket outlet 5 pin, 6 Amp on same board complete all as specified and directed by Engineer-in-charge.
All as per item No 8 but for socket outlet 5 pin, 6 Amp on independent board complete all as specified and directed by Engineer-in-charge.
All as per srl item No. 8 (here-in-before) but for one socket outlet 6 pin, 6/16 Amp with cable of 2.5 Sq mm, multi stranded copper conductor FRLSH cable on the independent board including provision of 2.5 Sq mm PVC insulated unsheathed with single core, multi stranded copper conductor FRLSH cable as earth wire to common earth & connecting to earth dolly complete all as specified and directed by Engineer-in-Charge.
All as per item No 8 here in before but for one light point controlled by two way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No 8 here in before but for call bell point complete all as specified and as directed by Engineer-in-Charge.
S& F switch piano flush type, 6 Amp 240 Volt, AC (ISI Marked) one way etc complete all as specified and directed by Engineer-in-charge.
S& F switch piano flush type, 6 Amp 240 Volt, AC (ISI Marked) two way etc complete all as specified and directed by Engineer-in-charge.
S&F one switch and one socket outlet 5 Pin 5 Amp 230 volts AC etc complete all as specified and directed by Engineer-in-charge. Note:- Switch and socket shall be of same make.
S&F one switch and one socket outlet multipurpose 3 Pin 5 Amp and 3 Pin 15 Amp 230 volts AC etc complete all as specified and directed by Engineer-in-charge. Note:- Switch and socket shall be of same make.
S&F 6 Amps bell push switch, 250 volts, AC ISI marked complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing call bell Ding-dong, 230 Volts AC supply complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing regulator for ceiling fan electronic step type suitable for 1200/1400 ceiling fan complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing ceiling rose surface bakelite 65mm x 50mm, 3 terminals with back plate etc complete all as specified and directed by Engineer-in-Charge.
Supply and fixing lamp holder angle/straight, including LED bulb 9/10W polycarbonate cased body with back plate suitable for batten fittings for landing T & wind shock complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in repair tube rod ecofriendly, 8W/9W polycarbonate body, 0.60m length, LED T8 (tubular lamp) 6500K, G13, 230V, 50HZ complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing sheet metal enclosures double door made out of CRCA mild steel sheet, flush mounted, acrylic door, 8 way, DB SPN 230 Volts, with 200 Amp rated bus bar, dust and vermin proof suitable for fixing MCB's and Isolators etc including taking down old DB of any type and capacity alongwith MCB etc complete all as specified and as directed by Engineer-in-Charge.
S & F sheet metal enclosures double door made out of CRCA mild steel sheet, flush mounted, acrylic door, 4 way, DB TPN 415 Volts, with 200 Amp rated bus bar, dust and vermin proof suitable for fixing MCB's and Isolators etc including taking down old DB of any type and capacity alongwith MCB etc complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in repair single pole and neutral sheet metal enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp 240 Volt complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in repair MCB, SP, 6 to 32 Amps, 'C' curve, 230 Volts, breaking capacity not less than 10 KA with over load and short circuit protection complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in repair MCB, SPN, 40 to 63 Amp, 230 Volts, 'C' curve breaking capacity not less than 10 KA with over load and short circuit protection,50 Hz including necessary attachment complete all as specified and as directed by Engineer-in-Charge
Supply and fixing in repair MCB, TPN, 100 Amp, 230 Volts, 'C' curve breaking capacity not less than 10 KA with over load and short circuit protection,50 Hz including necessary attachment complete all as specified and as directed by Engineer-in-Charge
Supply and fixing in repair MCB, TPN, 63 Amp, 230 Volts, 'C' curve breaking capacity not less than 10 KA with over load and short circuit protection,50 Hz including necessary attachment complete all as specified and as directed by Engineer-in-Charge
Supply and fixing in repair MCCB 4 pole, 230 volt, 63 Amp, 50 Hz with rupturing capacity 25KA, 'C' series complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repair MCCB 4 pole, 230 volt, 100 Amp, 50 Hz with rupturing capacity 25KA, 'C' series complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repair MCCB 4 pole, 230 volt, 160 Amp, 50 Hz with rupturing capacity 25KA, 'C' series complete all as specified and directed by Engineer-in-Charge.
Material and Labour for sub main wiring with 2 single core cable 6 sqmm, 1100 votls grade PVC insulated unsheathed of copper multi strandard conductor FRLSH cable with continuous copper earth conductor of size 6 sqmm, 1100 votls grade drawing through in & including PVC concealed conduit medium grade of size 20mm along with accessories such as Tee, elbow, bend etc including taking down old sum in wiring of any type and capacity complete all as specified and as directed by Engineer-in-Charge. Note :- Two runs of cable and one run of earthing wire shall be measured as one unit.
Material and Labour for sub main wiring with 2 single core cable 6 sqmm, 1100 votls grade PVC insulated unsheathed of copper multi strandard conductor FRLSH cable with continuous copper earth conductor of size 6 sqmm, 1100 votls grade drawing through existing PVC concealed conduit medium grade of size 20mm along with accessories such as Tee, elbow, bend etc including taking down old sum in wiring of any type and capacity complete all as specified and as directed by Engineer-in-Charge. Note :- Two runs of cable and one run of earthing wire shall be measured as one unit.
M&L point wiring for one light point / exhaust fan point /ceiling fan point controlled by one switch with 1.5 Sqmm (nominal area) PVC insulated, unsheathed multi strand copper conductor cable FR-LSH in and including concealed PVC conduit 20 mm dia, medium duty, ISI marked including new, steel/GI terminal boxes required modules suitable for modular switch/socket/fan including support plate and frame cover flush to surface for one light point, fan point , controlled by one switch on the same board with other switch or independent including PVC insulated unsheathed 1.5 Sqmm multi stranded copper conductor cable FR-LSH connected to common earth dolly complete including cutting, chasing the surface and then making good the same in CM (1:3) and finishing the surface to match with existing surface etc complete all as specified and directed by Engineer-in-charge. (Note :- Switches, sockets etc shall be measured and paid for separately under appropriate items of Sch 'A' ).
All as per item No 36 but for socket outlet 5 pin, 6 Amp on same board complete all as specified and directed by Engineer-in-charge.
All as per item No 36 but for socket outlet 5 pin, 6 Amp on independent board complete all as specified and directed by Engineer-in-charge.
All as per srl item No. 36 (here-in-before) but for one socket outlet 6 pin, 6/16 Amp with cable of 2.5 Sq mm, multi stranded copper conductor FRLSH cable on the independent board including provision of 2.5 Sq mm PVC insulated unsheathed with single core, multi stranded copper conductor FRLSH cable as earth wire to common earth & connecting to earth dolly complete all as specified and directed by Engineer-in-Charge.
All as per item No 36 here in before but for one light point controlled by two way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No 36 here in before but for call bell point complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing modular switch piano, flush type, one way, 5/6 Amps 230 Volts AC including decorative frame cover etc complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing Switch piano, Modular flush type, two way, 5/6 Amps 230 V AC including decorative frame cover etc complete all as specified and as directed by Engineer-in-Charge.
S&F 6 Amps bell push switch, modular type including decorative frame cover 250 volts, AC complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing modular, One switch and one socket outlet, 5 Pin, 6 Amps 230 Volts AC including decorative frame cover etc complete all as specified and as directed by Engineer-in-Charge. Note:- Switch and socket shall be of same make
Supply and fixing modular, One switch and one socket outlet, multipurpose 6 Pin, 5 Amp and 3 pin 15 Amp, 230 Volts AC including decorative frame cover etc complete all as specified and as directed by Engineer-in-Charge. Note:- Switch and socket shall be of same make
Supply and fixing modular fan regulator electronic step type (1-4), socket type 230-240 Volt AC supply with frame complete all as specified and as directed by Engineer-in-Charge
S&F in repair over voltage release 230 V AC UC 230 Volts, 2 module with MCB DP (2 Module) 32 Amp etc complete all as specified and directed by Engineer-in-Charge.
S & F in repair LED light fitting 34/36W New generation energy saving and environment friendly long life LED EDGE LIT luminaire suitable for armstrong grid ceiling complete. The driver should be procured separatly but the quoted rate should be inclusive of both fitting and driver. The fixture size in mm is 595x595x70. The module and the driver should be ordered at the same time complete with all accessories internally prewired and fixing on wall or ceiling by using twin core flexible cable 23/0.00076 from ceiling rose to LED light fittings connection complete all as specified and as directed .
Supply and fixing in repair SITC high bay LED150 W IP66 with excellent heat dissipation, light in weight and small in size with system high lumen efficacy including fixing with suitable size clamps, nuts, bolts etc. at a height of about 12 m complete all as specified and as directed by Engineer-in-Charge. Note:- (i) The point wiring with 2.5sqmm under the conduit is approximate 15mtr height from switches ( Poles of street light). (ii) The contractor should deploy experience labour with proper arrangement like ladder, tools etc as per site requirement. (iii) The contractor sholud provide all safety precaution to the labour during work. No extra payment is to be given on this account. (iv) The contractor should provide original purchase voucher, test certificate, lM-79 report from the manufacturer of LED light (v) There should be unconditional guarantee/warranty of LED fittings for minimum guarantee period of two years for which the contractor is liable. (vi) The contractor should visit the site before quoting the rate. (vii) Taking down of old retrieved fittings shall be included in the quoted rate. All fittings shall be deposted to AGE E/M-IV store yard. (viii) The quoted rate should include the cost the cost of repairing of "E board/Gypsum Board/POP ceiling damaged during the fixing of fittings.
S & F in repair LED Post Top fitting of 15W, energy saving, environmental friendly, powder coated aluminium die cast and spun aluminum with clear/opal diffuser and suitable for landscape lighting complete all as specified and directed. Note:- Sample will be approved by GE from list of make attached in tender documents before bulk procurement.Nothing extra shall be paid on this account.
S & F in repair LED Post Top fitting of 25W, energy saving, environmental friendly, powder coated aluminium die cast and spun aluminum with clear/opal diffuser and suitable for landscape lighting all as specified and directed.
S & F in repair energy efficient LED street light of 25 Watt with PDC aluminium body and clear glass with lens for wide beam distribution, top maintainable type with IP 66 degree of protection, PF>0.95 with voltage range 140 to 170 Volt, fitting should be provided with inbuilt 5KV minimum surge protection, short circuit and over voltage protection facility for driver and fitting including 25 watt LED lamp with GI bracket-01 No, MS clamp-02 Nos suitable for walls/columns metre long twin core round copper conductor cable of 1.50 metre long twin core round copper conductor cable of suitable size and testing complete all as specified and directed by Engineer-in-charge.
S & F in repair LED Tube rod 18W/ 20W/ 21W/ 22W, Polycarbonate body, 1.2m length, LED T8 (Tubular lamp), 6500K, G13 Lamp holders, 230V, 50Hz with & including precoated CRCA frame/ fitting suitable for holding T8 LED tubular Lamps, 1.2m length, 230V, 50Hz. The frame should be compatible with LED. The total fitting should be complete including LED driver, other accessories and rest complete all as specified and directed by Engineer-in-charge. Note: (i) The LED tube rod and CRCA frame should be of same make and they should be compatible with each other. (ii) The LED Tube shall be warranted for two years from the date of completion of work.
S&F in repair Intergal post top lanterns Moulded plastic capsul which houses lamp holder for x11 w led bulb including 1x11w LED bulb and connection of light complete all as specified and as directed.
Supply and fixing in repair 40mm bore GI tubing light grade with all fittings cut into suitable length including fixtures for base of post top lantern etc complete all as specified and directed .
Material and labour for cement concrete (1:4:8), type D-2 using 40 mm graded stone aggregate as in pole foundation etc complete all as specified and as directed by Engineer-in-charge.
Material and labour for cement concrete (1:3:6), type C-1 using 20 mm graded stone aggregate as in coping etc complete all as specified and as directed by Engineer-in-charge.
Supplying and fixing in repair 1100 volts grade heavy duty cable 10 Sqmm solid conductor PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular including taking down old service wire of any type and section complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in repair rigid non-metallic PVC conduit 25mm dia exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as plers, lock nuts, saddles, pipe hooks etc. complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in repair sheet metal board fabricated out of CRCA sheet 2.25 mm thick, double door single opening suibale for fixing MCBs, DBs, MCCBs with locking arrangement, verman proof and powder coated internally & externally of size 1200 mm x 800x 300 mm fixed flush in position with cement & sand mortar (1:4) complete all as specified and directed.
Supply and fixing in repair sheet metal board fabricated out of CRCA sheet 2.25 mm thick, double door single opening suibale for fixing MCBs, DBs, MCCBs with locking arrangement, verman proof and powder coated internally & externally of size 600mm x 600x 200 mm fixed flush in position with cement & sand mortar (1:4) complete all as specified and directed.
Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (PCC 1:2:4 B-1 using 20 mm graded stone aggregates for concrete pit including 10 mm thick CI cover frame) depth of pit not less than 2.25 m below normal ground level with top edge of the plate not less than 1.5 m below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal / coal dust and common salt filling in alternate layers and connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts check nuts and washers of GI or steel and connecting to earthing test point, main switch board, testing on completion including GI pipe 20 mm dia light grade for watering and bringing out the watering pipe upto 30 cm above the normal ground level plugged at top including all fitting and GI pipe 15 mm dia light grade for the protection of GI wire from earth pit to earth point, all as specified as shown in electrical plate No 3 SSR Part-I and testing on completion including taking down old earthing complete all as specified and as directed by Engineer-in-Charge. Note :- PCC chamber shall be constructed at least 1.5 m away from earth pit pipe for watering shall be provided in slanting manner.
S& F switch piano flush type, 6 Amp 240 Volt, AC (ISI Marked) one way etc for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
S&F one socket outlet 5 Pin 5 Amp 230 volts AC etc for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
S&F one socket outlet multipurpose 3 Pin 5 Amp and 6 Pin 15 Amp 230 volts AC etc for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
S& F switch piano flush type, 15 Amp 240 Volt, AC (ISI Marked) one way etc for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing call bell Ding-dong, 230 Volts AC supply for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair PVC pipe connection hot/ cold type, 15mm bore 450mm long having brass nuts and washers on both ends for geysers and including taking down of existing unserviceable one for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair PVC pipe connection hot/ cold type, 15mm bore 600mm long having brass nuts and washers on both ends for geysers and including taking down of existing unserviceable one for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair indication light square/round as per existing at site and taking out old unserviceable one with matching to exist one with all connection for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair element of 1/1.5/2 KW for up to 50Ltr geyser as per existing at site including connection after and including dismantling of existing unserviceable element from geyser for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair thermostat matching to exist one including all connection after and including dismantling of existing unserviceable one for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
S & F in repair surface mounted, LED ceiling light 230 Volt, 12 watt complete fitting and all other accessories including electric connection connecting with using flexible copper wire twin core for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- (i) The rate of LED lamp of 12 watt base is deemed to be included in the quoted rate.Nothing extra shall be paid on this account. (ii) AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair LED mirror light of 07 watt, 6000K, linear & compact with decorative grey end caps, polycarbonate body and ribbed opal diffuser complete including 07 watt tube rod complete connecting to electric point by using PVC insulated twin core copper conductor cable of suitable size for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair 18/20 watt Retro LED tube light fitting, wall/surface mounted, IP 20 protection, conforming to IS16106/IS16107, minimum 6000K batten decorative type 4 feet long polycarbonate body, white , in built LED driver, power factor >0.95, connecting to electric point by using PVC insulated twin core copper conductor cable of suitable size for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
S & F in repair surface mounted, decorative round bulk head luminaire comprising of high brightness LED lamp 10/12 Watt, 6000K polycarbonate with IP65 protection, the system wattage of fitting should not be more than 5 watt ± 10%, surge protection of minimum 2KV, power factor should be more than 0.90, cool while colour, total hormonic distoration (THD) should not be more than 15% lumen output should not be less than 900 lumens, total input voltage range 140-280V AC, colour rendering Index should not be less than 80 complete including all other accessories and fitting arrangement including electric connection connecting with using flexible copper wire twin core upto ceiling rose/conector for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Notes:- (i) AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
S&F in repair decorative wall mounting light fixture made up of poly carbonate with 7 watt LED bulb ( B-22 base) for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Notes:- (i) AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair LED Tube rod ecofriendly, 8W/9W polycarbonate body, 0.60m length, LED T8 (tubular lamp), 6500K, G13, 230V, 50Hz with and including CRCA fitting/batten suitable for holdinhg T8 LED tubular Lamps, 0.6m length, , 230V, 50Hz. The frame should be compatible with LED. The total fitting should be complete including LED driver, other accessories for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Notes:- (i) AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard. (ii) The LED tube rod and CRCA frame should be of same make and they should be compatible with each other complete all as specified and directed by Engr--in-Charge
Supply and fixing regulator for ceiling fan electronic step type suitable for 1200/1400 ceiling fan for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair 3mm thick Laminated Hylam sheet cover of approx size 125mmx125mm including fixing of existing switch, socket etc in new sheet for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair 3mm thick Laminated Hylam sheet cover of approx size 125mmx200mm including fixing of existing switch, socket etc in new sheet for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair 3mm thick Laminated Hylam sheet cover of approx size 200mmx275mm including fixing of existing switch, socket etc in new sheet for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Supply and fixing in repair LED Tube rod ecofriendly, 20W/22W polycarbonate body, 1.20m length, LED T8 (tubular lamp), 6500K, G13, 230V, 50Hz for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
S & F in repair MS sunken boxes of approx size 100mmx100mm x60mm of thickness as per IS14772-2000 of same board/independent board/power board including fixing of old existing sheet, switch and socket etc fixed on old sunken boxes to make the board fully functional for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
S & F in repair MS sunken boxes of approx size 175mmx100mm x60mm of thickness as per IS14772-2000 of same board/independent board/power board including fixing of old existing sheet, switch and socket etc fixed on old sunken boxes to make the board fully functional for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
S & F in repair MS sunken boxes of approx size 175mmx250mm x60mm of thickness as per IS14772-2000 of same board/independent board/power board including fixing of old existing sheet, switch and socket etc fixed on old sunken boxes to make the board fully functional for AARMAN COMPLAINTS on daily basis complete all as specified and directed by Engineer-in-charge. Note:- AARMAN COMPLAINTS shall be attended on daily basis and no extra charges shall be paid on this account. Also refer Sch 'A' notes in this regard.
Aman Enterprises
M/S SODHI ASSOCIATES
M/s NIRMAN BUILDERS
M/s VISHAL ELECTRIC STORE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .