| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹81.1 LAccepted-AOC | 1 | Accepted-AOC being lowest | |
| 2 | 2₹82.1 L+₹70,958 (0.87%)Rejected-Finance | 2 | Rejected-Finance not lowest | |
| 3 | 3₹83.4 L+₹2.0 L (2.40%)Rejected-Finance | 3 | Rejected-Finance not lowest | |
| 4 | 4₹88.5 L+₹7.1 L (8.74%)Rejected-Finance PASCHIM BHAGABANPORE DARUA CONTAI PURBA MEDINIPUR 721401 | PURBA MEDINIPUR | PURBA MEDINIPUR | WEST BENGAL | 721401 | 4 | Rejected-Finance not lowest | |
| 5 | 5₹97.8 L+₹16.3 L (20.1%)Rejected-Finance AT BALANTAR POST PATHARA VIA KHALLIKOTE DIST GANJAM ORISSA 761029 | GANJAM | ODISHA | 761029 | 5 | Rejected-Finance not lowest |
Tender Value
₹89.3 L
EMD Value
₹1.9 L
Closing Date
28 Jul 2022, 6:00 pmClosed
CWE NO 2 VISAKHAPATNAM
CE Complex Railway station Road Visakhapatnam 04
PROVISION OF CENTRAL GAS PIPE LINE AND MANIFOLD ROOM AT INHS NIVARINI AT INS CHILKA
2022_MES_530377_1
82572
Open Tender
Miscellaneous Works
Lump-sum
364 days
GE CHILKA
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
GE Chilka
₹1.9 L
Yes
23 Aug 2022
11 Jun 2022
30 Jul 2022
11 Jun 2022
28 Jul 2022
4 Jul 2022
11 Jun 2022 - 4 Jul 2022
Amount
Schedule "A" Part – I to Schedule "A" Part – VIII: NOTE: Schedule "A" Part – I to Part – VII are prepriced by MES. Bidders shall insert their Lumpsum amount in Green coloured field under Column - 6 only
Lumpsum price worked out by the contractor for “BUILDING” as listed in Schedule ‘A’ Part - I , inserted by MES on serial page No. 26
Lumpsum price worked out by the contractor for "Earthwork Excavation", as listed in Schedule "A" Part – II on Serial Page No.27.
Lumpsum price worked out by the contractor for “PATH” as listed in Schedule ‘A’ Part - III , inserted by MES on serial page No. 28
Lumpsum price worked out by the contractor for “INTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part - IV , inserted by MES on serial page No. 30
Lumpsum price worked out by the contractor for "EXTERNAL ELECTRIFICATION", as listed in Schedule "A" Part – V on Serial Page No. 32
Lumpsum price worked out by the contractor for "AREA DRAINAGE", as listed in Schedule "A" Part – VI on Serial Page No. 33.
Lumpsum price worked out by the contractor for "CENTRAL GAS PIPE LINE SYSTEM", as listed in Schedule "A" Part – VII on Serial Page No. 34.
Schedule "A" Part - VIII: [Miscellaneous Items for Sch "A" Part-IV, V & VII are not prepriced by MES and prepriced rate indicated as 0.00 under Col.5 signifies this fact only. Bidder shall insert their rates in Green colour filled under Col-6.
M&L green marble 18 to 20 mm thick (table rubbed and polished) in steps, jambs, pillars, window cills, cooking plateforms like in cement mortar (1:4) and including pointing in white cement (1:2) using marble dust with admixture of pigment to match with marble shade complete all as specified and directed.
Supply and fixing MCB 32 Amp, 240 Volt, SPN, breaking capacity 10 KA 'C' series, complete all as specified and directed. Make- C&S/Standard/Havells.
M&L point wiring with 1.5 sqmm single core, PVC insulated, unsheathed FRLSH copper cable, 1100 volts grade, with multi stranded copper conductor drawn through and including non-metallic, rigid non mettalic PVC conduit (medium grade) concealed in wall / ceiling with and including 1.5 sqmm single core PVC insulated, multistranded, unsheathed, FRLSH copper conductor cable as continuous earth continuity conductor (green in colour) with cast Iron / pressed steel terminal boxes 60 mm deep, on walls with 3 mm thick plastic laminated / hylam sheet cover, fixed on wall / other surfaces with brass screws and connecting to common earth dolly complete all as specified and directed for the following :-
One light / fan / exhaust / bell point controlled by one switch
One 3 pin 5 Amps socket out let on independent board.
One 3 pin 5 Amps socket outlet on same board with other switches.
All as per Sl. Item No. 12 above but with 2.5 Sqmm cable and 2.5 Sqmm earth continuity conductor for 15 / 16 Amps socket outlet on independent board
M & L concealed sub main wiring with 2 runs of 4 sqmm main wire along with 1 run of 4 sqmm earth wire (green in colour) single core FRLSH PVC insulated, unsheathed, multi-stranded, 1100 volts grade ISI marked copper conductor cable, drawn through and including adequate size rigid non-metallic PVC conduit (medium grade) with all fittings & accessories complete all as specified and directed. NOTE:- Two runs of main copper conductor, one run of earth wire and one run of PVC conduit shall be measured as one unit length.
S&F MCB 6 to 32 Amp, 240 Volt, SP, breaking capacity 10 KA 'C' series, complete all as specified and directed. Make- C&S/Standard/Havells.
S&F 20 W tubelight fitting with lamp, Endura linear LED Wall mounted LED batten with polycarbonate housing & intergated driver for efficient heat dissipatio with complete fitting.make: Havell Cat part No.- LUMILINEBS20WLED830SPCWH, Bajaj Cat part No. BCLSB 20 WH or equvalent to philips//CG/Surya roshini
Supply and lay fly ash brick of size 200x100x80mm locallly available as protection of cable in trenches complete all as specifed and directed.
M&L for cutting existing road/PCC /drain for laying of undergound cable and including necessary earth work and making good to match with the existing surface with PCC 1:3:6 Type CI using 20mm graded aggregates complete all as specified and directed.
Supply, installation, commissioning and testing of Oxygen Manifold: Main confirming to ISO standards with Middle Frames 2 Banks x 10 Cylinder per Each bank Oxygen Manifold (without cylinders) , suitable to withstand a pressure of 145 Kg/cm2, along with high-pressure copper annealed tail pipes with end Brass adapter suitable for oxygen cylinders and manifold. Top frame comprising of high pressure copper pipes of size 1/2” I.D. x 15 swg with high pressure brass fittings made of high tensile brass and connections through non- return valves; high pressure copper tail pipes, made of high pressure copper pipe of size 1/4” I.D. x 15 swg. The design of middle and bottom frames should be provided to fit both round and flat bottom cylinders safely. The manifold shall be tested (hydraulically) at 3500 psig and necessary test certificates accompany along with the supply. Only non helogenated polymer materials are to be used in the non return valves supplied along with the manifold complete all as specified and directed. Make:- Oxicareengineers/ Globalmedlife Solution/ Lifeline Medisol/ Aktiv
Supply, installation, commissioning and testing of Oxygen Manifold: Main confirming to ISO standards with Middle Frames 2 Banks x 2 Cylinder per Each bank Oxygen Manifold (without cylinders) , suitable to withstand a pressure of 145 Kg/cm2, along with high-pressure copper annealed tail pipes with end Brass adapter suitable for Oxygen Cylinders and manifold.Top frame comprising of high pressure copper pipes of size 1/2” I.D. x 15swg with high pressure brass fittings made of high tensile brass and connections through non- return valves; high pressure copper tail pipes, made of high pressure copper pipe of size 1/4” I.D. x 15 swg. The design of middle and bottom frames should be provided to fit both round and flat bottom cylinders safely. The manifold shall be tested (hydraulically) at 3500 psig and necessary test certificates accompany along with the supply. Only Non Halogenated Polymer materials are to be used in the Non Return Valves supplied along with the manifold. heavy duty regulator and special fittings for emergency system complete all as specified and directed. Make:- Oxicareengineers/ Globalmedlife Solution/ Lifeline Medisol/ Aktiv
Supply, installation, commissioning and testing of Nitrous oxyde Manifold: Main confirming to ISO standards with Middle Frames 2 Banks x 2 Cylinder per Each bank Oxygen Manifold (without cylinders) , suitable to withstand a pressure of 145 Kg/cm2, along with high-pressure copper annealed tail pipes with end Brass adapter suitable for Oxygen Cylinders and manifold.Top frame comprising of high pressure copper pipes of size 1/2” I.D. x 15swg with high pressure brass fittings made of high tensile brass and connections through non- return valves; high pressure copper tail pipes, made of high pressure copper pipe of size 1/4” I.D. x 15 swg. The design of middle and bottom frames should be provided to fit both round and flat bottom cylinders safely. The manifold shall be tested (hydraulically) at 3500 psig and necessary test certificates accompany along with the supply. Only Non Halogenated Polymer materials are to be used in the Non Return Valves supplied along with the manifold complete all as specified and directed. Make:- Oxicareengineers/ Globalmedlife Solution/ Lifeline Medisol/ Aktiv
Supply, installation, commissioning and testing of Nitrous oxyde Manifold: Main confirming to ISO standards with Middle Frames 1 Banks x 1 Cylinder per Each bank Oxygen Manifold (without cylinders) , suitable to withstand a pressure of 145 Kg/cm2, along with high-pressure copper annealed tail pipes with end Brass adapter suitable for Oxygen Cylinders and manifold.Top frame comprising of high pressure copper pipes of size 1/2” I.D. x 15 swg with high pressure brass fittings made of high tensile brass and connections through non- return valves; high pressure copper tail pipes, made of high pressure copper pipe of size 1/4” I.D. x 15 swg. The design of middle and bottom frames should be provided to fit both round and flat bottom cylinders safely. The manifold shall be tested (hydraulically) at 3500 psig and necessary test certificates accompany along with the supply. Only Non Halogenated Polymer materials are to be used in the Non Return Valves supplied along with the manifold. heavy duty regulator and special fittings for emergency system complete all as specified and directed. Make:- Oxicareengineers/ Globalmedlife Solution/ Lifeline Medisol/ Aktiv
Supply, testing and commissioning of Semi -automatic pisten type oxygen control with minimum FLOW CAPACITY 700 LPM, minimum two input points (Provision for one input, work in manual operation), operating temperatures +10 to +45 degree C, as per technical specifications, approved medical standards and consisting of following features complete all as specified and directed :- (a) Semi - Automatic control system consists two first stage regulators and consisting high pressure reducer panel, , high pressure input valve, input filter, 315 Bar input gauge, high pressure reducer body, pressure set up screw, high pressure reducer drain, high pressure gauge, 2nd stage regulator, regulator set up, plant output regulators, plant output pressure gauges, plant output connected piping, control/power wiring and all necessary arrangement complete and should comply Indian Medical Standards and should comply standard panel with ISO 10524-2, ISO 7396-1:2007/HTM02-01 as per technical specification.
(b) Control panel will have built in protection system to ensure safe operation by low voltage and all protections of surge, overload and earthfault. The Control panel shall include two pressure relief valves, one high pressure and one low pressure (c) The panel should have the capacity to withstand maximum operating pressure of 220 bar for safety purposes. (d) The main control unit must be protected by a mild steel with epoxy powder coated with a viewing window to monitor the digital display . Make:- Greggersen / Draeger /Penlon/ Tedisel Medical/ Trumph/ Aktiv
Supply, testing and commissioning of Semi -automatic Nitrous Oxidecontrol with minimum FLOW CAPACITY 700 LPM, minimum two input points (Provision for one input, work in manual operation), operating temperatures +10 to +45 degree C, all as per technical specifications, approved medical standards and consisting of following features complete all as specified and directed :- (a) Semi-Automatic control system consists two first stage regulators and consisting high pressure reducer panel, high pressure input valve, input filter, 315 Bar input gauge, high pressure reducer body, pressure set up screw, high pressure reducer drain, high pressure gauge, 2nd stage regulator, regulator set up, plant output regulators, plant output pressure gauges, plant output connected piping, control/power wiring and all necessary arrangement complete and should comply Indian Medical Standards and should comply standard panel with ISO 10524-2, ISO 7396-1:2007/HTM02-01 as per technical specification.
(b) Control panel will have built in protection system to ensure safe operation by low voltage and all protections of surge, overload and earthfault. The Control panel shall include two pressure relief valves, one high pressure and one low pressure (c) The panel should have the capacity to withstand maximum operating pressure of 220 bar for safety purposes. (d) The main control unit must be protected by a mild steel with epoxy powder coated with a viewing window to monitor the digital display . Make:- Greggersen / Draeger /Penlon/ Tedisel Medical/ Trumph/ Aktiv
Supply, installation, testing and commissioning of oxygen Gas outlet points complete with matching probe / adopter with one end suitable for Hose & other end suitable for terminal units complete set for Oxygen system as per technical specification as mentioned below complete all as specified and directed:- (a) The outlets shall be modular singles, and shall incorporate nameplate color-coding. The single modular outlets shall be of a design that provides for ganging of rough-in plates in the field to form multiples. (b) The gas services shall be sequentially arranged and located as shown on the plans with a minimum centerline spacing of 5 inches (12.5 cm) between outlets. (c) The outlets shall be capable of supporting dispensing equipment without the use of slide brackets. The medical gas outlets shall be designed so that, once installed, routine service of both the primary and secondary check valves can be accomplished without removing the nameplate or gas specific portions.
(d) The primary check valve shall be unitized and of the cartridge type. So that the primary check valve can be removed for service without shutting off the gas supply to the outlet, the secondary check valve shall operate automatically to stop the free flow of the pressure gas. (e) There shall be no secondary check for vacuum or gas evacuation service. Medical gas outlets that require the removal of the nameplate or gas specific components for routine service shall not be acceptable. (f) The outlets shall should meet with the provisions of council Directive of Medical Devices Directive. (g) All outlets are 100% tested for flow and leaks (h) The outlet nameplate shall be permanently color coded with a durable scratch-resistant and protective label. (j) Medical gas outlets shall be cleaned for oxygen service as per Medical Standards, capped and placed in a protective container for shipment. (k) The outlets shall be installed in strict accordance with manufacturer’s instructions, and tested before use in conformance with local and federal codes.
(l) Outlets shall be Double Lock Outlet type manufactured with an approx 165 mm length, Copper inlet pipe stub which is silver brazed to the outlet body. Body shall be of one piece brass construction. For positive pressure gas services, the outlet shall be equipped with a primary and secondary check valve and the secondary check valve shall have break safe mechanism and also comply to pressure test standards and rated at minimum 200 psi in the event the primary check valve is removed for maintenance.The outlet assembly should have separate colour coding for each services and will accept only corresponding gas specific adaptors. All outlets shall be cleaned and de-greased for medical gas service, factory assembled and tested.The medical gas outlets should be of quick connecting and wall mounted modular type. Terminal units must be colour coded in the front part with laser painting so that colour code last without wear and must contain an additional aluminium actuator in the front part which can be press locked and not screwed for easy service, maintenance and should be unbreakable. Make: S Kumar, Med Flow, UMED, G Flow
Supply,installation,testing and commissioning of DIN Probe Oxygen outlet complete all as specified and directed. Make: S Kumar, Med Flow, UMED, G Flow
All as per item No. 26 above but Vaccum Outlet
All as per item No. 26 above but N2O Outlet
All as per item No. 26 above but Air Outlet
Supply, Installation testing and commissiong of copper piping 35 mm OD x 0.9 to 1.2 mm thick (for oxygen, suction, air and nitrous oxide system) with complete fittings / fixtures as per technical specification and BS: 13348 and as mentioned below complete all as specified and directed:- (a) Installation of piping should be carried out as per approved medical standards with utmost cleanliness. (b) Only pipes, fittings and valves which have been degreased as per approved medical standards should be used . (c) Pipe fixing clamps for upto 28mm diameter. (d) Pipes should be non ferrous suitable for the diameter of the pipe and wherever required rigid metallic hanging or cemented supports to be used. (e) The main lines to the building to be taken overhead through heavy grade metallic poles or GI tubes with inspection points in metallic boxes wherever required . Adequate supports shall be provided while laying pipelines to ensure that the pipes do not sag. Suitable sleeves shall be provided wherever pipes cross through walls / slabs. All pipe clamps shall be non-reactive to copper.
(f) All pipe joints should be made using inert gas fluxless brazing method. (g) All joints should be of copper to copper and should be brazed by silver brazing filler material without flux while being brazed joints shall be continuously purged with oil free dry nitrogen to prevent the formation of copper oxide on the inside surface of the joint. (h) All pipes should be installed without springing or forcing. (j) All pipes should be protected against mechanical injury in a manner satisfactory to authorities having jurisdiction. (k) Test: After erection, all the new pipes cleaned or purged with the help of dry nitrogen gas. Complete system should be tested with dry nitrogen at 2 times of working pressure for 24 hours. (l) Painting: All existing and proposed exposed pipes/should be painted with two coats of Synthetic enamel paint & color codification as per IS : 2379 of 1963. and approved medical standards.
(m) All concealed pipes to have gas identification bands / labels at appropriate distance. (n) Similarly all pipes which need embedding in the wall should be tested / painted / labeled and properly insulated. (o) Certification: To be certified that pipes are suitable for the particular service and complete cross connection (anti-confusion) test should be carried out. (p) Distribution piping system: MATERIAL (PIPE): Solid drawn, seamless, deoxidized, non arsenical, half hard, tempered and degreased materials conforming to BS: EN 13348. Copper pipe must have reputed third party inspection certificate (E.g.Lloyd‟s or Kite marked or TUV or SGS). Fittings should be made of copper conforming to BS 864 and suitable for a working Pressure of upto 17 bar and especially made forbrazed socket type connections. All copper pipes should be inspected and certified for medical use before dispatch and the pipe should be delivered plugged or capped at both ends. Note: The tenderer shall design & submit complete layout drawings with proper colour code, fittings, fixtures complete for approval of GE or rep of accepting Officer before placing order and the quoted includes for the same Make: Mexflow / Janya / Metal Gem / Cubex .
All as per item No 30 above but copper pipe of size 28 mm x 0.9 mm thick for oxygen, suction, air and nitrous oxide system.
All as per item No. 30 above but copper pipe of size 22 mm x 0.9 mm thick for oxygen, suction, air and nitrous oxide system
All as per item No. 30 above but copper pipe of size 15 mm x 0.9 mm thick for oxygen, suction, air and nitrous oxide system
All as per item No. 30 above but copper pipe of size 12 mm x 0.9 mm thick for oxygen, suction, air and nitrous oxide system
Supply, Installation, testing and commissioning of 35 mm OD MEDICAL LINE VALVE or ISOLATING VALVE ( for oxygen, suction, air and nitrous oxide) as per CE CERTIFIED /HTM -2022/02-01/DIN/ISO/ BS EN 1057 or ball valves as per BS 1057 , rated at 400 psig, as well as full vacuum ( 29.9" Hg). Valves go from full ON to full OFF by turning the vinyl-gripped valve handle 90 degree Locking-type handles may be ordered separately when required. Copper tubing is factory installed to help prevent valve seat damage during soldering. main and riser valves are not required to be installed in a box unless specially noted or required complete all as specified and directed. Make: CONEX / RB/RN / SIM / AUDCO / AKTIV.
All as per Sl. Item No. 35 above but 28 mm
All as per Sl. Item No. 35 above but 22 mm
All as per Sl. Item No. 35 above but 15 mm
S&F in conversion kit oxygen complete all as specified and directed.
S&F conversion kit N2O complete all as specified and directed. Make: Oxicareengineers / Globalmedlife Solution / Lifeline Medisol / Aktiv
S&F probe for oygen terminal unit complete all as specified and directed. Make: Oxicareengineers / Globalmedlife Solution / Lifeline Medisol / Aktiv
S&F probe for N2O terminal unitall complete all as specified and directed. Make : Oxicareengineers / Globalmedlife Solution / Lifeline Medisol / Aktiv
S&F probe for vacuum terminal unit complete all as specified and directed. Make : Oxicareengineers / Globalmedlife Solution / Lifeline Medisol / Aktiv
S&F probe for air terminal unit complete all as specified and directed. Make : Oxicareengineers / Globalmedlife Solution / Lifeline Medisol / Aktiv
S&F BPC flowmeter with humidifier bottle complete all as specified and directed. Make : Oxicareengineers / Globalmedlife Solution / Lifeline Medisol / Aktiv
Supply, Installation, testing and commissioning of. Vacuum Pump 5HP - 2 Nos , Vacuum switch - 2 No., DOL starter - 2 No, 5 HP Motor - 2 No. with inter connecting pipes, necessary electric connection DB to starter / motor and special fittings complete all as specified and directed. Make: ANEST IWATA Model:BVLS 50 DE -5HP, IR, Boush or equivalent.
S&F 1000 ltr receiver tank for central suction system complete all as specified and directed.
S&F 750 ltr receiver tank for central medical air system complete all as specified and directed.
S&F filter of scrubber (1.25") complete all as specified and directed.
Supply, Installation, testing and commissioning of ward vacuum regulator with all fittings complete all as specified and directed. Make: Oxicareengineers / Globalmedlife Solution / Lifeline Medisol / Aktiv
Supply, Installation, testing and commissioning of theatre vacuum unit complete all as specified and directed. Make: Oxicareengineers/ Globalmedlife Solution/ Lifeline Medisol/ Aktiv
Supply, Installation, testing and commissioning of TRIDANT complete all as specified and directed. Make:- Desiccant Air Dryer. Model : DRYSPELL PLUS 20 - 25 CFM.
AREA ALAM PANELS : Supply, Installation, testing and commissioning of Digital Area Alarm Service fully complying with ISO 7396-1:2007 complete all as specified and directed for the following:- Make : Oxicareengineers / Globalmedlife Solution/ Lifeline Medisol / Aktiv
4 Gas alarm panel (oxygen, air, nitrous oxide and vacuum)
3 Gas alarm panel (oxygen, air and vacuum)
2 Gas alarm panel (oxygen and vacuum)
AREA VALVE BOX: Supply, Installation, testing and commissioning of Area Valve Service fully complying with ISO 7396-1:2007 complete all as specified and directed for the following:-. Make: Oxicareengineers / Globalmedlife Solution / Lifeline Medisol / Aktiv
4 Gas Valve box
3 Gas Valve box
2 Gas Valve box
M/s SHIVA BUILDERS
M/s Kamal Builders
RANA ENTERPRISES
ABHIMANYU MAHARANA
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .