Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹58.7 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹70.7 L+₹12.0 L (20.4%)Admitted-Finance VILLAGE KARTHOLI NATIONAL HIGHWAY BARI BRAHAMANA JAMMU JAMMU KASHMIR 181133 | SAMBA | JAMMU AND KASHMIR | 181133 | L2 | Admitted-Finance | |
| 3 | L3₹79.8 L+₹21.1 L (35.8%)Admitted-Finance | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | HI-TECH TRANSFORMERS L2 | ROHIT ASSOCIATES L3 | JAI VIJAY INFRASTRUCTURE COMPANY L1 |
|---|---|---|---|---|---|---|
| 1.00Augumentation of Sub Stations from 250KVA to 400KVA on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: Locations:- 1)250KVA Bandhore(ESD Hira Nagar) 2)250KVA Rajbagh(ESD Hira Nagar) 3)250KVA Barnoti(ESD Kathua) | ||||||
| 1.01 | 11/0.433kV, 400KVA, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Copper wound ), and with LV Cable Box having detachable Aluminium Gland plate | 3 | Nos. | 7,66,500 ₹22,99,500 | 5,40,000 ₹16,20,000 | 5,25,000 ₹15,75,000 Lowest |
| 1.02 | Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type | 3 | Set | 5,500 ₹16,500 | 7,000 ₹21,000 | 5,000 ₹15,000 Lowest |
| 1.03 | 11 kV Horn Gap Fuse Set 3 Phase 200A | 3 | Set | 5,500 ₹16,500 | 4,500 ₹13,500 Lowest | 5,000 ₹15,000 |
| 1.04 | 240mm² (02Ckt) Single Phase Cable,1.1K V Grade, PVC Insulated Stranded Conductor FRLS type(88Mtrs per Sub Station) | 264 | Mtr | 303 ₹79,992 | 150 ₹39,600 Lowest | 400 ₹1,05,600 |
| 1.05 | GI Channel/Angle/Flat of sizes(60Kg per Sub Station) | 180 | Kgs | 110 ₹19,800 | 80 ₹14,400 Lowest | 100 ₹18,000 |
| 1.06 | Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover(03Nos. per Sub Station). | 9 | Nos | 3,850 ₹34,650 | 1,000 ₹9,000 Lowest | 2,000 ₹18,000 |
| 1.07 | Pre Fabricated LT Switch(02Nos. Per Sub Station) | 6 | No. | 3,300 ₹19,800 | 1,000 ₹6,000 Lowest | 2,500 ₹15,000 |
| 1.08 | Foundation for 400KVA Distribution Transformer as per Drawing attached as Annexure A of SBD | 3 | No. | 71,500 ₹2,14,500 | 65,000 ₹1,95,000 | 30,000 ₹90,000 Lowest |
| 1.09 | Dismantling Charges of old Equipments(LA, HG, Cables, Iron of sorts etc) including carriage to Divisional Stores at Kathua at no cost.(Complete Job) | 3 | No. | 3,300 ₹9,900 | 1,000 ₹3,000 Lowest | 5,000 ₹15,000 |
Tender Value
Refer Docs
EMD Value
₹1.6 L
Closing Date
13 Mar 2021, 2:00 pmClosed
Executive Engineer, ED, Kathua
Office of the Executive Engineer, ED, Kathua
Augumentation of Sub Stations on Turnkey Basis falling under the jurisdiction of O M Division, KathuaJPDCL under Capex Budget for the Year 202021
2021_PDD_118794_1
Ked/37 of 2020-21 Dt.01.03.2021
Open Tender
Electrical Works
Turn-key
10 days
Kathua
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,000
Executive Engineer, ED, Kathua
₹1.6 L
17 Mar 2021
2 Mar 2021
15 Mar 2021
2 Mar 2021
13 Mar 2021
2 Mar 2021
2 Mar 2021 - 4 Mar 2021
Amount
Augumentation of Sub Stations from 250KVA to 400KVA on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: Locations:- 1)250KVA Bandhore(ESD Hira Nagar) 2)250KVA Rajbagh(ESD Hira Nagar) 3)250KVA Barnoti(ESD Kathua)
11/0.433kV, 400KVA, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Copper wound ), and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11 kV Horn Gap Fuse Set 3 Phase 200A
240mm² (02Ckt) Single Phase Cable,1.1K V Grade, PVC Insulated Stranded Conductor FRLS type(88Mtrs per Sub Station)
GI Channel/Angle/Flat of sizes(60Kg per Sub Station)
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover(03Nos. per Sub Station).
Pre Fabricated LT Switch(02Nos. Per Sub Station)
Foundation for 400KVA Distribution Transformer as per Drawing attached as Annexure A of SBD
Dismantling Charges of old Equipments(LA, HG, Cables, Iron of sorts etc) including carriage to Divisional Stores at Kathua at no cost.(Complete Job)
Augumentation of Sub Stations from 100KVA to 250KVA on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: Locations:- 1) 100KVA Tanda( ESD Hira Nagar) 2)100KVA Prehta(ESD Basholi) 3)100KVA Dali DyalaChak(ESD Hira Nagar) 4)100KVA Budhi (ESD Kathua) 5)100KVA Keeian W.No.2 (ESD Noagrota) 6)100KVA Prithvi Chak (ESD Kathua) 7)100KVA Haripur Patel (ESD Hira Nagar)
11/0.433kV, 250KVA, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Copper wound ), and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11 kV Horn Gap Fuse Set 3 Phase 200A
185mm² (02Ckt) Single Phase Cable,1.1K V Grade, PVC Insulated Stranded Conductor FRLS type(88Mtrs per Sub Station)
GI Channel/Angle/Flat of sizes(60Kg per Sub Station)
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.(03Nos. per Sub Station)
Pre Fabricated LT Switch(02Nos. Per Sub Station)
Dismantling Charges of old Equipments(LA, HG, Cables, Iron of sorts etc) including carriage to Divisional Stores at Kathua at no cost.(Complete Job)
Augumentation of Sub Stations from 100KVA to 250KVA on Turnkey Basis(Except Transformer) by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: Note:-250KVA transformer dismantled from the locations at s.no.1 above shall be used at below mentioned locations Locations:- 1) 100KVA Dhali Sumwan( ESD Kathua) 2)100KVA Jasrota (ESD Hira Nagar) 3)100KVA Dhar Nr. Church(ESD Billawar)
Dismantling, carriage, erection and commissionig of old 250KVA Transformer
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11 kV Horn Gap Fuse Set 3 Phase 200A
185mm² (02Ckt) Single Phase Cable,1.1K V Grade, PVC Insulated Stranded Conductor FRLS type(88Mtrs per Sub Station)
GI Channel/Angle/Flat of sizes.(60kg per Sub Station)
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.(03Nos. per Sub Station).
Pre Fabricated LT Switch(02Nos. Per Sub Station)
Dismantling Charges of old Equipments(LA, HG, Cables, Iron of sorts etc) including carriage to Divisional Stores at Kathua at no cost.(Complete Job)
Augumentation of Sub Stations from 63KVA to 100KVA on Turnkey Basis(Except Transformer) by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: Note:-100 KVA transformers dismantled from the locations at s.no.2 & 3 above shall be used at below mentioned locations Locations:- 1) 63KVA Dadwara ( ESD Billawar) 2)63KVA Nehi-Basti Dewal(ESD Billawar) 3)63KVA Amuwala Ramkot (ESD Ramkot) 4)63KVA Gujroo Nagrota (ESD Ramkot) 5)63KVA Plakh (ESD Basholi) 6)63KVA Batara (ESD Basholi) 7)63KVA Juthana (ESD Kathua) 8)63KVA Mai Chak (ESD Kathua) 9)63KVA Maroli(ESD Kathua) 10)63KVA Gadhyal(ESD Hira Nagar)
Dismantling, carriage, erection and commissionig of old 100 KVA Transformer
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11 kV Horn Gap Fuse Set 3 Phase 200A
185mm² (02Ckt) Single Phase Cable,1.1K V Grade, PVC Insulated Stranded Conductor FRLS type(44Mtrs per Sub Station)
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.(03Nos. per Sub Station)
Pre Fabricated LT Switch(01Nos. Per Sub Station)
Dismantling Charges of old Equipments(LA, HG, Cables, Iron of sorts etc) including carriage to Divisional Stores at Kathua at no cost(Complete Job)
Dismantling Charges of old 63KVA Transformers including carriage to Divisional Stores at Kathua at no cost(Complete Job)
HI-TECH TRANSFORMERS
ROHIT ASSOCIATES
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .