Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.4 LAccepted-AOC 37 4TH CROSS ASHWATHNAGAR SANJYANAGAR POST BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | L1 | Accepted-AOC Lowest bid value | |
| 2 | L2₹44.7 L+₹5.4 L (13.9%)Rejected-AOC 202 NEW RAM VIHAR COLONY PINTO PARK MORAR GWALIOR 474005 | GWALIOR | GWALIOR | MP | 474005 | L2 | Rejected-AOC Higher bid value | |
| 3 | L3₹69.7 L+₹30.4 L (77.7%)Rejected-AOC 1 A BASEMENT 30 31 RAJA HOUSE NEHRU PALACE NEW DELHI 110 019 | SOUTH EAST | DELHI | 110019 | L3 | Rejected-AOC Higher bid value |
| Sl No | Description | Qty | Unit | MONA GENERATOR SEVICES PVT. LTD. L3 | M/S J S PRAKASAM L1 | M/S AUTOMATION AND SWITCHGEAR CONTROL L2 |
|---|---|---|---|---|---|---|
| 1.00 | Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length- 2.10 mtr,height- 2.0 mtr and width- 0.5 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 800 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/platform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories complete all as specified and directed.
Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates. | 1 | Each | 2,92,228 ₹2,92,228 | 1,55,000 ₹1,55,000 Lowest | 2,50,000 ₹2,50,000 |
| 1.01Incoming:- (a) MCCB 4 Pole,630 Amps, adjustable type, 415 volt of breaking capacity not less than 50 KA - 01 No. (b) On load Changeover switch 415 Volt 4 pole of capacity 630 Amp- 01 No (c) Digital type ammeter composite type with suitable CT -01 No. (d) Indicator lamp LED type set of three(R,Y,B) - 1 No (e) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,125 Amps, 415 volt of breaking capacity not less than 25 KA -03 Nos. (b) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -07 Nos . (c) MCCB 4 Pole,63 Amps, 415 volt of breaking capacity not less than 16 KA -01 Nos . | ||||||
| 2.00 | Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length-1.65 mtr,height- 2.10 mtr and width- 0.5 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mmx50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 800 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/plateform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories complete all as specified and directed.
Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates. | 1 | Each | 3,18,467 ₹3,18,467 | 1,65,000 ₹1,65,000 Lowest | 2,00,000 ₹2,00,000 |
| 2.01Incoming:- (a) MCCB 4 Pole,630 Amps, adjustable type, 415 volt of breaking capacity not less than 50 KA - 01 No. (b) On load Changeover switch 415 Volt 4 pole of capacity 630 Amp- 01 No (c) Digital type ammeter composite type with suitable CT -01 No. (d) Indicator lamp LED type set of three(R,Y,B) - 1 No (e) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,200 Amps, adjustable type 415 volt of breaking capacity not less than 36 KA -05 Nos. (b) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -03 Nos . | ||||||
| 3.00 | Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length-1.50 mtr,height- 2.10 mtr and width- 0.5 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 750 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/platform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories complete all as specified and directed.
Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates. | 1 | Each | 2,33,191 ₹2,33,191 | 1,25,000 ₹1,25,000 Lowest | 2,25,000 ₹2,25,000 |
| 3.01Incoming:- (a) MCCB 4 Pole,500 Amps, adjustable type 415 volt of breaking capacity not less than 50 KA -01 No. (b) On load Changeover switch 415 Volt 4 pole of capacity 500 Amp - 01No (c) Digital type ammeter composite type with suitable CT -01 No. (e) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -08Nos . | ||||||
| 4.00 | Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length-3.50 mtr,height- 2.0mtr and width 0.5 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 1500 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/plateform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories.
Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates. | 1 | Each | 7,04,065 ₹7,04,065 | 2,50,000 ₹2,50,000 Lowest | 5,00,000 ₹5,00,000 |
| 4.01Incomming:- (a) ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 1250 Amps -01 No (b) On load Changeover switch 415 Volt 4 pole of capacity 1250 Amp-01 No (c) Digital type ammeter composite type with suitable CT -01 No. (d) Indicator lamp LED type set of three(R,Y,B) - 1 No (e) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -25 Nos . | ||||||
| 5.00 | Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length- 2.50 mtr,height- 2.15mtr and width- 0.95 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 1500 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/plateform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories complete all as specified and directed.
Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates. | 1 | Each | 6,16,193 ₹6,16,193 | 2,10,000 ₹2,10,000 Lowest | 4,20,000 ₹4,20,000 |
| 5.01Incomming:- (a) ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 1250 Amps -01 No (b) Digital type ammeter composite type with suitable CT -01 No. (c) Indicator lamp LED type set of three(R,Y,B) - 1 No (d) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,250 Amps,adjustable type 415 volt of breaking capacity not less than 50KA -08 Nos . (b) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -03 Nos . | ||||||
Tender Value
Refer Docs
EMD Value
₹91,270
Closing Date
25 Aug 2025, 6:00 pmClosed
GE (AF) BANGALORE
GE (AF) BANGALORE, HQ TC AIR FORCE , BANGALORE - 560006
SPL REPAIR TO LT PANELS AND E/M INSTALLATION AT HQTC (U)
2025_MES_722142_1
8382/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) BANGALORE
AS PER NIT
5 documents required · 5 mandatory
₹500
GE (AF) BANGALORE
₹91,270
6 Sept 2025
23 Jul 2025
28 Aug 2025
23 Jul 2025
25 Aug 2025
6 Aug 2025
24 Jul 2025 - 31 Jul 2025
Amount
Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length- 2.10 mtr,height- 2.0 mtr and width- 0.5 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 800 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/platform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories complete all as specified and directed. Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates.
Incoming:- (a) MCCB 4 Pole,630 Amps, adjustable type, 415 volt of breaking capacity not less than 50 KA - 01 No. (b) On load Changeover switch 415 Volt 4 pole of capacity 630 Amp- 01 No (c) Digital type ammeter composite type with suitable CT -01 No. (d) Indicator lamp LED type set of three(R,Y,B) - 1 No (e) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,125 Amps, 415 volt of breaking capacity not less than 25 KA -03 Nos. (b) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -07 Nos . (c) MCCB 4 Pole,63 Amps, 415 volt of breaking capacity not less than 16 KA -01 Nos .
Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length-1.65 mtr,height- 2.10 mtr and width- 0.5 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mmx50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 800 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/plateform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories complete all as specified and directed. Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates.
Incoming:- (a) MCCB 4 Pole,630 Amps, adjustable type, 415 volt of breaking capacity not less than 50 KA - 01 No. (b) On load Changeover switch 415 Volt 4 pole of capacity 630 Amp- 01 No (c) Digital type ammeter composite type with suitable CT -01 No. (d) Indicator lamp LED type set of three(R,Y,B) - 1 No (e) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,200 Amps, adjustable type 415 volt of breaking capacity not less than 36 KA -05 Nos. (b) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -03 Nos .
Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length-1.50 mtr,height- 2.10 mtr and width- 0.5 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 750 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/platform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories complete all as specified and directed. Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates.
Incoming:- (a) MCCB 4 Pole,500 Amps, adjustable type 415 volt of breaking capacity not less than 50 KA -01 No. (b) On load Changeover switch 415 Volt 4 pole of capacity 500 Amp - 01No (c) Digital type ammeter composite type with suitable CT -01 No. (e) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -08Nos .
Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length-3.50 mtr,height- 2.0mtr and width 0.5 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 1500 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/plateform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories. Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates.
Incomming:- (a) ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 1250 Amps -01 No (b) On load Changeover switch 415 Volt 4 pole of capacity 1250 Amp-01 No (c) Digital type ammeter composite type with suitable CT -01 No. (d) Indicator lamp LED type set of three(R,Y,B) - 1 No (e) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -25 Nos .
Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length- 2.50 mtr,height- 2.15mtr and width- 0.95 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 1500 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/plateform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories complete all as specified and directed. Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates.
Incomming:- (a) ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 1250 Amps -01 No (b) Digital type ammeter composite type with suitable CT -01 No. (c) Indicator lamp LED type set of three(R,Y,B) - 1 No (d) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,250 Amps,adjustable type 415 volt of breaking capacity not less than 50KA -08 Nos . (b) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -03 Nos .
Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length-2.50 mtr,height- 2.15mtr and width-0.95 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 1500 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/plateform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories complete all as specified and directed. Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates.
Incoming:- (a) ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 1250 Amps -01 No (b) Digital type ammeter composite type with suitable CT -01 No. (c) Indicator lamp LED type set of three(R,Y,B) - 1 No (d) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,400 Amps, adjustable type 415 volt of breaking capacity not less than 50 KA -01 No. (b) MCCB 4 Pole,250 Amps, adjustable type 415 volt of breaking capacity not less than 36 KA-02 Nos. (c) MCCB 4 Pole,200 Amps, adjustable type 415 volt of breaking capacity not less than 36 KA-05 Nos. (d) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA-04Nos.
Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length-2.50 mtr,height- 2.15mtr and width- 0.95 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 800 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/plateform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland and housing with the following fitment accessories. Note:- (i) The Panel shall be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing shall be included in quoted rates.
Incoming:- (a) MCCB 4 Pole,630 Amps,adjustable type 415 volt of breaking capacity not less than 50 KA -01 No (b) On load Changeover switch 415 Volt 4 pole of capacity 630 Amp - 01 No (c) Digital type ammeter composite type with suitable CT -01 No. (d) Indicator lamp LED type set of three(R,Y,B) - 1 No Outgoing:- (a) MCCB 4 Pole,160 Amps,adjustable type 415 volt of breaking capacity not less than 36 KA -02 Nos . (b) MCCB 4 Pole,125 Amps, 415 volt of breaking capacity not less than 25 KA -04 Nos . (c) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -04 Nos . (d) MCCB 4 Pole,63 Amps, 415 volt of breaking capacity not less than 16 KA -02 Nos .
Supply,installation,commisioning and testing out door type factory made LT panel of size not less than length 2.50 mtr,height 2.15mtr and width 0.50 mtr made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 50mm x50mmx6mm for mounting and 0.5 mtr above ground level with canopy top,two side ventilators,front and back openable hinged, double door shutters with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 800 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators and separate aluminium bus bar chamber for incoming and outgoing feeder, and suitable size aluminium bus bar for connection of all MCCB incoming side from main bus bar and all internal connection of size not less than 6 sqmm copper conductor cable excluding MCCB and including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/plateform of the LT panel with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland for housing with the following fitment accessories. Note:- (i) The Panel should be CPRI approved. (ii) Panel drawing must be approved by the Engineer-in-charge before fabrication. (iii) Aluminium bus bar will be used for MCCB connection incoming side from main bus bar.(iv) Incoming and outgoing location of all cables on LT panels written with high quality red colour synthetic enamel paint. (v) Excavation required for extra cable connection in new panel incl returning filling & removing included in quoted rates.
Incomming:- (a) MCCB 4 Pole,630 Amps,adjustable type 415 volt of breaking capacity not less than 50 KA -01 No (b) On load Changeover switch 415 Volt 4 pole of capacity 630 Amp - 01 No (c) Digital type ammeter composite type with suitable CT -01 No. (d) Indicator lamp LED type set of three(R,Y,B) - 1 No (e) Digital type Voltmeter composite type with ,0-440 Volts -1 No. Outgoing:- (a) MCCB 4 Pole,200 Amps,adjustable type 415 volt of breaking capacity not less than 36 KA-02 Nos. (b) MCCB 4 Pole,125 Amps, 415 volt of breaking capacity not less than 25 KA -03Nos . (c) MCCB 4 Pole,100 Amps, 415 volt of breaking capacity not less than 16 KA -04Nos . (d) MCCB 4 Pole,63 Amps, 415 volt of breaking capacity not less than 16 KA -02Nos .
Supply,installation,commisioning and testing out door type factory made busbar chamber of size not less than 600x450x300 mm made out of mild steel CRCA sheet of 3.15 mm thick with angle iron frame of size 40mm x40mmx5mm for mounting and 0.5 mtr above ground level with locking arrangement (including 65 mm Godrej Freedom lock with 03 Nos key), weather & vermin proof IP 66 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including 600 Amp aluminium bus bar 4 nos mounted on hygroscopic insulators including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on out side surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation/plateform of the busbar chamber with PCC 1:2:4 type B2 including connection of all incoming and outgoing cables with provision of lugs and cable gland complete all as specified & directed by Engineer-in-Charge.
M&L for Earthing complete with galvanised steel earth electrode plate of size 600x600x6mm thick, buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below normal ground level, connected to galvanised iron strip of size 32 x 6 mm as earth lead up to test point with suitable size GI nuts/bolts, washers,check nut and brazed properly up to main board,LT panel etc and adequate quantity of charcoal and salt 15 cm around the earth plate including earth pit in cement concrete 1:2:4 type B-1 using 20mm graded stone aggregates,40mm thick precast RCC cover in 1:2:4 reinforced with 8mm dia TMT bars 3 Nos both way including CI cover 10 mm thick with hinged and frame of angle iron 25x25x6mm with 6mm dia MS bar handle made to shape, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel and wire mesh and medium grade GI protection pipe 40mm bore up to main board complete all as shown in electrical plate no 3 of MES schedule Part-I , connected to earthing testing point and testing on completion complete all as specified and directed. Note: (i) The unit rate shall include 40 mm dia GI pipe up to 7.5m for protection of earth lead. (ii) The unit rate includes GI main earthing lead/strip of size 32x6 mm from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance of each earthing is recorded more than 3 ohms then the earthing shall be re done by the contractor without any extra cost to the department.
Excavation in trenches not exc. 1.5m wide and not exc. 1.5m deep and getting out in soft/loose soil complete all as specified and directed.
Returning, filling in,including spreading, levelling ,watering and well ramming in layers not exc 25cm thick in soft/loose soil complete all as specified and directed.
Removing surplus soil to a distance not exc 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and directed.
M&L Sand cushioning to under ground cable with locally available dry sand for protection of cable 8cm thick before laying of cable and 15 cm thick after laying and stretching the cable below the bricks/PCC cover ,punning of sand using suitable T&P as per site requirement complete all as specified and directed by Engineer-in-Charge. Note- Punned thickness of sand i.e 18 cm to be consider for measurement purpose.
Supplying and laying un-reinforced precast concrete cable cover class LV, Type 1, flat, size 250x150x40 mm complete all as specified and directed.
M&L for Plain cement concrete 1:2:4 type B1(using 20mm graded crushed stone aggregate) as in benching,coping including weathering slightly rounded or chamfered angles or as per site requirement with necessary plastering work complete all as specified and directed.
Taking out unserviceable cable any type/size from trenches,pole, road,duct etc including necessary joints,U/S fittings and pipes etc complete all as specified and directed.
Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 50 sqmm 3.5 core and connecting up incoming/out going cables connection with suitable size lugs and testing complete all as specified and directed.
All as per item No-18.00 here-in-before but of size 70 sqmm 3.5core.
All as per item No-18.00 here-in-before but of size 95 sqmm 3.5core.
All as per item No-18.00 here-in-before but of size 120 sqmm 3.5core.
All as per item No-18.00 here-in-before but of size 185 sqmm 3.5core.
All as per item No-18.00 here-in-before but of size 240 sqmm 3.5core.
All as per item No-18.00 here-in-before but of size 300 sqmm 3.5core.
M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150mm dia suitable for 0.4mpa working pressure complete all as specified and directed.
Disconnecting and taking out old rusted pipe and material and labour for 50 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including Flat Iron clamps=02 Nos of size 50x6mm, with nut, bolt and washers complete all as specified and directed.
Disconnecting and taking out old rusted pipe and material and labour for 80 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including Flat Iron clamps=02 Nos of size 50x6mm, with nut, bolt and washers complete all as specified and directed.
M&L for Loose filling with aggregates of gauge 40 mm filling in sub stn area as per direction including cleaning all the area,removing vegitation and debris making level, and filling the aggregate up to 200 mm height complete all as specified and directed.
M/S AUTOMATION AND SWITCHGEAR CONTROL (BID ID -3405507)
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3392129)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .