Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance POST BOX NO 539 JUNGLIGHAT P O SRI VIJAYA PURAM 744 103 | SRI VIJAYA PURAM | SOUTH ANDAMAN | ANDAMAN AND NICOBAR ISLANDS | 744103 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance 9 EZRA STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | Admitted-Finance |
Tender Value
₹10.3 L
EMD Value
₹20,575
Closing Date
16 Nov 2022, 10:00 amClosed
EE WSD APWD
EE WSD APWD Port Blair
Supplying, installation, testing and commissioning of 25KVA Diesel Generator Set with 25 KVA AMF Panel for operation at APWD Central Store, Phoenix bay under Section-II of EandM Sub - Division, Workshop Division, APWD, Port Blair
2022_APWD_7887_1
180/NIT/WSD/2022-23
Open Tender
Miscellaneous Works
Works
60 days
Port Blair
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
₹20,575
17 Nov 2022
28 Oct 2022
16 Nov 2022
28 Oct 2022
16 Nov 2022
31 Oct 2022
28 Oct 2022 - 11 Nov 2022
Amount
Supplying, installation, testing and commissioning of "KIRLOSKAR GREEN" Kirloskar Genset Engine Model No. 3R1040 T G1, 42 HP @ 1500 RPM, 3cylinder,vertical, Liquid- cooled diesel oil Engine directly coupled with "KOELGREEN" Make AC alternator, 3-phase, 415 Volts, 50Hz, power factor @ 0.8, Self regulated designed to run at 1500 RPM 20KW/25KVA DG Set, with acoustic enclosure (Sound proof) as per Central pollution control board approved (CPCB-II) approved DG Set etc. as required. Make:- Kirloskar or equivalent.
Supplying, installation, testing and commissioning of microprocessor based Automatic mains failure panel for 25 KVA capacity genset of suitable size with following technical specification.
1) Electricity board supply loading/Unloading in Off/Manual/Auto mode.
4) Interlocking loops with solid state logic circuit to avoid shorting of EB supply side and generator supply side.
5) Short circuit protection system for both EB side and generator side.
6) Over load Protection system for generator.
7) Single phase prevention system.
8) Phase sequence sensing system.
9) Time sensing system for all operation.
10) Digital monitoring system for voltage, amps and frequency.
11) Short circuit protection for DC Circuit.
12) SMPS type automatic battery charging system.
Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
Providing 15 mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
Supplying, installation, testing and commissioning of ASHLOK make SEE brand safe earthing electrode type-19, 50mm dia, length 2 mtrs (short time current -52.6 rms for 1 sec, peak-125.6) with back fill compound including providing masonary enclosure with cover plate having locking arrangement etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Supplying of PVC insulated and PVC sheathed aluminium conductor armoured XLPE power cable of 1.1KV grade of following sizes etc as required. Make :- RR Kabel or equivalent.
a) 3.5 core x 95 sqmm
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
a) 63 mm dia (OD-63 mm & ID-51 mm nominal)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.
a) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
a) Above 35 sq. mm and upto 95 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
a) 3½ X 95 sq. mm (45mm)
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required
a) 80 mm dia
Supplying and laying of one number PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, conforming to IS 694 in the existing RCC/HUME/METAL pipes etc. as required.
a) 4 core x 2.5 sqmm
ISLAND MARINE
Prasur Electricals and Engineering Company
Momani Diesels
BHARAT MULTITECH INDUSTRIES PVT. LTD.
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .