CWE AF BIKANER
HQ CWE (AF) Bikaner
PROVN OF OTM ACCN FOR PAR AT AF STN NAL
2021_MES_443479_1
81465/E8
Open Tender
Civil Works
Lump-sum
270 days
GE AF NAL
As per Appendix A of NIT
8 documents required · 8 mandatory
₹1,000
GE AF NAL
₹1.5 L
Yes
27 Aug 2021
17 May 2021
23 Aug 2021
17 May 2021
20 Aug 2021
6 Aug 2021
18 May 2021 - 10 Jun 2021
60 days
Amount
Schedule 'A' Part-I (BUILDING WORK)
Construction of OTM Accn for PAR at AF Stn Nal complete all as specified and as shown on drawing.
Schedule 'A' Part-II (EXCAVATION & EARTH WORK)
Lump sum price worked out by contractor for "EXCAVATION & EARTH WORK” as listed in Schedule ‘A’ Part- II.
Schedule 'A' Part - III (INTERNAL ELECTRIFICATION)
Lump sum price worked out by contractor for "“INTERNAL ELECTRIFICATION ” as listed in Schedule ‘A’ Part- III.
Schedule 'A' Part - IV (HARDSTANDING/ROAD/ PATH)
Lump sum price worked out by contractor for "HARDSTANDING/ROAD/ PATH” as listed in Schedule ‘A’ Part- IV.
Schedule 'A' Part- V (EXTERNAL WATER SUPPLY)
Lump sum price worked out by contractor for "EXTERNAL WATER SUPPLY" as listed in Schedule 'A' Part- V.
Schedule 'A' Part- VI (EXTERNAL ELECTRIFICATION)
Lump sum price worked out by contractor for "(EXTERNAL ELECTRIFICATION" as listed in Schedule 'A' Part- VI.
Schedule 'A' Part- VII (SMOKE/FIRE DECTECTOR)
Lump sum price worked out by contractor for "SMOKE/FIRE DECTECTOR" as listed in Schedule 'A' Part- VII.
Schedule 'A' Part-VIII (LIGHTING PROTECTION)
Lump sum price worked out by contractor for "LIGHTING PROTECTION" as listed in Schedule 'A' Part-VIII.
Schedule 'A' Part-IX (FIRE POINT)
Lump sum price worked out by contractor for "FIRE POINT" as listed in Schedule 'A' Part-IX.
Schedule 'A' Part -XI (MISCELLANEOUS ITEMS)
Supply and fixing power management box constructred with PVC box consisting with 5 Nos 5 amps switch & 5 Ams socket outlet piano type 230 volt single way controlled with and including one No MCB 32 Amps DP 230 volt 10 KA and indicator lamp with neon lamp and necessery fixing arrangment on wall all as specified and directed.
Supply and fixing power management box constructred with PVC box consisting with 5 Nos 15 amps switch & 15 Ams socket outlet piano type 230 volt single way controlled with and including one No MCB 32 Amps DP 230 volt 10 KA and indicator lamp with neon lamp and necessery fixing arrangement on wall all as specified and directed.
Supply and fixing vertical TPN DB double door suitable for fixing 100 amp MCCB, IP 45 protection with powder coated enclosure 4 way insulated busbar assemblyo rating 200 Amps including MCCB 4 pole, 415 V, 100 A, 16 kA - 01 No complete all as specified and directed. Make : Indo Asian(Optipro) / Legrand/ ABB.
Supply and fix MCB SP 6 to 32 Amps 10 KA 'C' curve 240 volts 50 Hz including making necessary incoming and outgoing connection with suitable size of lugs etc. complete all as specified and directed. Make :- Legrand /L&T/Havells
Supply and fix conventional LED street light 70 watt 230 volts pressure die cast aluminium housing, heat resistant toughened glass with frame, IP protection IP.66 batter optics for uniform distribution having surge protection 5 KV, sealed driver complete all as specified and as directed. Make: Havells/Crompton/Bajaj/Surya
Supply and fix Junction box (Bus bar chamber box) of size 250 x 200x 105 mm made out palstic suitable for 415 Volt, 4 Way TPN aluminium bus bars of capacity 100 amps with 01 No. MCB, SP, 2.5 Amp, 240 volts, 10 KA for controlling the street light complete fixing arrangement to the pole with nut, bolts and washers including providing the electrical connection for incoming / outgoing cable through proper lugs/thimbles complete all as directed. Make:- Syntex /MECO/BRITE/LEGRAND
Supply, installation testing and commissioning of UPS for 30 min back up single phase AC input 160 V to 260 V 50 Hz single phase three wire system ( phase+ Neutral+ Ground) and out put 230 + 10 % V AC 50 Hz single phase sinusoidal waveform, voltage regulation < + 2 % Inverter efficiancy ˃ 85 % overload capability 110% for ˃ 10 minutes total harmonic distortion (THDI) < 5 % at full load working temparature 0-50° C and 95 % RH with and including Battery bank and battery stand. Battery shall be sealed maintanance free (SMFB) of capacity suitable for 5 KVA all as specified details given below: Capacity :- 5 KVA - 4 KW (0.8 pf) Technology :- True Online cable conversion Input voltage 230 V (single phase) Input voltage range :- 160 V to 260 V single phase Input frequency : 50 Hz Input frequency range :- 45 to 55 Hz for working on genarator. Battery Charger :- Type of Charger :- Constant voltage Constant current Battery recharge time to 80 % :- 8 hours after 100 % discharge Rectifier - IGBT
Inverter; - Inverter Tecnology :- IGBT power divices with modulation technology Crest Factor :- 3:1 Out put wave form :- Sinusoidal AC out Put Output Voltage :- 230 VAC three wire Regulation (steady State) :- + 1% Dynamic Regulation + 3 % with 100% step load of 0.8 PF & 3.1 CF and recovery in less than 40 milli seconds. Total harmonic Distortion : <2% for 100 % linear load & <5 % for 100 % non linear load Output Freaquency :- Inverter Mode 50 Hz + 0.1 Hz Overal efficiancy :- ˃/- 88 % Over load capacity :- 110 % for 15 minutes
Bypass :- Static bypass :- Static bypass to ensure seamless transfer to mains. Manual Bypass :- Manual / maitenance bypass Protection and controls :- Input and out put MCB, soft start features for rectifier and inverter, Battery current limitting protection , Built in over load protection, output short circuit protection. Insulation transformer :- In built isolation transformer should be provided at the output. Battery Details :- Battery type : sealed maintenance free battaries. Back up time :- 30 minutes backup Battery Make : Exide Power safe/Amar Raja/Amron Indications :- Main ON /OFF, Inverter normal/fail, battery low, load on Bypass LCD disply :- Touch screen LCD disply for information, Input voltage, Output voltage, Output current, output frequency, Battery voltage, Battery Charge, Discharge current. Audible alarm with indication: - Main failure, battery low, over tmparature, inverter trip, load on Bypass. Communication Port :- Interfaces port :- SNMP Standards (Mandatory):- ISO 9001 and 14001 Cold start in the absence of Mains: - Cold start is available to start on battaries. Acquostic noice level : - </- 60 db Relative humidity :- 95 5 non condensing Cooling : - Forced air cooling.
Supply, installation testing and commissioning of indoor type voltage stabilizer of capacity 75 KVA with control panel (automatic/servo voltage controller three phase 50 Hz for automatic controlling / Regulating of voltage comprising auto transformer , back and boost transformer , wiring and termination all in copper ( with new filtered and dehydrated stabilizer oil, servo motor , auto controlled microprocessor based control circuit ( suitable for supply from DG set also ), auto and bypass arrangement other setting and accessories as under:- (i) Supply and fix digital type volt meter to read input/ output voltage (415 V) , Ammeter suitable CTs and Frequency meter, Mains/low/high limit indicators, Manual increase/ decrease push buttons, Auto / Manuel mode control switch and output adjustment with the following specification and confirming to IS 9815 (Part -1 of 1994) :- (a) Rated Capacity 75 KVA Copper wound oil cooled (b) System 3 Phase, Ac supply , 50 Hz (c) Input Voltage 300 V - 480V (d) Output Voltage set 415 V +/- 1 % sped of correction 8 V/sec (e) Type of cooling Naturally oil cooled (f) Type of system unbalanced (g) Operating Temp 15 to 60° C (h) High /Low voltage cut off featurs (j) Protection Under voltage, over Voltage, Phase failure, reverse phase protection, over load protections. (k) Over Voltage cut off
Material and labour for making of LT Panel by Supply, assembly, erection, testing and commissioning of indoor type floor mounted free standing dust and vermin proof panel/DB with IP-55 protection fabricated and covered with 2 mm thick CRCA sheet for outer & 1.6 mm for inner compartment, including base fram made of MS channel 75 x 40 duly pretreated in seven tank process for de-greasing, de-rusting & Phosphated painted with 2 coats of primer paint then painted with final coat of epoxy based powder coated paint. Panel/DB shall be having front and rear opening for installation of separate cable alleys, busbar chamber and switchgear compartments. Provision in cable alleys to be kept for bottom cable entry for incoming & outgoing cables. A clear space of 200mm to be kept from floor level for switchgear compartment. Air ventilation breathers to be provided for heat dissipation. Suitable sized knock-out holes for cable glands shall be provided. (Location at existing GCA Sub stn) Paints shall be epoxy based DANCOT/Asian make as per shade approved by Engineer in charge. Each compartment shall be numbered/lettered as per the approved drg. Affixing MV danger plate as suitable intervals/locations. Incoming 400 A MCCB, 4P,36KA - 02 Nos with adjustable electronic release, CT's 400/5, Ammeter, ASS, Voltmeter, VSS, Phase Indicating lamps, & control fuses/MCB's etc. as required & detailed in the specifications and indicated on drawings, Make: Legrand or equivalent - 1set. On load Change Over switch 400 Amps 3 phase 440 Volt 50 Hz - 01 No
Material and labour for making of LT Panel by Supply, assembly, erection, testing and commissioning of indoor type floor mounted free standing dust and vermin proof panel/DB with IP-55 protection fabricated and covered with 2 mm thick CRCA sheet for outer & 1.6 mm for inner compartment, including base frame with MS channel 75 x 4 mm duly pretreated in seven tank process for de-greasing, de-rusting & Phosphated painted with 2 coats of primer paint then painted with final coat of epoxy based powder coated paint. Panel/DB shall be having front and rear opening for installation of separate cable alleys, busbar chamber and switchgear compartments. Provision in cable alleys to be kept for bottom cable entry for incoming & outgoing cables. A clear space of 200mm to be kept from floor level for switchgear compartment. Air ventilation breathers to be provided for heat dissipation. Suitable sized knock-out holes for cable glands shall be provided. Paints shall be epoxy based DANCOT/Asian make as per shade approved by Engineer in charge. Each compartment shall be numbered/ lettered as per the approved drg. Affixing MV danger plate as suitable intervals/locations. Incoming 160 A MCCB, 4P,36KA with adjustable electronic release, CT's 160/5, Ammeter, ASS, Voltmeter, VSS, Phase Indicating lamps, & control fuses/MCB's etc. as required & detailed in the specifications and indicated on drawings, Make: Legrand or equivalent - 1set.
(xix) Start & stop push button -02 Nos (xx) Analogue Frequency meter -01 Nos (xxi) Power contractor 140 A, 3 pole, 415 V for DG set - 01 No (xxii) Power contractor 140 A, 3 pole, 415 V for main - 01 No (xxiii) MCCB 160 A 25 KA 3 pole Thermal for Main& DG supply - 02 Nos (xxiv) Control Relay -02 set (xxv) Change over switch 160 A 4 pole for bye pass Main Supply - 01 No (xxvi) Change over switch 160 A 4 pole for bye pass DG supply - 01 No (xxvii) Linking bus bar 200 A 3 strips & Neutral 100 A aluminium 01 No (xxviii) Acoustic enclosure with natural air curculation without loss of any power to ventilation fan. The enclosure shall be modular in construction with hinged bolted structure to provide easy dismantling and shall be made out of high quallity CRCA steel sheet of 1.6mm thick with sufficient accessories for maintenance work openable and lockable door air tight gasket interior lightening arangement of 20 W fitting with On/Off switch to meet latest emission norms. (xxix) Indicator lamp for for mains, DG, Load on Main, load on DG, etc as per standard norms.
Supply installation testing and commissioning of oil cooled isolation transformer indoor type of capacity 75 KVA 3 phase 50 Hz copper wounded oil cooled, class of insulation B metalic body duly powder coated designed for input voltage range 415 + 5 % and out put voltage range ratio 1:1, vector group Dyn 11 , Delta - Star indoor type IP-42 (CPRI approved/other Govt organisation with frist filling of transformer oil of requistic dielectric strength up to level, efficiency more than 95 % separate neutral bushing shall be brought out for earthing potential difference between neutral to earth less than one volt with all standard fittings like digital temparature meter, adequate number of cooling radiators, lifting hooks, aearthing terminals as per IS complete with cover load/ short circuit protection. The Isolation Transformer can reduce a stable supply to the circuit and the connected equipments, the primary and secondary will be made out of two electromafnets that are copper wound around each other in order to allow the primary coil to induce a current in the secondary coil.
Material and labour straight through cable joint kit by using M-seal Kastex cable accessories based on cast resin system ie (electrical insulation, mechanical protection and moisture imperviousness to the joint) for LV PVC / XLPE cable up to 400 Sq mm 3.5 core 1100 volt grade at site (technical / domestic area) complete all as specified and directed for the following sizes:- Make: Raychem / Denson/ M-seal.
Material and labour boring of road crossing of size 80 mm dia at suitable depth not less than 1 m by mechanical using machinery complete in any type of soil strata without damaging the surface for passing pipes / cables etc including removing excavated soil to a distance n exc 50m complete all as specified and as directed. Note : (i) Location of boring holes shall be decided by the Engr-in-Charge as per requirement, nothing extra shall be payable on account of variation in length of crossing of road etc. (ii) During boring soil strata may be changed, hence nothing extra shall be paid to the contractor for boring of holes through different strata/different type of soil. Tenderer is hereby advised to keep in mind this aspect while quoting his rates.
Material and labour for cutting existing CI / GI pipe line 80 mm dia and insert Tee suitable for new connection with 40 mm dia GI pipe including all fixing arrangement all as specified and directed.
Supply and fix PVC insulated sheathed FRLS 2 core 1.5 sqmm 2 core copper conductor cable through metalic steel conduit 20 mm dia ISI marked complete all as specified and as directed.
Fixing only Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 270 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity suitable for 1.5 TR Air conditioner complete all as specified and as directed. Note : Item shall be issued under Schedule B store for free for fixing only.
Fixing only Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 270 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity suitable for 2.0 TR Air conditioner complete all as specified and as directed. Note : Item shall be issued under Schedule B store for free for fixing only.
Supply and fixing energy saving decorating box type batten light fitting 230 volts surface mounted complete with high effeciency PMMA diffuser soft glare free light LED lamp 20 watt blue coloured end caps with all accessories, pre- wired, including providing flexible copper wire twin core cable complete all as specified and directed by enginer in charge. Make :- Havelles/Philips /Wipro/ crompton
Supply and fixing Energy saving ceiling fan 1200 mm sweep 50 watts, white / brown / ivory color with ISI marking and BEE 5 star rated complete including provision of copper wire 0.5sqmm 3 core, connected from ceiling rose to fan and marking MES No in black paint complete all as specified and as directed. Make : Havells/Khaitan / Usha / Bajaj .
Supply and fixing heavy duty exhaust fan 450 mm sweep 1400 rpm, 230 V 50 Hz metal body with self opening louvers incl all mounting accessories and making connections using three core copper conductor cable connected from ceiling rose to fan and marking MES No in black paint and making hole / opening of suitable size in existing wall and making good in cement mortar 1:4 and matched with existing surface complete all as specified and as directed. Make : Havells/Khaitan / Usha / Bajaj / Crompton.
Supply and fix as in repairs conventional LED lightfitting 45 watt 230 volts pressure die cast aluminium housing, heat resistant toughened glass with frame, IP protection IP.66 batter optics for uniform distribution having surge protection 5 KV, sealed driver complete all as specified and as directed. Make: Havells/Crompton/Bajaj/Surya
Material and labour for Point wiring (concealed) with PVC insulated fire retardant low smoke (FRLS) multi stranded copper conductor cable of 1.5 sqmm in and including PVC conduit heavy duty (ISI mark) on concealed wiring and pressed steel terminal boxes (for mounting switches / sockets /regulators / ceiling roses etc) made out of MS sheet not less than 1.6 mm thick depth including painting with one coat of red oxide primer on internal and external surface covered with 3mm thick laminated plastic sheet ISI marked including 1.5 sqmm PVC insulated fire retardant low smoke (FRLS) multi stranded copper conductor cable as earth continuity wire connected to common earth and each terminal box/fitting all as specified and directed. Note :- (i)The wiring shall be provided in standard colour code i.e. Red for Phase, Black for Neural and Green for earth. (ii) The quoted rate is deemed to include for cutting/chasing for concealing terminal boxes etc and making good the surface to match the existing surfaces. (iii) In case of ceiling portion where concealed is not possible, the surface conduit shall be provided as directed. (iv) The earth wire shall be connected to common earth and each terminal boxes and fitting all as directed. (a) One light point controlled by one switch.
All as per description of serial item No. 10.29 here in before but One ceiling fan/wall fan point controlled by one switch complete all as specified and as directed.
All as per description of serial item No. 10.29 here in before but One exhaust fan point contrelled by one switch complete all as specified and as directed.
All as per description of serial item No. 10.29 here in before but One switch socket outlet 3 pin 6 Amp on same board complete all as specified and as directed.
All as per description of serial item No. 10.29 here in before but one 3 pin socket outlet 5 Amp on independent board complete all as specified and as directed.
All as per description of serial item No. 10.29 here in before but for One 3-pin socket outlet 15 Amp on independent board with 4 sqmm FRLS cable including 4.0 sqmm FRLS multistranded copper cable as earth continuity wire complete all as specified and as directed.
Supply and fix socket out let 5 pin 6 amp multipurpose, flush type complete all as specified and directed.
Supply and fix Ceiling rose surface Bakelite 65 x 50 mm three terminals complete all as specified and directed.
Material and labour for earthing complete with GI earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly in ground vertical position, earth pit not less than 3.00 Mtr deep below ground level with top edge of the plate not less than 2.4 m below ground level. The earth plate to be connected with galvanised iron earthing wire of size 4 mm dia by means of nuts, bolts, chcek nuts and washers made of galvanised iron or steel earthing strip to be protected by galvanised iron pipe 40 mm bore (medium grade) up to ground level and thereafter with 40mm dia HDPE pipe up to test point. Earthing shall be include with providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) up to 90 cm all around earth plate further filled with 60 cm thick Tibba sand Earthing shall also be include for providing concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work complete all as specified and directed.
Material and labour chemical Earthing complete with copper earth plate of size 900 mm x 600 mm x 5.00 mm thick buried directly in ground vertically in pit of depth not less than 3.6 metre below normal ground level with top edge of the earth plate at a depth not less than 3.0 metre below normal ground level surrounded from all sides of 15 cm with backfil chemical compound, earth electrode connected to copper strip 32 x 6 mm as earthing lead by exhothermic weld protected by galvanized steel pipe 50 mm bore (light grade) connected to machinery/equipment all as shown in electrical plate No. 3 of SSR-2010 Part I and including necessary excavation and earth work in any type of soil, PCC (1:3:6) type C-1 chamber, RCC cover 50mm thick (1:2:4) type B-1 reinforced with 6 mm dia MS round bars @ 15 cm c/c both ways and MS frame of suitable size made of angle iron 50mm x 50mm x 6 mm, complete all as specified and directed. (for PAR Eqpt) Note :- (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point. (ii) Earth pit shall be constructed minimum 0.5 metre away from earth. (iii) The quantity of backfill chemical compound and depth of earth pit shall be increased by the contractor to ensure earth resistance less than 1 ohm on completion and testing without any extra cost to Govt
Material and labour earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick, burried directly in ground in vertical position, earth pit not less than 3.65 m deep below ground level with top edge of the plate not less than 2.90 m below ground level. The earth plate to be connetced with copper earthing strip of size 20 mmx 3mm thick by means of brazing between copper strip and earth plate min 45 cm in vertical length and copper strip also to be joined by brazing only. The copper earthing strip to be protected by galvanised iron pipe 40 mm bore (medium grade) up to ground level and thereafter with 40mm dia HDPE pipe up to test point. Earthing shall include provision of funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) up to 90 cm all around earth plate further filled with 60 cm thick Tibba sand and 2nd layer with 30 cm of Magnesium sulphate powder (compact thickness ), 3rd layer with tibba sand up to ground level. Earthing shall also include concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 Mtr etc all as shown on electrical plate No. 3 of MES Schedule Part-I complete to obtain less than 2 Ohm earth resistance value, complete all as specified. Note : (i) Cost of this items includes the scope of earth work, charcoal, salt, PCC, RCC pit cover of required size. (ii) Tibba sand shall be arranged by the contractor at his own and the cost thereof shall be deemed included in unit quoted rate of this item. (iiI) Electrical Plate No. 3 referred in the item above is mainly for earth chamber.
Material and labour for earthing complete with GI earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly in ground vertical position , earth pit not less than 3.00 m deep below ground level with top edge of the plate not less than 2.4 m below ground level. The earth plate to be connetced with galvanised iron earthing strip of size 25 mm x 4 mm by means of nuts, bolts, chcek nuts and washers made of galvanised iron or steel earthing strip to be protected by galvanised iron pipe 40 mm bore (medium grade) up to ground level and there after with 40mm dia HDPE pipe up to test point. Earthing shall be include with providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) up to 90 cm all around earth plate further filled with 60 cm thick Tibba sand Earthing shall also be include for providing concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-enforced with 8mm dia TMT bar @ 15 cm C/C both ways and suitable handle made of 10mm dia) including necessary earth work all as specified and directed.
Supply, install and erect in true vertical position steel tubular swaged welded poles single swan neck 9.0 m long complete with MS base plate of 6 mm thick of size 300mm x 300mm, finial taper plug, pole cap, bolts, nuts and washers and screwed, pole made out of ERW MS tubing conforming to IS-2713 ( Part II),1980 type 410-SP-31, L.T pole including drilling of holes of required size and Nos for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embedded in concrete, painting with two coats of aluminium paint over a coat of primer incl excavation incl PCC complete in post hole in any type of strata, PCC 1:2:4 foundation, filling, in post holes with PCC 1:3:6 and cylindrical coping with PCC 1:2:4, of 30cm dia and 45cm high complete all as specified and directed (Note : Unit rates of this item includes the cost of PCC in foundation, PCC coping and excavation and earthwork).
Supply and fix Rigid steel conduit Stove enamelled, black of size 20mm dia complete all as specified and directed.
Fixing and installation only air conditioner 1.5 TR capacity air cooled hi wall split type remote controlled with indoor and outdoor units duly connected with inlet & outlet gas copper tubes duly insulated with insulation material complete and with in-built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and BEE 3.2., gas filling, fixed on MS stand fixed to wall/floor with nuts and bolts, PVC insulated sheathed connection cable 3 core for indoor & outdoor units, PVC flexible water pipe upto floor level, making necessary holes for passing of pipes and making good complete all as specified and directed. Note : Item shall be issued under Schedule B store for free for fixing only. Note: The cost of condenser / refrigerant tubes between indoor and outdoor unit, in excess of standard length 3 mtrs, shall be deemed included in the unit quoted rate of this item. Contractor is advised to visit the site before quoting the rates. Nothing extra shall be admissible for the tubes provided in addition to those supplied by the manufacturer with the AC.
Fixing and installation only air conditioner 2 TR capacity air cooled hi wall split type remote controlled with indoor and outdoor units duly connected with inlet & outlet gas copper tubes duly insulated with insulation material complete and with in-built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2., gas filling, fixed on MS stand fixed to wall/floor with nuts and bolts, PVC insulated sheathed connection cable 3 core for indoor & outdoor units, PVC flexible water pipe upto floor level, making necessary holes for passing of pipes and making good complete all as specified and directed. Note : Item shall be issued under Schedule B store for free for fixing only. Note: The cost of condenser / refrigerant tubes between indoor and outdoor unit, in excess of standard length 3 mtrs, shall be deemed included in the unit quoted rate of this item. Contractor is advised to visit the site before quoting the rates. Nothing extra shall be admissible for the tubes provided in addition to those supplied by the manufacturer with the AC.
Supply and fix sheet metal enclosure single pole and neutral enclosure with two pin and earth plug and socket complete with provision for fixing of one MCB SP 16 Amps complete all as specified and directed.
Supply and fix rotational mouled polyethylene water storage tanks (Cylindrical vertical with closed tap) hoisted and fixed in position all as specified in SSR Part 1 of capacity 1000 Ltrs complete with ball valve with polythene float and fly nut complete suitable for 25 mm dia GI pipe including CC foundation 150mm height on RCC roof all as specified and as directed.
Supply, installation testing and commissioning of hand operated chain pulley block of capacity of 3 ton double fall type ISI marked made of mild steel used for heavy duty weight lifing purpose as per IS : 3832 : 2005 all as specified details given below :- (a) Lifting height - 3 mtr (b) Load chain- the material for load chain used in the chain pulley block shall be of high tensile steel as per grade 80 of IS : 6216. The chain shall be manufactured and tested as per IS : 6216. (c) Hand chain dia- The hand chain shall be of Grade 30 of IS : 2429 Part-II hand chain need not be load tested. (d) Painting of hoist shall be done as per standared of manufacturer's. Make : INDEF/TAPARIA/BEMCO
Material and labour for PCC 1:2:4 type B 1 (20mm grade aggregate) Note :- PCC blocks of size 300 mm x 300 mm x 300 mm to be provided for each termination complete all as specified and directed. (PCC 0.027 Cum is required for each block).
Supply and fix as in repairs HDPE pipe medium grade external dia 50 mm, exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. complete all as specified and directed.
M/s Madan Gopal Vyas
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .